maxxess 3 Series User manual

eMAX-MR50
SINGLE DOOR CONTROLLER – Series 3
Installation Guide and Specifications
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference
(2) This device must accept any interference received,
including interference that may cause undesired operation.
This device meets CE Specifications, and is RoHS Certified.
This device is UL 294 Recognized. FEBRUARY 2018

February, 2018 eMAX-MR50 Series 3-Manual Page 2 of 9
TABLE OF CONTENTS
Paragraph Title Page No.
1. General …………………………………………………………………………………………….. 3
2. eMAX-MR50 Hardware ……………………………………..…………….………….………...… 3
3. Reader Wiring ……………………………………………………………………………………. 4
4. Door Strike/Lock Relay Wiring ……………………………….……………………………….. 5
5. Communication Wiring ……………………………………….……………………………….. 5
6. Dip Switch Configuration …………….……………………………….………….…………… 6
7. Status LEDs ………………………………………………………………..……………………. 7
8. Specifications …………………………………………………………………...………………. 8
Warranty and Liability ……………………………………………………………………………….. 9
Change History:
Original Original document creation February, 2018

February, 2018 eMAX-MR50 Series 3-Manual Page 3 of 9
eMAX-MR50 SINGLE DOOR CONTROLLER
Series 3
1. General:
The eMAX-MR50-S3 Single Door Controller provides a solution for interfacing to a TTL (D1/D0, Clock/Data),
F/2F or RS-485 Reader-type devices, and associated door hardware. It also provides for tri-stated LED control
and buzzer control. Two Form-C contact relay outputs may be used for door lock control or alarm signaling.
Two inputs are provided that can be used for monitoring the door contact and request to exit device. Input
circuits can be configured as unsupervised or supervised. Communication to the eMAX-MR50-S3 controller is
accomplished via a 2-wire RS-485 interface. The eMAX-MR50-S3 requires 12 to 24 Vdc for power.
2. eMAX-MR50 Hardware:
The eMAX-MR50-S3 requires filtered 12 to 24 Vdc ± 10% for power. Two inputs on the board are typically
used for door contact and exit request monitoring. End of line resistors are required for supervision, shown
below.
Note: The input power is passed through to the reader terminal strip and is available for powering a reader.
Readers that require different voltage requirements must be powered separately. Care must be taken to ensure
that the input voltage is within the voltage range of the reader. The reader power output terminal, TB4-6 (VO),
is not current limited.
Note: Refer to the eMAX-EP controller Installation and Specifications manual for proper grounding details.
TB1
GND
TR-
TR+
VO
D0
DAT
GND
D1
LED
CLK
BZR
TB4
2.35 [59.7]
2.75 [69.9]
3.85 [97.8]
0.20 [5.1]
0.20 [5.1]
Ø0.156 [Ø4.0]
4 PLACES
J1
J2
D1
D2
D4 D3
TB3
TB2
I1
I1
I2
I2
GND
VIN
C
NC
NO
C
NO
NC
K2K1
4.25 [108]
K2
K1
S1
85 6741 23
^
|
ON
STATUS LEDs
J2 - TAMPER INPUT,
NORMALLY OPEN SWITCH
1K,1%
1K,1%
1K,1%
1K,1% NC
NO EXIT REQUEST
NORMALLY OPEN
DOOR CONTACT
NORMALLY CLOSED
NORMALLY CLOSED
COMMON
NORMALLY OPEN
NORMALLY OPEN
NORMALLY CLOSED
COMMON
+12 to 24Vdc INPUT VOLTAGE
INPUT VOLTAGE RETURN
STRIKE RELAY (K1)
GROUND
BUZZER
LED
DATA1/CLOCK/TR+
DATA0/DATA/TR-
READER POWER
RS-485
INTERFACE
READER
TAMPER, NO
AUX. RELAY (K2)
TR-
GROUND
TR+
I2
I1
SIO COMM.
OPTIONAL EOL
SUPERVISION
SHOWN
TB1
GND
TR-
TR+
VO
D0
DAT
GND
D1
LED
CLK
BZR
TB4
J1
J2
85 6 7
41 2 3
^
|
ON
TO J2
TB3
TB2
I1
I1
I2
I2
GND
VIN
C
NC
NO
C
NO
NC
K2K1
K2
K1

