Turbo Economiser E2T User manual

TURBO
s.r.l.
Electronic Control Systems For Dust Collectors
e-mail: info@turbocontrols.it web: www.turbocontrols.eu
TE . ++39 (0)362 574024 FAX ++39 (0)362 574092
ECONOMIZER
E2T
24Vdc
25 ÷ 56 OUTPUTS
User Manual
05/01/2016
Manual Release 1.00
Hardware Release 1.01

1
General Description
Economizer for controlling the pneumatic cleaning function of industrial dust
collection s stems.
The pressure differential is digitall controlled b an internal transducer allowing
to determine filter obstruction with accurac .
The device has three output rela s contacts and two digital input contacts.
A large, bright displa is provided for reading the filter obstruction level, the
active solenoid valves and an alarms in an moment.
Technical Specifications
Casing
Made of insulating, ABS base and pol carbonate lid.
Degree of protection to water and dust: IP65 (EN60529).
Shock resistance: IK08/07 (8 joule) (EN62262).
Performance Of The Device
Dedicated software program, managed b the microprocessor, eas to set up
and consult, facilitates the use of the instrument also b users unfamiliar.
Power voltage 24 Vdc.
Output voltage 24Vdc.
LED displa with 7 segments, 3 digits 0.8” each.
Three alarm rela .
Micro SD memor card for data storage, extractable for consultation.
Sampling is performed ever 10 seconds, the time interval is editable.
Four operation modes: manual; automatic;
automatic with forced c cle; proportional.
Operating times expressed in seconds with selectable ranges for an
application (option pause time in minutes).
Pressure measurements expressed in kPa optional in inch Wc.
Washing function with the fan off (post-cleaning) through the “dP fan”
threshold in the automatic/automatic with forced c cle/proportional modes
and through contact in the manual mode with up to 99 c cles that can be
selected.
Total and partial hour counter for maintenance.
Three alarm rela s.
Maximum dP (filter obstructed) alarm.
Minimum dP alarm (broken sleeve/cartridge), with possibilit of
inclusion/exclusion.
Solenoid valve not working alarm.
Filtering element maintenance deadline alarm (with on/off selection).
External contact cleaning activation.
Compressed air presence enable input.
Pre-coating function (with possibilit of inclusion/exclusion).
4-20mA output proportional to dP reading for remote pressure reading.
Manual solenoid valve activation.
Setting the current date and time associated with the archiving historical
data on the SD card, where are stored the detected values.

2
Electric Specifications
Electric Power
24 VDC– 25W
Selectable Output Voltage
24 Vdc
Maximum Load 25 W.
Inputs An Outputs Galvanically Insulate
Enable contact (remote cleaning enable).
Fan contact (post-cleaning).
4 – 20mA (dP remote reading).
The solenoid valves connected to the unit are normall closed.
The activation of a solenoid valves causes them to open and let out a jet of air.
Alarm Relays
The three alarm rela s contain 2 clean contacts on terminals 4 ÷ 9 di J4.
Maximum permitted load: 2A @ 24Vdc
Fuse
1 x 3 A @ 24Vdc.
Working Temperature
from -10°C to 55°C
Storage Temperature
-20°C to 60°C
Timer Specifications:
Pulse Time (Valve Opening)
from 50 ms to 5 sec
Pause Time (Interval Between Valve Openings)
1 sec - 999 sec
Differential Pressure Gauge
Measurable pressure range: from 0 to 4 kPa
Maximum applicable pressure: 16 kPa - 0.16 bar
(optional sensor 10kPa)
War nin g ! Hi ghe r p r es su r es w il l
da m age t he devic e.
Do no t c o nnec t c l og gi n g
measur i ng t ub e s to t h e
compr e s s e d air c irc ui t .
War nin g ! Read t he s ect i on on
in s tal l a ti on be fo re con n ec ti ng
the dev i c e .

