Triconex Tricon v9 User manual

Field Terminations Guide
for Tricon v9–v10 Systems
Assembly No. 9700052-018
February 2009
Tricon Version 9–10 Systems

Information in this document is subject to change without notice. Companies, names and data used in
examples herein are fictitious unless otherwise noted. No part of this document may be reproduced or
transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express
written permission of Invensys Systems, Inc.
© 2006–2009 by Invensys Systems, Inc. All rights reserved.
Triconex, Tricon, Trident, TriStation 1131, TriStation MSW, and CEMPLE are trademarks of Invensys plc,
its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
Document No. 9720052-018
Printed in the United States of America.

Field Terminations Guide for Tricon v9–v10 Systems
Contents
Preface ix
Summary of Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Product and Training Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
We Welcome Your Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Chapter 1 Introduction to Field Terminations 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
External Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Basic Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
RG 1.180 Termination Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hazardous Location (Nonincendive) Termination Panels . . . . . . . . . . . . . . . . . . . . . . 4
Termination Panels with Interposing Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Bypass Panel for Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Termination Panel with RTD/TC/AI Input Signal Conditioning. . . . . . . . . . . . . . . . 6
Termination Panel 9251-210 for Digital Output Module 3603B . . . . . . . . . . . . . . . . . . 6
Termination Panel 9863-710 for Analog Output Module 3806E. . . . . . . . . . . . . . . . . . 6
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Interface Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fanned-Out Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Special Cables (Relay Loopback). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 2 Field Termination Options and Installation 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Determining Field Termination Options by Module Part Number. . . . . . . . . . . . . . . . . . . 10
Determining Field Termination Options by Module Type. . . . . . . . . . . . . . . . . . . . . . . . . . 14
Digital Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pulse Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pulse Totalizer Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Supervised Digital Output Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Supervised/Non-Supervised Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . 17
Dual Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Relay Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Thermocouple Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

iv Contents
Field Terminations Guide for Tricon v9–v10 Systems
Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
HART Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installation and Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installing a Termination Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Removing or Replacing a Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installing a Fanned-Out Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Removing or Replacing a Fanned-Out Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 3 Digital Input Termination Panels 33
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
16-Point Commoned Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9561-810 (115 V, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9562-810 (48 V, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9563-810 (24 V, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
9563-910 (24 V, commoned, resistor protected, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . 43
32-Point Commoned Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
9565-810 (48 VDC, commoned, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9566-710 (24 VDC, commoned, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
9566-810 (24 VDC, commoned, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
16-Point Non-Commoned Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9561-110 (115 V, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Basic Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
9551-110 (115 V, basic, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
9552-610 (48 V, basic, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9553-610 (24 V, basic, 16/32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9750-310 (24 VDC, basic, 32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
9750-410 (48 VDC, basic, 32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Pulse Input and Pulse Totalizer Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
9753-110 (8 PI pts./16 PTI pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Bypass Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
BP9228-010 (24 V, bypass, 32 pts., for 32 pt. modules). . . . . . . . . . . . . . . . . . . . . . . . . 76
BP9229-010 (24 V, bypass, 32 pts., for 64 pt. modules). . . . . . . . . . . . . . . . . . . . . . . . . 78
Chapter 4 Digital Output Termination Panels 81
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8-Point Commoned Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
9661-510 (115 VAC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9661-810 (120 VDC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9662-710 (24 VDC low-power, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9662-910 (24 VDC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9667-910 (48 VDC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
16-Point Commoned Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9661-610 (115 VAC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9661-910 (120 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

