
035-16734-000 560.20-N1Y
Unitar
Products Group 5
LOCATION
1. Units ma
be located in the conditioned space or in an
adjacent room. Units ma
not be located outdoors, and
must be protected from freezin
.
2. Units should be installed in an area offerin
proper
power and control wirin
, condenser water pipin
, con-
densate trap and pipin
, overflow if required, heatin
pip-
in
if required, outdoor air duct if required, and suppl
and return air.
3. Suppl
air ma
be ducted or distributed with a plenum.
Return air ma
be ducted, unducted or returned throu
h
an inlet
rille. If the unit is to have an outdoor air intake,
it should be located near and outside wall.
Units should be located for ease of service, with adequate
clearance for compressor access, front and ri
ht side, fan
drive access, chan
in
filters, and heatin
coil service if
required. Refer to respective unit dimension detail (Fi
ure 2,
3, and 4) for required clearances.
FOUNDATION
1. Units ma
be placed on the floor or be elevated on a suit-
able platform.
2. No special foundation or isolation is required for most
applications.
a. Unit incorporates adequate isolation to eliminate
fan, compressor, and condensin
section vibration.
Flexible duct is also recommended.
b. It is not necessar
to bolt unit to the floor or support-
in
structure.
c. Floor or platform must be capable of supportin
the
operatin
wei
ht of the unit. See Table 2 for unit
wei
hts.
3. For installations requirin
extreme quiet operation, the
followin
precautions should be considered:
a. Locate unit outside the conditioned space.
b. Suppl
and return air ducts should be used, con-
nected to the unit with asbestos cloth collars, and
lined with sound absorbin
material.
c. Support the unit on a separate floor structure form
that of the conditioned space.
d. Place a non-deterioratin
sound isolation pad under
the entire unit base.
CLEARANCE
Clearance must be provided for:
1. Air intake and dischar
e – with or without ductwork.
2. Condenser water pipin
and connections.
3. Electrical power connections.
4. Heatin
coil pipin
and connections, if required.
5. Trapped condensate drain connection.
6. Maintenance and service access. Recommended mini-
mum clearances for units are shown on the unit dimen-
sion drawin
’s Fi
ures 2, 3, and 4. These clearances
are based on standard arran
ements of units. For non-
standard arran
ements, allow clearances that are in line
with the recommended minimum values shown.
RIGGING
1. Lift with slin
s under the unit.
2. Use spreader bars across the top of the unit to prevent
crushin
the unit frame and panels.
3. Avoid possible surface dama
e b
NOT removin
the
carton or the skids until the unit is at or near its final loca-
tion and soon to be installed.
UNCRATNG
Keep the units in their carton until moved close to point of
installation. Units are mounted on skids and should be
“trucked” to location in a vertical position. Under no circum-
stances should the
be “walked” on the corners of the crate.
1. Remove the shippin
carton.
2. Remove skid from under the unit.
3. Remove front access panel from condenser section.
This is necessar
for access to the electrical box, con-
denser water pipin
and the removal of compressor ship-
pin
blocks.
FOR WINTER SHUTDOWN, RESIDUAL WATER
MUST BE BLOWN FROM THE CONDENSER IF
THE UNIT IS LOCATED IN AN AREA WHERE
THE AMBIENT TEMPERATURE MAY DROP
BELOW 32°F OR IF THE UNIT HAS AN OUT-
DOOR AIR INTAKE.
TABLE 2: OPERATING AND SHIPPING WEIGHT
(LBS.)
MODEL C2ED 060 090 120 180
SHIPPING WEIGHT 452 755 809 1115
OPERATING WEIGHT 402 690 744 1040