2: General Description
2-4 UPS453-01-00 MINIpowerPLUS User Manual Dated 08-03-12
The voltage booster stage obtains its power from the batteries, and when the UPS operates in this mode the
operator is informed that the battery is ‘on load’ and therefore discharging, and a number of alarms activate at
preset voltage levels as the battery discharges. The operating threshold and function of these battery alarms
can be set by the operator through the UPS Setup menu to suit local application requirements.
Bypass operation
When operating in the bypass mode the bypass circuit totally excludes the UPS and connects the UPS input
supply directly to the UPS output.
The UPS automatically switches to bypass operation if:
• the UPS develops a fault which renders it unable to sustain the UPS output supply
• the UPS is shutdown for maintenance or repair purposes
• (momentarily) to assist the UPS handle an overload condition that exceeds the inverter rating
During normal operation the inverter is synchronised to the incoming mains supply so that when a transfer to
the bypass mode is required it takes place in a synchronised manner to prevent the risk of a power break or
excessive voltage.
A dedicated bypass configuration menu provides a means of customising the by-pass circuit operation to
meet specific application demands. This feature provides many options such as: ‘automatic’, ‘disabled’, ‘by-
pass in load waiting’ mode, etc.
2.4 Warranty
The MINIpowerPLUS is supplied with a limited warranty that the UPS and its component parts are free from
material and manufacturing defects for a period of one year from the date of original commissioning or fifteen
months from the date of original delivery, whichever is the sooner. This warranty is the only warranty given
and no other warranty, express or implied, is provided.
This warranty will be invalidated if the UPS is put into use without having first been commissioned by a fully
trained and authorised engineer, unless the UPS is supplied with the batteries already fitted and connected.
This warranty does not apply to any losses or damages caused by misuse, abuse, negligence, neglect,
unauthorised repair or modification, incorrect installation, inappropriate environment, accident, act of God or
inappropriate application.
If the UPS fails to conform to the above within the warranty period then Uninterruptible Power Supplies Ltd..
will, at its sole option, repair or replace the UPS. All repaired or replaced parts will remain the property of
Uninterruptible Power Supplies Ltd..
As a general policy, Uninterruptible Power Supplies Ltd. does not recommend the use of any of its products
in life support applications where failure or malfunction of the product can be reasonably expected to cause
failure of the life support device or to significantly affect it’s safety or effectiveness. Uninterruptible Power
Supplies Ltd. does not recommend the use of any of its products in direct patient care. Uninterruptible Power
Supplies Ltd. will not knowingly sell its products for use in such applications unless it receives in writing
assurances satisfactory to Uninterruptible Power Supplies Ltd. that the risks of injury or damage have been
minimized, the customer assumes all such risks and the liability of Uninterruptible Power Supplies Ltd. is
adequately protected under the circumstances.
Key Point: When the UPS is operating on battery, if the UPS mains supply cannot be restored the
operator should arrange an orderly shutdown of the load before the UPS batteries reach a fully
discharged state, whereupon the UPS is forced to shut down.
CAUTION: The UPS contains batteries which must be re-charged for a minimum of 24 hours
every six months to prevent deep-discharging. Batteries that have been, for whatever reason,
deep-discharged are not covered by the warranty.