Contents v
Field Terminations Guide for Tricon v9–v10 Systems
9662-610 (24 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9662-810 (24 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9663-610 (115 VAC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
9664-810 (120 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
9667-810 (48 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
16-Point Non-Commoned Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
9251-210 (120 VDC, non-commoned, 16 pts., 3603B module). . . . . . . . . . . . . . . . . . 122
9661-110 (115 VAC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
9662-110 (24 VDC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
9664-110 (115 VAC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
9667-110 (48 VDC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
9668-110 (non-commoned relay output, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Basic Digital Output Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
9651-110 (basic digital/relay output, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
9652-610 (48 VDC, basic, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
9653-610 (24 VDC, basic, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Commoned Interposing Relay Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
9670-610 (115 VAC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . . 150
9671-810 (24 VDC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . . . 153
9672-810 (48 VDC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . . . 157
9673-810 (120 VDC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . . 160
Non-Commoned Interposing Relay Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
9670-110 (115 VAC, non-commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . 164
Chapter 5 Analog Input and Analog Output Termination Panels 169
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
16-Point Current Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
9761-210 (current input, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
9761-410 (current input, 0–10 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
9762-210 (current input, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
9762-410 (current input, 0–10 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
9771-210 (current input, 0–5 VDC, user configurable, 16 pts.) . . . . . . . . . . . . . . . . . 183
32-Point Current Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
9750-210 (current input, 0–5 VDC, basic, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
9760-210 (current input, 0–5 VDC, 32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
9760-410 (current input, 0–10 VDC, 32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
9765-210 (3-wire current input, 0–5 VDC, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Thermocouple Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
9765-610 (TC input, upscale/downscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
9766-210 (TC input, upscale, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
9766-510 (TC input, downscale, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Voltage Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
9750-810 (0–5 VDC/0–10 VDC voltage input, basic, 32 pts.) . . . . . . . . . . . . . . . . . . 209
9753-110 (0–5 VDC/0–10 VDC voltage input, basic, 16 pts.) . . . . . . . . . . . . . . . . . . 211

vi Contents
Field Terminations Guide for Tricon v9–v10 Systems
9763-810 (0–5 VDC/0–10 VDC voltage input, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . 214
RTD/TC/AI Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
9764-310 (RTD/TC/AI input, 0–5 VDC, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Analog Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
9863-710 (3806E module, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
9853-610 (current output, basic, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
9871-810 (3807 module, 4 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Chapter 6 Hazardous Location (Nonincendive) Termination Panels 243
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Field Wiring in Hazardous Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Cable and Load Parameters (Entity Parameters) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Electrical Code Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Analog Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
9791-610 (4-20 mA, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
9787-110 (0-5 VDC voltage input, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
9785-610 (TC input, downscale, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
9784-610 (TC input, upscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
9786-110 (TC input, upscale/downscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
9789-610 (4-20 mA, high-density, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
Analog Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
9861-610 (3805E/H module, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
9871-810 (3807 module, 4 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
9572-610 (24 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
9570-610 (24 VDC, high-density, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
9571-610 (24 VDC, fail-safe, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Digital Output Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
9671-610 (24 VDC, commoned, supervised, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . 286
Pulse Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
9793-110 (pulse input, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Chapter 7 RG 1.180 Termination Panels 295
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
Analog Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
9790-610 (4-20 mA, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
9795-610 (4-20 mA, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
9792-610 (4-20 mA, 0-5 VDC, 16 pts., user-configurable, 48 VDC field) . . . . . . . . . 306
9783-110 (0-5 VDC voltage input, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
9782-110 (TC input, upscale/downscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
Analog Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
9860-610 (3805E/H module, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Pulse Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
9794-110 (pulse input, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323

Contents vii
Field Terminations Guide for Tricon v9–v10 Systems
RTD/TC/AI Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Chapter 8 Fanned-Out Cables 327
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328
Description of Fanned-Out Cables (9101-010). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328
Fanned-Out Cables with Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Connecting 32-Point Digital Input Modules to Fanned-Out Cables . . . . . . . . . . . . 329
Connecting 64-Point Digital Input Modules to Fanned-Out Cables . . . . . . . . . . . . 333
Fanned-Out Cables with Digital Output Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Connecting 16-Point Digital Output Modules to Fanned-Out Cables. . . . . . . . . . . 335
Connecting 32-Point Digital Output Modules to Fanned-Out Cables. . . . . . . . . . . 341
Connecting 32-Point Relay Output Modules to Fanned-Out Cables. . . . . . . . . . . . 344
Appendix A Re-Keying Connectors 347
Re-Configuring a System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
I/O Connector Key Positions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
Re-Keying a Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Re-Keying a Fanned-Out Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
Appendix B Fanned-Out Cable Pinouts 355
Signal Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
Connector #1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Connector #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359
Appendix C Recommended Replacement Parts 361
Appendix D Panel Dimensions 365
Appendix E Shield Ground 369
Appendix F Panel Labels 371
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
16-Point Non-Commoned DI/DO/RO Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
16-Point Non-Commoned AI/TI Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
16-Point Commoned AI/DI/DO Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
32-Point Commoned AI/DI Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
16-Point Commoned AI ATEX/RG 1.180 Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377
16-Point RTD/TC/AI Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
Appendix G Part Number Cross-Reference 379
Appendix H Minimum Bend Radiuses of Cables 383
Appendix I Low-Density Chassis I/O Module Compatibility 387
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388

