
FIXED OUTDOOR AIR INTAKE DAMPER
This damper is shipped inside the return air compartment. It is
completely assembled and ready for installation. A damper
baffle inside the hood is adjustable to provide variable
amounts of outdoor air intake on units that are not provided
with an economizer or a motorized damper option. Refer to
Figure 3.
Gasketing and mounting screws are provided in a parts bag
attached to the hood assembly. Apply gasketing to the three
flangesurfaces on the hood priorto installing the hood. Extend
gasketing 1/4 inch beyond the top and bottom of the two side
flanges to insure adequate sealing.
Adjusting the damper to the desired air flow may be done
before mounting the hood into position or (after installation) by
removing the front hood panel or the screen on the bottom of
the hood. Damper baffle in position 1 will allow approximately
10%recirculatedairflow, position2approximately15%and,to
allow approximately 25%, remove the damper baffle.
On units with bottom return air applications, install the damper
assembly over the opening in the side return air access panel.
Remove and discard the opening cover and the covering over
the hood mounting holes (used for shipping) before installing.
Secure with the screws provided.
On units with side return air applications, install the damper
assembly on the return air ductwork as close to the unit as
possible. Cut an opening 16 inches high by 18 inches wide in
the ductwork to accommodate the damper. Using the holes in
the hood flanges as a template, drill 9/64 inch dia. (#26 drill)
holes into the ductwork and secure with the screws provided.
CAUTION: If outdoor air intake will not be required on units
with bottom return air applications, the damper
assembly should still be mounted on the side
returnairaccesspanel,pertheinstructionsabove,
to insure moisture is not drawn into the unit during
operation. The covering over the mounting holes
onlyneedberemoved.Do not remove the opening
cover.
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install a condensate drain
line from the one-inch NPT female connection on the unit to an
open drain.
An alternate drain connection (one-inch NPT female coupling)
is provided inboard on the same centerline as the exterior
location.
NOTE: The condensate drain line MUST be trapped to pro-
vide proper drainage. See Figure 4.
COMPRESSORS
Unitsareshippedwithcompressormountingsfactory-adjusted
and ready for operation.
CAUTION: Do Not loosen compressor mounting bolts.
FILTERS
Two-inchfiltersaresuppliedwitheachunit.Filtersmustalways
be installed ahead of the indoor coil and must be kept clean or
replaced with same size and type. Dirty filters will reduce the
capacity of the unit and will result in frosted coils or safety
shutdown.Minimum filter areaandrequiredsizesareshownin
Table 4.
SERVICE ACCESS
Access to all serviceable components is provided by the
following removable panels:
•Compressor compartment
•Electric Heat compartment
•Side Supply & Return Air compartments (Two panels)
•Blower compartment (Three panels)
•Main control box
•Filter compartment
•Outdoor Air compartment (Two panels)
Refer to Figure 9 for location of these access panels.
CAUTION: Make sure that all screws and panel latches are
replaced and properly positioned on the unit to
maintain an air-tight seal.
THERMOSTAT
The room thermostat should be located on an inside wall
approximately 56 inches above the floor where it will not be
subject to drafts, sun exposure or heat from electrical fixtures
or appliances. Follow manufacturer's instructions enclosed
withthermostatfor general installationprocedure.Colorcoded
insulated wires (#18 AWG) should be used to connect
thermostat to unit.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the
National Electrical Code, ANSI / NFPA No. 70 (in U.S.A.),
currentCanadianElectricCode(CEC)CSAC22.1 (inCanada)
and/orlocalordinances.Theunitmustbeelectricallygrounded
in accordance with NEC and CEC (as specified above) and/or
local codes. Voltage tolerances which must be maintained at
the compressor terminals during starting and running
conditions are indicated on the unit Rating Plate and Table 1.
The internal wiring harness furnished with this unit is an
integral part of a ETL and CGA design certified unit. Field
alteration to comply with electrical codes should not be
required.
4 Unitary Products Group
530.22-N5W
FIG. 3 - FIXED OUTDOOR AIR DAMPER
FIG. 4 - RECOMMENDED DRAIN PIPING