3
Installation Instructions / Notes An Warnings
Protect the device from direct exposure to sunlight.
Do not position the device near or directl in contact with sources of heat or
electromagnetic fields.
Connect the device to power lines other than those for operating motors or
other large power devices which could generate network interference.
Fix the device of a height of at least 60 cm from the ground.
Use flame-retardant cables with a minimum cross-section area of 0.25 mm2
for all control signals.
Check that atmospheric conditions are safe before starting an operation on
the device.
For electric operations, alwa s remove voltage, wait 30 seconds for the
inside capacitors to discharge before opening. At the end of the operations,
close the device to restore the correct degree of protection before powering
up.
Use flame-retardant cables with a minimum cross-section area of 0.75mm²
to connect to the power suppl .
An use not described in this user instruction manual or incorrect use of the
device ma cause damage to the device or to the devices connected to it.
Furthermore, incorrect use or tampering with the device ma cause injur .
Waterproofness of the casing is guaranteed when the flap is closed.
Make sure that rigid or flexible ducts used for wiring, if an , do not fill up
with water or other liquids.
An holes made in the casing must be protected b accessories with degree
of protection equal to at least that of the economizer.
Cut off power suppl immediatel if water is found in the casing.
Do not use the economizer if you have not read or do not understand this manual.

4
Display Keypa
There are four round buttons on the front panel for controlling the device and
turning on the displa as shown in the following figure.
The SET button enables to enter and exit the
programming menu, and activate the manual
test of solenoid valve selected in function F06.
The + and – buttons enable to scroll functions
from F01 to Fxx. After entering one of the Fxx
functions use the OK button to select and then
+ and - increase or decrease the values.
The OK button is used to confirm data and
reset alarms.
If the + button is pressed during ordinar
operation, the activit hour meter is displa ed.
The - Button pressed during the ordinar
operation, displa s the counts partial hours of
activit .
If the Micro SD Card is inserted, the pressing of the OK button enables safe
removal of the card.
Menu Diagram
Press SET, the letter F flashes.
Press + and – to select the required function.
Press OK to confirm.
Increase or decrease the value of the
parameter.
Holding down the + and - buttons to scroll
through all the functions until the end of the
left or right.
Press OK to confirm and exit.
Press SET again to exit programming mode.

5
List of Functions
F01: Configuring the operation mode.
Possible values: 0 – Manual (dP excluded)
1 – Automatic (Default) (dP included)
2 – Automatic with forced c cle (dP included)
3 – Proportional (dP included)
F02: Solenoid activation time.
Possible values: 0.05” – 5.00” step 0.01”.
Default = 0.20”.
F03: Washing pause time between solenoid valves.
Possible values: 001” – 999” step 1”.
Default = 020”.
F04: Number of connected outputs.
Possible values: 01 – 56.
depending on the version of the instrument, step 1.
Default = 001.
F05: Output voltage setting.
Possible values: 24 Vdc.
Default = 24 Vdc.
F06: Manual output activation.
Possible values: 1 – number of outputs set in F04.
Press SET to activate the set output.
F07: Zero dP threshold.
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 0.00 kPa.
F08: Cleaning c cle start threshold.
Possible values:
0.00 kPa – 3.99 kPa step 0.01.
Default = 0.80 kPa.
F09: Cleaning c cle stop threshold.
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 0.40 kPa.
F10: Max dP Alarm Threshold (Filter Clogging)
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 3.00 kPa.
F11: Fan on recognition mode.
Possible values: 0 from contact – 1 from dP.
Default = 1 from dP.
F12: dP threshold for fan on recognition if F11=1.
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 0.10 kPa.
F13: Number of post cleaning c cles after stopping the fan.
Possible values: 01 – 99 step 1.
Default = 01.

6
F14: Post cleaning mode pause time between solenoid valves (fan off).
Possible values: 001” – 999” step 1”.
Default = 010”.
F15: Maintenance frequenc expressed in tens of hours
Possible values: 001 – 999 step 1. (e.g.: 1=10h, 10=100h).
Default = 100 (=1000h).
F16: Maintenance deadline alarm enable.
Possible values: 0 (disabled) – 1 (enabled).
Default = 0 (disabled).
F17: Maintenance hour counter reset.
Possible values: 0 (disabled) – 1 (reset).
Default = 0 (disabled).
Note: The maintenance hour counter
will be reset and the F17 parameter will be set back to 0 by setting F17 to 1.
F18: Precoating function enabling.
Possible values: 0 (disabled) – 1 (enabled).
Default = 0 (disabled).
F19: dP threshold for precoating function.
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 2.00 kPa.
F20: Enabling Minimum dP Alarm function.
Possible values: 0 (disabled) - 1 (enabled).
Default = 0 (disabled).
F21: Min dP Alarm Threshold (Broken Sleeve/Cartridge)
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 0.20 kPa.
F22: Selection of minutes or hours for Forced Cleaning C cle.
(Onl if the operating mode F01 = 2)
Minutes (0 =minutes, 1 =hours)
Default = 0 (Minutes)
F23: Setting time interval for Forced Cleaning C cle in relation
to the choice of F22.
Setting values: 1 - 999 step 1.
Default = 240 (240 minutes).
F24: Setting the date on the internal clock.
Settable values: Da 1 – 31 d.
Month 1 – 12 п.
Year 00 – 99 y.
F25: Setting of the time for the internal clock.
Settable values: Hours: 0 – 23 HH.
Minutes: 0 – 59 пп.
F26: Exclusion of the valve in short circuit.
If set to 1 the valve shorted is excluded from the c cle.
Settable Values 0 (not excluded) - 1 (excluding)
Default = 0 (not excluded).