viii Contents
Field Terminations Guide for Tricon v9–v10 Systems
Module Upgrades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
ETP Upgrades for Compatibility with I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
3700 and 3700A AI Module ETP Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
3704E AI Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
3604E DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
3614E DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394
3615E DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
3624 DO Module ETP Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
Appendix J Using V8 ETAs with v9/v10 Systems 399
Appendix K Warning Labels 403
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
General Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
Hazardous Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406
Hot Surface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407

Field Terminations Guide for Tricon v9–v10 Systems
Preface
This guide includes information on external termination products for Tricon v9 systems and
Tricon v10 systems.
Summary of Sections
•Chapter 1, Introduction to Field Terminations—introduces the Triconex external field
termination products for the Tricon system.
•Chapter 2, Field Termination Options and Installation—provides information for
determining field termination options using I/O module part numbers or I/O module
types, and describes how to install and remove termination panels and fanned-out
cables.
•Chapter 3, Digital Input Termination Panels—describes external field termination
panels that you can use with digital input modules.
•Chapter 4, Digital Output Termination Panels—describes external field termination
panels that you can use with digital output modules.
•Chapter 5, Analog Input and Analog Output Termination Panels—describes external
field termination panels that you can use with analog input modules and analog output
modules.
•Chapter 6, Hazardous Location (Nonincendive) Termination Panels—describes
external field termination panels that you can use in hazardous locations.
•Chapter 7, RG 1.180 Termination Panels—describes external termination panels that
you can use in nuclear power plant EMI/RFI environments.
•Chapter 8, Fanned-Out Cables—describes fanned-out cables that you can use with
digital I/O modules.
•Appendix A, Re-Keying Connectors—explains how to re-key connectors by module
type and voltage to protect modules from inadvertent connection to inappropriate
voltages.
•Appendix B, Fanned-Out Cable Pinouts—provides pin-out information for connecting
fanned-out cables and basic termination panels.
•Appendix C, Recommended Replacement Parts—contains a list of recommended parts
that can be used to replace existing Tricon parts, or customize a Tricon system.
•Appendix D, Panel Dimensions—specifies the physical dimensions of the different
types of termination panels.
•Appendix E, Shield Ground—illustrates how to connect a shield to earth.
•Appendix F, Panel Labels—illustrates how to apply termination panel labels.

xPreface
Field Terminations Guide for Tricon v9–v10 Systems
•Appendix G, Part Number Cross-Reference—identifies the ETA part number and cable
part number for each termination panel model number.
•Appendix H, Minimum Bend Radiuses of Cables—identifies the minimum bend
radiuses of cables.
•Appendix J, Using V8 ETAs with v9/v10 Systems—identifies version 8 “low-density”
external termination assemblies (ETAs) that can be used with version 9 systems.
•Appendix K, Warning Labels—describes General Hazard, Hazardous Voltage, and Hot
Surface warning labels.
Related Documents
• Planning and Installation Guide for Tricon v9–v10 Systems
• Safety Considerations Guide for Tricon v9–v10 Systems
•TriStation 1131 Developer’s Guide, v4.3
Product and Training Information
To obtain information about Triconex products and in-house and on-site training, see the
Triconex Web site or contact your regional Triconex support office.
Web Site
http://www.ips.invensys.com/en/triconex
Technical Support
Customers in the U.S. and Canada can obtain technical support from the IPS Global Client
Support (GCS) center at the numbers below. International customers should contact their
regional support center.
Requests for support are prioritized as follows:
• Emergency requests are given the highest priority
• Requests from participants in the System Watch Agreement (SWA) and customers with
purchase order or charge card authorization are given next priority
• All other requests are handled on a time-available basis
If you require emergency or immediate response and are not an SWA participant, you may
incur a charge. Please have a purchase order or credit card available for billing.
Telephone
Toll-free number 866-746-6477, or
Toll number 508-549-2424 (outside U.S.)

