Electrical Consideration / Precautions
The controller is considered “rack and panel mounted equipment” per EN 61010-1, Safety Requirements for
electrical equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements. Conformity
with 2/23/EEC Low Voltage Directive, requires the user to provide adequate protection against a shock hazard.
The user shall install this controller in an enclosure that prevents OPERATOR access to the rear terminals.
FAILURE TO COMPLY WITH THESE INSTRUCTIONS COULD RESULT IN DEATH OR SERIOUS INJURY.
Shielded twisted pair cable is required for all Analog Input & Output, Process Variables,
RTD, Thermocouple, DC volts-mV, low level signal, mA, Alarm Outputs, and Computer
communication interface circuits.
CAUTION
FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY RESULT IN PRODUCT DAMAGE.
Power Supply / Wiring Requirements
Applying 240V AC to a controller rated for 12-24VDC will severely damage the controller
and is a fire and smoke hazard.
This controller is suitable for connection to 230 15% VAC, 50 Hz power mains.+
It is the user responsibility to provide the following
230 15% VAC - a switch, fuse (1/2A, 250V) or a circuit breaker.+
The above items should be installed together with UT-1412 for the products electrical protection.
The switch, Fuse or circuit-breaker should be located close to the controller, within easy reach
operator. The switch or Circuit-breaker should be marked as the disconnecting device for the
controller. applying power to Multiple instruments, make sure that sufficient current is supplied,
Otherwise, the instruments may not start up normally due to the voltage drop caused by the in-
rush current.
FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY RESULT IN PRODUCT DAMAGE.
Disposal action of Instruments follows as per country and regional law and rules & regulation also same in
international. Company might be follows as per rules.
DISPOSAL ACTION
PRE CAUTIONS, WARNING AND DISPOSAL ACTION
Line voltage Wiring

@
+91 7046223333 , 9427301436
www.utplindia.in
www
1
UT-1403
TEMPERATURE + RH TRANSMITTER
CONTENTS
2. NSTALLATIONI
2.1 MOUNTING
2.2 EXTERNAL DIMENSION
2.3 TECHNICAL SPECIFICATIONS
2.4 WIRING DIAGRAM
1. OVERVIEW
1.1 INTRODUCTION
2
2
3
3
3
4
5
...................................................................................................
........... ..............................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
1.2 SAFETY NOTES 2
........... ..............................................................................

@
+91 7046223333 , 9427301436
www.utplindia.in
www
2
1. Introduction1
Function
Mount Anywhere
The UT-1403 product group is Process control instruments that must be panel mounted. The wiring terminals
-must be provided. the UT-1403 is environmentally hardened and, if suitably handled, can be mounted virtua
-lly anywhere in plant or factory; in a panel or enclosure wall mounted or Flameproof enclosure or even on
the process machinery. it can withstand ambient temperature up to 50°C. There are basically two mountings
available : Duct mount and Wall mount.
1. OVERVIEW
1.2 Safety Notes
Please read this manual carefully and completely before you use the device for the first time. The device may only
be used by qualified personnel and repaired by UNITECH Instruments personnel. There is no warranty of damages
or injuries caused by non-observance of the manual.
The device may only be used in approved temperature range.Ø
The opening of the case should only be done by qualified personnel.Ø
The instrument should never be placed in the highly power noise environment.Ø
You should not make any technical changes on the deviceØ
The appliance should only be cleaned with a clean damp cloth OR use only pH-neutral cleaner.Ø
UT-1403
TEMPERATURE + RH TRANSMITTER
Unitech Technocrats pvt. Ltd’s Temp Humidity Transmitter [UT-1403] is designed to sensing the Temperature
and Humidity parameters and transmitting in a Measuring signal as 4 to 20 mA for both parameters.
These instrument accepts inputs from standard temperature and RH (humidity) sensor attached to the
PCB, The PCB sense the Signal and Transmitter it to desired output as 4 to 20mA. This output used in
instrumentation or in automation with input scale-range for display or in a control.

