INSPECTION
Assoonasaunitisreceived,itshouldbeinspectedforpossible
damage during transit. If damage is evident, the extent of the
damageshould benoted onthe carrier'sfreight bill.Aseparate
request for inspection by the carrier's agent should be made in
writing.
LIMITATIONS
These units must be installed in accordance with all national
andlocalsafetycodes.Ifnolocalcodesapply,installationmust
conform with the appropriate national codes. See Table 1 for
Unit Application Data. Units are designed to meet National
SafetyCodeStandards.Ifcomponentsaretobeaddedtoaunit
to meet local codes, they are to be installed at the dealer's
and/or the customer's expense.
LOCATION
Use the following guidelines to select a suitable location for
these units.
1. The condensing unit is designed for outdoor installation
only. Thecondenser fansarethe propellertypeand arenot
suitable for use with ductwork.
2. The condensing unit and the evaporator blower should be
installed as close together as possible and with a minimum
numberofbendsintherefrigerantpiping.Referto“RE-
FRIGERANT PIPING” for additional information.
3. The condensing unit should not be installed where normal
operating sounds may be objectionable. On either rooftop
orgroundlevelinstallations,rubberpaddingcanbeapplied
between the base rails and their supports to lessen any
transmission of vibration.
ROOF-TOP LOCATIONS
Becarefulnottodamagetheroof.Consultthebuildingcontrac-
tororarchitectiftheroofisbonded.Choosealocationwithade-
quate structural strength to support the unit.
The condensing unit must be mounted on solid level supports.
The supports can be channel iron beams or wooden beams
treated to reduce deterioration.
Aminimum of two (2) beams are required to support each unit.
The beams should: (1) Be positioned perpendicular to the roof
joists.(2)Extendbeyondthedimensionsoftheunittodistribute
the load on the roof. (3) Be capable of adequately supporting
theentireunitweight.RefertoFigure1andTable2forloaddis-
tribution and weights.
Thesebeamscanusuallybesetdirectlyontheroof.Flashingis
not required.
NOTE: On bonded roofs, check for special installation
requirements.
GROUND LEVEL LOCATIONS
The units must be installed on a one-piece level concrete slab
with a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the units overall base
dimensions. Refer to Figure 4.
Footers under the slab that extend below the frost line is rec-
ommended.Any strainon therefrigerant linesmaycause are-
frigerant leak. The slab should not be tied to the building
foundation because noise and vibration will telegraph into the
building.
A unit can also be supported by concrete piers. These piers
should (1) extend below the frost line, (2) be located under the
unit's four corners, and (3) be sized to carry the entire unit
weight. Refer to Figure 1 and Table 2 for the center of gravity
and unit weight.
CAUTION: Care should be taken to protect the unit from tam-
pering and unauthorized persons from injury.
Screws on access panels will prevent casual tam-
pering. Additional safety precautions such as
fences around the unit or locking devices on the
panels may be advisable. Check local authorities
for safety regulations.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any pack-
aging until the unit is near the place of installation.
Rigthe unitby attaching chainor cableslingswith hooksto the
round lifting holes provided in the base rails.
CAUTION: Spreaders, longer than the largest dimension
across the unit, MUST be used across the top of
the unit.
WARNING:BEFORE LIFTING A UNIT, MAKE SURE THAT
ITS WEIGHT IS DISTRIBUTED EQUALLY ON
THE CABLES SO THAT IT WILL LIFT EVENLY.
Units may also be moved or lifted with a fork-lift from the front,
rear or the compressor end only through the slotted openings
provided in the base rails.
Unitary Products Group 3
035-17393-000 Rev. A (0501
INSTALLATION
MODEL HAHB180 & 240
Voltage Variation1
Min. / Max. 208/230-3-60 187 / 252
460-3-60 414 / 506
Ambient Air on Con-
denser Coil
Min. / Max.
Standard 45°F / 115°F
with Head Pressure
Control 0°F / 115°F
1Utilization range “A” in accordance with ARI Standard 110.
2The minimum allowed ambient temperature for mechanical cooling without the head pres-
ure control accessory installed must be raised if the indoor air flow is less than the
minimum value given in the capacity tables.
TABLE 1 - UNIT APPLICATION DATA
FIG. 1 - CENTER OF GRAVITY
Unit Dim. (in.)
AB
15 Ton 16 32
20 Ton 16 32