February, 2018 eMAX-MR50 Series 3-Manual Page 4 of 9
3. Reader Wiring:
The reader port supports a reader with TTL (D1/D0, Clock/Data), F/2F, or 2-wire RS-485 signaling.
**Refer to the reader manufacture specifications for cabling requirements. In the 2-wire LED mode, the buzzer
output is used to drive the second LED. Reader port configuration is set via the host software.
Typical D1/D0 or Clock/Data Reader
Typical RS-485 Device
* Inputs on supervised F/2F readers may be unsupervised or supervised (supervised shown).
Typical Unsupervised F/2F Reader
Typical Supervised F/2F Reader
Jumper D1 to LED on supervised F/2F readers
TB4
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
1
TB4
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
1
TB4
D1
GROUND 1
F/2F Reader
+12 Vdc
DO (GREEN LED)
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
TB4
D1
GROUND
F/2F Reader
+12 Vdc
DO(GREEN LED)
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1

February, 2018 eMAX-MR50 Series 3-Manual Page 5 of 9
4. Door Strike/Lock Relay Wiring:
Two (2) Form-C contact relays are provided for controlling the door strike/lock or other such devices. See
specifications section for the relay contact ratings. Load switching can cause abnormal contact wear and
premature contact failure. Switching of inductive loads (strike) also causes EMI (electromagnetic interference)
which may interfere with normal operation of other equipment. To minimize premature contact failure and to
increase system reliability, contact protection circuit must be used. The following circuit wiring is recommended.
Locate the protection circuit as close to the load as possible (within 12 inches [30 cm]), as the effectiveness of
the circuit will decrease if it is located far away. See documentation included with locking device regarding
suppression diode requirements.
Diode Selection:
Diode current rating: 1x strike current
Diode breakdown voltage: 4x strike
voltage
For 12 Vdc or 24 Vdc strike, diode
1N4002 (100V/1A) typical
Typical DC Door Strike Wiring
5. Communication Wiring:
The eMAX-MR50-S3 Controller communicates to a Maxxess EP Series Intelligent Area Controller (EP2500 for
example) via a half-duplex multi-drop 2-wire RS-485 interface. The total cable length is limited to 4,000 feet
(1,219 meters). Shielded cable of 24 AWG with characteristic impedance of 120 ohm is specified for the 2-wire
RS-485 interface. The last device on each end of the communication line should have the terminator installed
(install jumper J1).
MR-50 CONTROLLER
TO ADDITIONAL
SIO UNITS
TR-
GND
TR+
MR-50
TB1
GND
TR-
TR+
VO
D0
J1
J2
85 6741 23
^
|
ON
TB1
GND
TR-
TR+
VO
D0
J1
J2
85 6741 23
^
|
ON
J1 - RS-485 COMMUNICATION
TERMINATOR JUMPER
INSTALL ON LAST UNIT OF
COMMUNICATION LINE

February, 2018 eMAX-MR50 Series 3-Manual Page 6 of 9
6. DIP Switch Configuration:
Switches 1 to 5 select the device address. Switch 6 and 7 select the communication baud rate. Switch 8
enables encrypted communication. All other configuration settings are set via host software. Defaults
are address 0 and baud rate 38,400.
S8
S7
S6
S5
S4
S3
S2
S1
SELECTION
OFF
OFF
OFF
OFF
OFF
Address 0
OFF
OFF
OFF
OFF
ON
Address 1
OFF
OFF
OFF
ON
OFF
Address 2
OFF
OFF
OFF
ON
ON
Address 3
OFF
OFF
ON
OFF
OFF
Address 4
OFF
OFF
ON
OFF
ON
Address 5
OFF
OFF
ON
ON
OFF
Address 6
OFF
OFF
ON
ON
ON
Address 7
OFF
ON
OFF
OFF
OFF
Address 8
OFF
ON
OFF
OFF
ON
Address 9
OFF
ON
OFF
ON
OFF
Address 10
OFF
ON
OFF
ON
ON
Address 11
OFF
ON
ON
OFF
OFF
Address 12
OFF
ON
ON
OFF
ON
Address 13
OFF
ON
ON
ON
OFF
Address 14
OFF
ON
ON
ON
ON
Address 15
ON
OFF
OFF
OFF
OFF
Address 16
ON
OFF
OFF
OFF
ON
Address 17
ON
OFF
OFF
ON
OFF
Address 18
ON
OFF
OFF
ON
ON
Address 19
ON
OFF
ON
OFF
OFF
Address 20
ON
OFF
ON
OFF
ON
Address 21
ON
OFF
ON
ON
OFF
Address 22
ON
OFF
ON
ON
ON
Address 23
ON
ON
OFF
OFF
OFF
Address 24
ON
ON
OFF
OFF
ON
Address 25
ON
ON
OFF
ON
OFF
Address 26
ON
ON
OFF
ON
ON
Address 27
ON
ON
ON
OFF
OFF
Address 28
ON
ON
ON
OFF
ON
Address 29
ON
ON
ON
ON
OFF
Address 30
ON
ON
ON
ON
ON
Address 31
OFF
OFF
115,200 BPS, See note 1 below.
OFF
ON
9,600 BPS
ON
OFF
19,200 BPS
ON
ON
38,400 BPS
OFF
Encrypted communication not required
See note 2 below.
ON
Encrypted communication required
See note 2 below.
Note 1: Firmware revisions prior to 1.39.1, this setting is 2,400 BPS
Note 2: Firmware revisions prior to 1.39.1, SW8 is not defined. Set to the OFF position