7
Alarms
The unit runs a number of checks during the start-up c cle and during normal
operation. The possible alarms and respective solutions are shown in the
following table.
A. Nr.
Description Action
E01 F05 set to 24Vdc – AC jumper
detected
- For 24Vdc, switch the device off
and move the AC/DC jumpers to DC.
Jumper table p. 12.
- For 24Vac, press OK, then press
SET, set the function F05 using “+”
and “-”, select A24 and press OK to
confirm.
E02 F05 set to 24Vac – DC jumper
detected
- For 24Vac, switch the device off
and move the AC/DC jumpers to AC.
Jumper table p. 12.
- For 24Vdc, press OK, then press
SET, set the function F05 using “+”
and “-”, select d24 and press OK to
confirm.
E06
Solenoid valve current lower than
minimum threshold or disconnected
solenoid valve
Check correct connection of the
solenoid valve and respective data.
The alarm is self-reset.
E07 Solenoid valve current higher than
maximum threshold
Check correct connection of the
solenoid valve and respective data.
The alarm is self-reset.
E08
Output short circuit
The signaling of the code E08
alternates with the indication of the
interested output is shown as Uxx
where xx is the number of the
output and the value of dP.
Turn off the device and then turn it
back on, after having verified the
plant of the solenoid valves.
E09
dP maximum pressure exceeded
(F10)
Detected for longer than 20
seconds.
Check state of filtering elements.
E10 dP sensor hardware offset out of
range.
The self-calibration of the dP sensor
has determined that a value is out of
range. Disconnect the air tubes and
repeat the function. Take the device
to be serviced if the alarm occurs
again.
E11 Maintenance deadline reached Carr out maintenance.
E12
dP sensor full-scale value reached
Immediate reporting without an
dela .
Check state of filtering elements.
IMPORTANT: Running in this
condition ma damage the device.

8
E13
Minimum dP alarm value ranging
from F12 to F21 (warning: the
alarm is generated with a fixed
dela of 60 seconds).
Check the status of the filtering
elements.
E14
Indicates that a valve in short
circuit has been excluded from the
c cle.
The signaling of the code E14
alternates with the indication of the
interested output is shown as Uxx
where xx is the number of the
output and the value of dP.
An output is considered a short
circuit if not responding for 3
following activations.
An activation without error resets
the counting.
Turn off the device and then turn it
back on, after having verified the
plant of the solenoid valves.
E20 Internal clock error.
Replace buffer batter (CR1632 3V
130mAh) and set current time and
date.

9
Description Of Operation
The installed SW version and the s mbol ---, meaning that coherence between
settings stored in E2Prom and the set jumpers is being checked, will appear on
the displa when the economizer is powered up. A corresponding error code will
appear in case of discrepancies between settings (see Alarms Table). Onl editing
functions will be allowed on the unit. The operator ma switch off the unit and
configure the jumpers correctl .
S mbol 0_0 will appear on the displa if the test is entirel successful. The
following pages will then appear:
In automatic mode (F01=1):
dP value alternating with OFF if the enabling contact (14-15) is open
dP value alternating with -0- if the enabling contact (14-15) is closed and the fan
is off.
dP value onl if the fan is enabled and active.
In manual mode (F01=0):
OFF if the enabling contact is open (14-15)
-0- if the enabling contact (14-15) is closed and the fan is off
Manual Operating Mo e F01=0
The economizer will work as a programmable c cle sequencer in manual mode.
The connected outputs will be activated at the programmable frequencies. Manual
mode can be activated b accessing the configuration menu and setting F01 to 0.
F02 and F03 will set the activation time and the pause time, respectivel .
Automatic Operating Mo e F01=1
B selecting automatic mode (F01=1), the economizer will work autonomousl
can carr out the pneumatic washing c cle onl when needed. The device will
start the washing c cle if the obstruction is higher than Threshold_dP_Start
(F08). Washing is suspended when obstruction drops under Threshold_dP_Stop
(F09) level until it reaches a value higher than the Threshold_dP_Start threshold
once again. When washing is active, the economizer respects the times set in F02
(operating time) and F03 (pause time).
Automatic Mo e With Force Cycle F01 = 2
Identical to the automatic mode, except for the fact that it is possible to obtain a
cleaning c cle with the activation of the solenoid valves connected without
reaching the Threshold_dP_Start (F08). The forced cleaning interval ma range
from 1 to 999 h and can be selected through function F22 and F23.