@
+91 7046223333 , 9427301436
www.utplindia.in
www
3
2.1 Mounting
2.2 External Dimension
2. INSTALLATION
All dimensions are in mm
CAUTION
The product can be mounted on tilted or horizontal
panel using the mounting clamps supplied. Proper
space must be available at the back of the panel for
installation and maintenance activity.
Installation Mounting Precautions
FAILURE TO COMPLY WITH THESE INSTRUCTION MAY
RESULT IN INSTRUMENT DAMAGE
UT-1403
TEMPERATURE + RH TRANSMITTER
100.0
25.0
40.0
25.0
40.0
25.0
150.0
25.0
100.0
* THIS LENGTH VERY AS PER STANDARD SIZE
*
Duct Mount
Wall Mount
HVAC
DUCT
TM
TM
Duct Mount
Wall Mount

@
+91 7046223333 , 9427301436
www.utplindia.in
www
4
2.3 Technical Specifications
TECHNICAL SPECIFICATIONS
FLAME PROOF ENCLOSURE
Cable Entry 8 X 3/4” ET
Display Glass Clear glass thougnet type A as per IS 2206
Degree Protection IP 65 as per IS 2147
Enclose Certification
Gas Group
Enclosure is certified by C.M.R.I.
I IIA IIB as per IS 2148/1981
MOC Aluminium Alloy
FlameProof
[Optional]
UT-1403
TEMPERATURE + RH TRANSMITTER
Air and non-combustible gas
Temp : +/- 0.25 *c and humidity : +/- 1.7 %
Membranes filter.
Rs 485 Or Wireless (RF).
4-20mA / 0-10 v DC(2 wire Or 4 wire).
Field adjustable 0.5~15s.
IP65 / FLP / Clean room (SS).
100 mm X 80 X 40 mm
Power Supply 24VDC
Range Temp : -20....60 *c & Humidity -0...100 % (Programable)
OP. Temperature Range -40 ~ 70°C.
Electrical Consumption <45mA.
Pressure connection duct Mounted : 150 mm Or 300 MM
Electrical Connection 2.5 sq mm cable terminal
Accuracy
Sensor Protection
Communication Output
Output Signal
Response Time
Protection class
Enclosure Size
Medium

@
+91 7046223333 , 9427301436
www.utplindia.in
www
5
2.4 Wiring Diagram
CAUTION
WIRING CONSIDERATION
Shielded twisted pair wire is used for all analog I/P, Process sensors RTD,
Thermo-couple, mV-mA DC, Volt DC, Linear input and Communication.
AILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULTF
IN INSTRUMENT DAMAGE
CAUTION
LINE VOLTAGE
This product is suitable for connection 110/230VAC, 50Hz or 12/24 VDC main power
supply. It is user responsibility to provide proper protection for the products electrical
protection .
when applying power to various instruments, make sure sufficient current is supplied.
otherwise the instruments may not start up due to the Voltage drop.
AILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULTF
IN INSTRUMENT DAMAGE
UT-1403
TEMPERATURE + RH TRANSMITTER
TERMINAL DETAILS
234156
+-++++-
24VDC
SUPPLY TR
mA OUT
RS-485
COMM.
+
24VDC
-
1 2 3 4 5 6
SUPPLY
+
TEMP.
+
+
RS-485
-
RH COMM.
mA OUT
UT-1403
24VDC
12
DC SUPPLY
+-
SUPPLY
4~20/0~20mA
0~10
42
V
RETRANSMISSION
COMMUNICATION
RS-485
56
COMMNICATION
D+ D-
4~20/0~20mA
0~10
32
V
RETRANSMISSION
OUTPUT-1 [TEMP.] OUTPUT-2 [RH]

Table of contents
Other Unitech Transmitter manuals
Popular Transmitter manuals by other brands

Midland
Midland ALAN 507 SpeakEasy user manual

Zaxcom
Zaxcom TRXFB3 user manual

NIVELCO
NIVELCO EchoTREK SG-300 series Installation and programming manual

SSS Siedle
SSS Siedle VBS 650-0 Product information

Vestamatic
Vestamatic VestaFunk MS16 Series Installation and operating instructions

Widex
Widex SCOLA TEACH44 User instructions