Preface xi
Field Terminations Guide for Tricon v9–v10 Systems
Fax
Toll number 508-549-4999
Web Site
http://support.ips.invensys.com (registration required)
E-mail
We Welcome Your Comments
To help us improve future versions of Triconex documentation, we want to know about any
corrections, clarifications, or further information you would find useful. When you contact us,
please include the following information:
• The title and version of the guide you are referring to
• A brief description of the content you are referring to (for example, step-by-step
instructions that are incorrect, information that requires clarification or more details,
missing information that you would find helpful)
• Your suggestions for correcting or improving the documentation
•TheversionoftheTriconex hardware or software you are using
• Your name, company name, job title, phone number and e-mail address
Send e-mail to us at:
Please keep in mind that this e-mail address is only for documentation feedback. If you have a
technical problem or question, please contact the IPS Global Client Support (GCS) center. See
Technical Support on page x for contact information.
Or, you can write to us at:
Attn: Technical Publications
Triconex
15345 Barranca Parkway
Irvine, CA 92618
Thank you for your feedback.

xii Preface
Field Terminations Guide for Tricon v9–v10 Systems

2Chapter 1 Introduction to Field Terminations
Field Terminations Guide for Tricon v9–v10 Systems
Overview
This chapter introduces the Triconex external field termination products for the Tricon system.
All cables and termination panels are built to withstand harsh industrial environments. The
environmental specifications for components used on these products are the same as for a
Tricon chassis. For more information, see the Planning and Installation Guide for Tricon v9–v10
Systems.

External Termination Panels 3
Field Terminations Guide for Tricon v9–v10 Systems
External Termination Panels
An external termination panel (ETP) is an electrically-passive printed circuit board (PCB) to
which field wiring is easily attached. A panel connector, terminal blocks, and optional
components are mounted to the PCB and enclosed in a DIN-rail compatible plastic housing. A
termination panel and associated cable pass input signals from the field directly to an input
module, or pass output signals from an output module directly to field wiring. This
arrangement permits the removal or replacement of I/O modules without disturbing field
wiring.
Standard termination panels are best for remote marshaling of field wiring where maximum
flexibility, high density and simple maintenance is desired. Standard termination panels allow
you to marshal field signals in a separate enclosure up to 99 feet (30 meters) from a Tricon.
A standard termination panel consists of a PCB with all necessary components—such as two-
piece terminal blocks, resistors, fuses and blown-fuse indicators—mounted on a DIN-rail
compatible plastic housing. The housing snaps into mounting rails in accordance with
DIN 50 22.
Compression terminals on the standard panel are designed for use with 24- to 12-gauge (0.3
mm2to 2.1 mm2) wiring. Some panels have an optional current-limiting series resistor, others
have a fuse with a blown-fuse indicator, to protect the field wiring and field device.
Standard termination panels are pre-configured for a specific application. For instance,
commoned standard termination panels can be ordered with commoned power-and-return, or
redundant DC power configurations with a diode-ORing. The thermocouple input termination
panel provides cold-junction temperature sensors and can be ordered with upscale, downscale,
or programmable burnout detection. A standard termination panel for analog voltage inputs
provides commoned or non-commoned signal returns, while the current-mode version has a
precision resistor at each input point to convert current to voltage.
Each standard termination panel is packaged with a matched interface cable that connects the
panel to the backplane of a Tricon chassis. A female connector at one end of the cable is keyed
to match the male connector on the Tricon backplane. A male connector on the other end of the
cable attaches to the standard termination panel.
In addition to standard termination panels, there are other types of termination panels,
including:
• Basic termination panels
• Hazardous location (nonincendive) termination panels
• RG 1.180 Termination Panels
• Termination panels with interposing relays
• Bypass panels for digital inputs
• Termination panels with RTD/TC/AI input signal conditioning
• Termination panels for 3603B digital output modules
• Termination panels for 3806E analog output modules