10
Proportional Mo e F01 = 3
With the proportional mode, the economizer will work in full autonom , initiall
setting the dP_Start threshold (F08), activation time (F02) and pause time (F03).
When the Start Cleaning threshold is exceeded, the solenoid valves are
automaticall activated in sequence. If the dP threshold drops below 15% at the
end of an entire c cle of pulses of the connected solenoid valves, the washing is
suspended until pressure returns to a value above the Start Cleaning dP value. If
the dP value does not drop below 15% of the Start Cleaning threshold, the
frequenc of the c cle time is automaticall reduced in proportion with each
entire c cle of pulses of the connected solenoid valves, until a minimum c cle
time between solenoid valves reaches 10 seconds. The minimum threshold of 10
seconds has been chosen so as not to hamper the dispensing of air b the
compressor connected to the filter.
Cleaning Function With Fan Off (PCC)
This function allows to carr out one or more cleaning c cles (the number of
c cles is defined b F13) when the fan is off. The on or off state of the fan ma
be determined b the state of the contacts 12-13 (contacts open = fan off) if
F11=0, or ma be determined automaticall (with F11=1) when the dP pressure
drops under the threshold defined in F12. The pulse time of the valves will alwa s
be that defined in F02, while the pause time in this case is defined in F14.
The displa alternatel shows the number of the valve activated and the word PCC.
Number Of Output Selection
The number of outputs (solenoid valves) on which the economizer will run the
cleaning c cle can be selected. Cleaning will be carried out in order from the first
to the last solenoid valve. The valves can be adjusted b the F04 function.
Precoating Function (F18=1)
This function is used to carr out precoating. Precoating is a filtering element
treatment carried out with precoating powder. Washing and manual output
activation is suspended during precoating until the precoating thresholds defined
in F19 is reached.
The dP value and the message PC (precoating) will appear alternativel on the
displa .
P Zero Calibration (F07)
This function is used to reset dP reading with the fan off.
Increase or decrease the value shown b pressing “+” and “-” as required. This
value will be subtracted from the value read b the dP sensor.
P Sensor Self-Calibration
This function allows to reset dP reading with the fan off automaticall .
Hold “SET” and “OK” pressed at the same time with the device off. The message
“CAL” will appear after the start-up test. Release the buttons. The unit will go
back to normal state after a few instants. Automatic calibration is complete.

11
Fuse
A fuse which can be reset in case of need is located near the power terminal
board. Use a dela ed fuse 5x20mm as shown in the table on next pages.
SD Memory Car
The Micro SD memor card slot is located on the bottom right of the control unit
under the pol carbonate lid.
The card is not supplied with the control unit. A card with a maximum of 32GB
can be used.
The card must be formatted FAT32, which is the format recognized b all devices
and operating s stems.
Before removing the memor card, press the OK button with the control unit on,
wait for the cd (card) indication and the alternating flashing of the horizontal
lines of the third figure ≡. The card can now be safel removed. The Micro SD
Card connector is push-pull.
Press upwards and extract the card to remove it.

