15
Instructions for the installer
Note:
The appliances are equipped with expan-
sion vessels. Before installing the applian-
ce check that the vessel’s capacity is suf-
ficient;ifthis is notthecase, provisionmust
be made to fit an additional expansion
vessel.
3.5 - BOILER INSTALLATION
Before connecting the boiler to the heating system the fol-
lowing requirements must be carried out by competent and
qualified engineers:
a) The system is flushed out with a suitable product in order
to eliminate any metallic tooling or welding residues and
oil and grime which could reach the boiler and affect the
proper running of the boiler;
b) Check that the boiler has been preset for operating with
the gas type available.
This is verifiable via the indication on the packaging and
on the data badge;
c) Check that the chimney/flue pipe has an adequate drau-
ght, does not have any constrictions, and that no other
appliance’s flue outlets have been fitted, unless the chim-
ney is serving more than one heating appliance, accor-
ding to the specific standards and regulations in force.
The connection between the boiler and chimney/flue out-
let can be made only after this verification has been car-
ried out.
As a safety measure against gas leaks, Unical
recommends installing a surveillance and pro-
tective system composed of a gas leakage
detector combined with an on-off selenoid
valve fitted on the gas supply line.
The gas supply pipe must have a section which is identical or
greater then the one used on the boiler and must assure a
correct gas pressure.
It is however important to comply with the “General installa-
tion standards” indicated in the standards UNI 7129, UNI 7131
and UNI 1137-1.
Before commissioning an internal gas distribution system and
therefore before connecting it to the gas meter, the complete
installation must be tested for gas soundness.
If any part of the system is concealed from view the gas soun-
dness test must be carried out before covering the pipes.
Before connecting the pipework the system must be tested
with air or inert gas at a pressure of at least 100mbar.
Before commissioning the boiler ensure that the following
operations are carried out:
- Open the gas meter cock and vent the air contained in the
piping and subsequently proceed to vent device by devi-
ce.
- Check, with the gas cock turned off, that there are no gas
leaks. During the 2nd quarter of the hour from the start of
the test, no pressure drop should be detected by the pres-
sure gauge. Any gas leaks must be found by using only
water soap solutions, or an equivalent product, and elimi-
nated.
Never look for gas leaks using a naked flame.
For fitting the boiler:
- Place the steel mounting template on to the wall.
- Determine the position of the holes for fixing the support
bracket.
- Drill the holes and fix the support bracket using the screw
anchors supplied with the boiler.
- Engage the boiler on to the support bracket.
- Mark the positions of the gas, cold water supply, hot water
outlet, CH flow and return, pressure relief valve and/or
condensate drain.
DANGER!
The gas connection must be carried out only
by a qualified engineer who will have to res-
pect and comply to the regulations in force
and to the requirements indicated by the lo-
cal gas supplier. An incorrect installation
could cause injury to persons, animals or
damage to property. The manufacturer shall
not be held liable for any injury and/or dama-
ge.
Before installing the boiler it is recommen-
ded to thoroughly clean all the fuel feed pi-
pework in order to remove any eventual resi-
dual grime which could compromise the boi-
lers correct functioning.
If you smell gas:
a) Do not turn on or off electrical switches,
use the telephone or any other object
which can provoke sparks;
b) Open all doors and windows in order to
allow fresh air to enter and purify the
room;
c) Close all gas cocks
d) Contact a service engineer, qualified in-
staller or the gas supply company.
3.6 - GAS CONNECTION