February, 2018 eMAX-MR50 Series 3-Manual Page 7 of 9
7. Status LEDs:
Power-up: All LED’s OFF
Initialization: Once power is applied, initialization of the module begins
The D1 LED is turned ON at the beginning of initialization
Run time: After a successful initialization, the LEDs have the following meanings:
D1 LED: Heartbeat and On-Line Status:
Off-line: 1 second rate, 20% ON, 80% OFF
On-line: Non-encrypted communication: 1 second rate, 80% ON, 20% OFF
Encrypted communication:
.1 S ON, .1 S OFF, .1 S ON, .1 S OFF, .1 S ON, .1 S OFF, .1 sec ON, .3 S OFF
D1 LED Error Indication:
Waiting for application firmware to be downloaded: .1 S ON, .1 S OFF
D2 LED: SIO Communication Port Status:
Indicates communication activity on the SIO communication port

February, 2018 eMAX-MR50 Series 3-Manual Page 8 of 9
8. Specifications:
Revision E assembly:
The eMAX-MR50-S3 Interface is for use in low voltage, class 2 circuits only.
Primary Power: 12 to 24 Vdc ± 10%, 150 mA maximum (plus reader current)
Outputs: Two Form-C contact relays:
K1: Normally open contact (NO) contact: 5 A @ 30 Vdc resistive
Normally closed contact (NC) contact: 3 A @ 30 Vdc resistive
K2: 1 A @ 30 Vdc resistive
Inputs: Two unsupervised/supervised, standard EOL, 1k/1k ohm, 1%, ¼ watt
One unsupervised, dedicated for cabinet tamper
Reader Interface:
Reader power: 12 to 24 Vdc ± 10% (input voltage passed through)
Reader LED output: TTL compatible, high > 3 V, low < 0.5 V, 5 mA source/sink maximum
Buzzer output: Open collector, 12 Vdc open circuit maximum, 40 mA sink maximum
Data Inputs: TTL compatible, F/2F or 2-wire RS-485
Communication: 2-wire RS-485: 9600, 19200, 38400 or 115200 bps
Cable Requirements:
Power: 1 twisted pair, 18 AWG
RS-485 I/O devices: 1 twisted pair with drain wire and shield, 24 AWG, 120 ohm impedance,
4,000 ft. (1,219 meters) maximum
Alarm Inputs: 1 twisted pair per input, 30 ohms maximum
Outputs: As required for the load
Reader data (TTL): 6-conductor, 18 AWG, 500 ft. (150 meters) maximum
Reader data (F/2F): 4-conductor, 18 AWG, 500 ft. (150 meters) maximum
Reader data (RS-485): 1 twisted pair with drain wire and shield, 24 AWG, 120 ohm impedance,
2,000 ft. (610 meters) maximum
Mechanical:
Dimension: 4.25 in. (108 mm) W x 2.75 in. (70 mm) L x 1 in. (25.4 mm) H
Weight: 4 oz. (120 g) nominal
Environment:
Temperature: -55 to +85 °C, storage,
-40 to +75 °C, operating
Humidity: 5 to 95 % RHNC
UL294, 6th Edition Performance Levels:
Feature
Level
Standby Power
I
Endurance
IV
Line Security
I
Destructive Attack
I

February, 2018 eMAX-MR50 Series 3-Manual Page 9 of 9
Warranty
Maxxess Systems, Inc. warrants the product is free from defects in material and workmanship under normal
use and service with proper maintenance for one year from the date of factory shipment. Maxxess Systems,
Inc. assumes no responsibility for products damaged by improper handling or installation. This warranty is
limited to the repair or replacement of the defective unit.
There are no expressed warranties other than set forth herein. Maxxess Systems, Inc. does not make, nor
intends, nor does it authorize any agent or representative to make any other warranties, or implied warranties,
and expressly excludes and disclaims all implied warranties of merchantability or fitness for aparticular purpose.
Returns must be accompanied by a Return Material Authorization (RMA) number obtained from customer
service, and prepaid postage and insurance.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is available.
This product is not intended for, nor is rated for operation in life-critical control applications. Maxxess Systems,
Inc. is not liable under any circumstances for loss or damage caused by or partially caused by the misapplication
or malfunction of the product. Maxxess System, Inc. liability does not extend beyond the purchase price of the
product.
Other manuals for 3 Series
1
This manual suits for next models
2
Table of contents
Other maxxess Controllers manuals