4Chapter 1 Introduction to Field Terminations
Field Terminations Guide for Tricon v9–v10 Systems
Basic Termination Panels
Basic termination panels are a low-cost means of connecting field wiring to a Tricon. Basic
termination panels allow you to marshal field signals in a separate enclosure up to 99 feet (30
meters) from a Tricon chassis.
A basic termination panel consists of a PCB—with panel connector and terminal blocks—
mounted on a DIN rail-compatible plastic housing. The housing snaps onto mounting rails in
accordance with DIN 50 022. Current-to-voltage conversion resistors are also mounted on
analog input panels configured for current input. You must provide any other components
required for your application.
The panel connector and terminal blocks are directly interconnected via the PCB. The
compression terminals on the terminal blocks are designed for use with 24- to 12-gauge (0.3
mm2to 2.1 mm2) wiring.
Refer to Appendix B, Fanned-Out Cable Pinouts for signal labels and connector pin numbers.
Each signal label indicates the corresponding screw terminal on the termination panel. The
panel connector’s pin numbers match those on the Tricon backplane’s connector.
A basic termination panel is packaged with a cable that connects between a Tricon chassis
backplane and the basic termination panel. A female connector on one end of the cable is keyed
to match the male connector on the Tricon backplane. A male connector on the opposite end of
the cable is keyed to match the male connector on the termination panel.
Basic termination panels are available in these configurations:
• Digital input panels
• Digital output panels
• Relay output panels
• Analog input panels
•Analogoutputpanels
• Pulse input panels
• Pulse totalizer input panels
RG 1.180 Termination Panels
RG 1.180 termination panels are suitable for use in applications that need to meet the
requirements of Regulatory Guide 1.180, “Guidelines for Evaluating Electromagnetic and
Radio-Frequency Interference in Safety-Related Instrumentation and Control Systems, Revision
1” published by the U.S. Nuclear Regulatory Commission.
Hazardous Location (Nonincendive) Termination Panels
Hazardous location (nonincendive) termination panels are suitable for use in Zone 2, and Class
1, Division 2 field circuits. These panels contain extra circuitry designed to limit power available
to the field terminals and have been examined and certified by TÜV Rheinland as being
nonincendive. This guarantees that if the field wires are accidentally opened, shorted, or

External Termination Panels 5
Field Terminations Guide for Tricon v9–v10 Systems
grounded, and the Tricon is operating normally, the wiring and attached devices will not
release sufficient energy to cause ignition in the specified flammable atmosphere.
Termination Panels with Interposing Relays
Termination panels with interposing relays can be used with most digital output modules and
are recommended for these applications:
• Load currents greater than 2 amps
• Field voltages greater than 115 VAC
• Voltage-level conversions
• Motor-starter circuit compatibility
Interposing relay panels are available in these configurations:
•16-pointcommoned
• 16-point non-commoned
The digital outputs of the interposing relays are not fault-tolerant. However, each relay
provides an auxiliary contact that can be fed into a digital input to send a loopback signal to the
control program. A user-written loopback check in the control program can ensure that the relay
has achieved its commanded state. The loopback cable must be ordered separately.
Each interposing relay panel provides the capability to common power and return through a
factory-mounted bus-bar arrangement.
Each interposing relay panel consists of:
• A 7 in x 19 in (36 cm x 48 cm) rack-mountable panel with terminals for 16 digital
outputs and 16 digital inputs.
• Two ELCO connectors mounted on the panel for connecting to digital input modules
using digital input cables 9141-010, 9142-010, or 9143-010.
• An EIA standard RS-310-C plate on which the termination panel is mounted.
• A digital output module and a cable compatible with the selected coil voltage.
Bypass Panel for Digital Inputs
Bypass termination panels can be used to connect digital inputs using a bank of 32 pre-wired
switches. Bypass panels have a master keyswitch and terminals for redundant +24 VDC power
sources. Each input point contains an ON status indicator and can be energized only if the
master keyswitch is ON and the corresponding point switch is ON. Each point has a location for
a user-definable label.
Each bypass termination panel comes with one or two 10-foot (3-meter) cables for connecting
the termination panel to a Tricon backplane.