12
Connection Diagram

13
Contacts An Relay Terminal Block J4
Enable contact input consensus 14.15 terminals.
Is used to activate the control unit remotel , it can be turned on and off
remotel .
The unit is supplied with a jumper on the two terminals 14:15, without it will
not turn on.
Fan contact 12.13 input terminals.
Indicated b the control unit that the plant has been started and is in operation.
The unit is supplied with a jumper on two 12:13 terminals to simulate the state
of the plant, as if the fan was turned on.
Alarm Rela K1 4.5 terminals.
The rela is normall closed, opens in case of alarms, and opens to the control
unit off in the absence of power.
The alarms that open the rela s are:
Problem with solenoid valves E06-E08.
Maintenance interval has been reached.
If one of these occurs, the rela is activated.
Alarm Rela K2 6.7 terminals.
The rela is normall closed, opens in case of alarm, and opens to the control
unit off in the absence of power.
The alarm that open the rela s is:
Max dP has been reached.

14
Connection Diagram Expansions
Expansion Up To 32 Channels
Expansion Up To 40 Channels

15
Expansion Up To 48 Channels

16
Expansion Up To 56 Channels

17
Terminal Table
To access at the terminal blocks of the control board, unscrewing countersunk
screws of the cover panel blue.
Main Board
Terminal
Description Terminal
Description
01 Power Suppl 24 Vdc 46 Solenoid output 16
02 Power Suppl 24 Vdc 47 Solenoid output 17
03 Earth (GND) 48 Solenoid output 18
49 Solenoid output 19
03 Earth (GND) 50 Solenoid output 20
03 Earth (GND) 51 Solenoid output 21
30 Solenoid valve common 52 Solenoid output 22
30 Solenoid valve common 53 Solenoid output 23
31 Solenoid output 01 54 Solenoid output 24
32 Solenoid output 02
33 Solenoid output 03 04 Alarm rela contact 01
34 Solenoid output 04 05 Alarm rela contact 01
35 Solenoid output 05 06 Alarm rela contact 02
36 Solenoid output 06 07 Alarm rela contact 02
37 Solenoid output 07 08 Alarm rela contact 03
38 Solenoid output 08 09 Alarm rela contact 03
39 Solenoid output 09 12 Fan input
40 Solenoid output 10 13 Fan input
41 Solenoid output 11 14 Enable input
42 Solenoid output 12 15 Enable input
43 Solenoid output 13
44 Solenoid output 14 10 4-20mA dP output -
45 Solenoid output 15 11 4-20mA dP output +

18
Expansion Boards
Expansion up to 32 channels Expansion up to 48 channels
Terminal
Description Terminal
Description
03 Earth (GND) 03 Earth (GND)
30 Solenoid valve common 30 Solenoid valve common
55 Solenoid output 25 71 Solenoid output 41
56 Solenoid output 26 72 Solenoid output 42
57 Solenoid output 27 73 Solenoid output 43
58 Solenoid output 28 74 Solenoid output 44
59 Solenoid output 29 75 Solenoid output 45
60 Solenoid output 30 76 Solenoid output 46
61 Solenoid output 31 77 Solenoid output 47
62 Solenoid output 32 78 Solenoid output 48
Expansion up to 40 channels Expansion up to 56 channels
Terminal
Description Terminal
Description
63 Solenoid output 33 79 Solenoid output 49
64 Solenoid output 34 80 Solenoid output 50
65 Solenoid output 35 81 Solenoid output 51
66 Solenoid output 36 82 Solenoid output 52
67 Solenoid output 37 83 Solenoid output 53
68 Solenoid output 38 84 Solenoid output 54
69 Solenoid output 39 85 Solenoid output 55
70 Solenoid output 40 86 Solenoid output 56
Fuse Table Jumper Configuration Output
Voltage Value
24 Vdc 3 A
24VDC

19
Installation An Casing Dimensions
Other Turbo Controllers manuals
Popular Controllers manuals by other brands

SKF
SKF Magforce STD 10007 series Installation, operation and maintenance manual

Daikin
Daikin BRC7C62 installation manual

Enttec
Enttec Playback user manual

Mitsubishi Electric
Mitsubishi Electric melsec q00ujcpu user manual

Grundfos
Grundfos UPZCP-3 Installation and operating instructions

THORLABS
THORLABS MCM3000 Series user guide

Kimaldi
Kimaldi BioMax2 Installation and programming manual

Briggs & Stratton
Briggs & Stratton GC1031 Operation instructions

maxxess
maxxess 3 Series Installation Guide and Specifications

SMC Networks
SMC Networks AWM20-01 Series Operation manual

APART
APART DIWAC instruction manual

Zennio
Zennio AudioInRoom manual