6Chapter 1 Introduction to Field Terminations
Field Terminations Guide for Tricon v9–v10 Systems
Termination Panel with RTD/TC/AI Input Signal Conditioning
Termination panels which use industry-standard analog signal conditioners provide a flexible,
user-configurable interface to resistive thermal devices (RTDs), thermocouples, and 4-20 mA
transmitters. Each termination panel supports 16 points and each analog module can support
up to 2 panels. These termination panels are compatible with any signal conditioners in the 1 to
5 volt output range. For example, the 7B series of signal conditioners from Analog Devices™ are
known to work well.
Termination Panel 9251-210 for Digital Output Module 3603B
The special 16-point non-commoned digital output termination panel 9251-210 is required for
use with the 16-point non-commoned digital output module 3603B.
Termination Panel 9863-710 for Analog Output Module 3806E
The special analog output termination panel 9863-710, with buffered loopback signals, is
available for use with the high-current analog output module 3806E.

Cables 7
Field Terminations Guide for Tricon v9–v10 Systems
Cables
Three types of cables can be used with the Tricon:
•Interface Cables
•Fanned-Out Cables
•Special Cables (Relay Loopback)
Interface Cables
Interface cables are packaged with all termination panels. Each interface cable has a female
connector on one end for connection to the male connector on a Tricon chassis backplane. The
opposite end has a keyed male connector for connection to a termination panel.
Although the standard length of all interface cables is 10 feet (3 meters), you may order any
length cable up to 90 feet (27.4 meters) in 10-foot increments using the last two digits of the
termination panel’s model number to specify length in feet. For example, specify 9xxx-x50 if you
want a 50-foot (15 meter) cable instead of the standard 10-foot (3-meter) cable.
Fanned-Out Cables
Fanned-out cables are a lower-cost alternative to using external termination panels. Fanned-out
cables allow you to marshal field signals in a separate enclosure up to 99 feet (30 meters) from
a Tricon. One end of a fanned-out cable has a female connector that connects to a Tricon chassis
backplane. The other end of the cable contains 50 fanned-out leads, each individually labeled
with its corresponding connector pin number.
Each fanned-out cable has the following characteristics:
• PVC outer covering
• 56-pin connector at one end
• 50 stranded, stripped, tinned and labeled 22-gauge leads at opposite end
Fanned-out cables should only be used with digital input and digital output modules. They are
not certified for use with analog signals. Contact the Triconex Customer Support Center if you
need a fanned-out cable for handling analog signals.
Although the normal length of all fanned-out cables is 10 feet (3 meters), any length cable can
be ordered up to 99 feet (30 meters) in 1-foot increments, using the last two digits of the cable
model number to specify the length in feet. For example, the model number 9101-050 specifies
a 50-foot cable instead of the normal 10-foot cable.
Special Cables (Relay Loopback)
If your application requires a special cable, it must be ordered separately. For example, if you
want to verify relay activation on a relay termination panel using a digital output module, you
must order a relay loopback cable to connect between the relay termination panel and a digital
input module. Currently, the only special cable available is the relay loopback cable (914x-010).

8Chapter 1 Introduction to Field Terminations
Field Terminations Guide for Tricon v9–v10 Systems
This manual suits for next models
1
Table of contents
Popular Conference System manuals by other brands

TANDBERG
TANDBERG DIRECTOR D5016402 user manual

INIM Electronics
INIM Electronics SmartLink-G installation manual

LEGRAND
LEGRAND MIDDLE ATLANTIC FlexView 800 Series instruction sheet

Poly
Poly Studio X Series user guide

Yealink
Yealink MeetingBar A30 quick start guide

NAPCO
NAPCO StarLink Connect LTE Series installation instructions