Vaventis fresh-r On-The-Wall User manual

IMPORTANT: Read this manual carefully before installing the fresh-r®!
Keep this manual for future use.
On-The-Wall
Installation manual

2
Installation manual
Foreword
Installation manual for the contractor
Dear contractor,
Thank you for purchasing the fresh-r®On-The-Wall or the fresh-r everywhere® On-The-Wall .
This manual is intended for professionals and contains all the necessary installation information.
To install the fresh-r®correctly and safely, it is essential that you read this information carefully
and familiarize yourself with the fresh-r®before you start. The fresh-r requires a fused 230 V
mains electricity supply and must be connected by a qualied electrician.
Other information relating to the target group can be found in chapter 2.
The information in this manual is important for the correct and safe installation of the fresh-r®.
With the table of contents you’ll be able to nd the right information in the manual quickly.
This is the installation manual. Besides this manual there is also an user manual available.
NOTICE
This manual covers two fresh-r systems:
1. fresh-r®On-The-Wall
2. fresh-r everywhere®On-The-Wall
Therefore some illustrations might dier from the actual model you have purchased.
Details about the fresh-r everywhere®On-The-Wall are to be found in appendix 15.2.

3
Contents
1. Intended use 4
2. Target group 4
3. Symbols used in this manual 4
3.1 Safety symbols 4
3.2 Other symbols 4
4. General safety instructions 5
5. Main components 5
6. Tools needed for the installation 6
7. How to install the fresh-r®? 6
8. Connect the fresh-r®to the internet 20
9. Installation checklist 22
10. Specications 23
11. Who can I contact for questions, spareparts or more information? 23
12. Warranty 23
13. Frequently asked questions 24
14. Declaration of conformity 26
15. Appendix 27
15.1 Technical drawings 27
15.1.1 fresh-r® 27
15.1.2 fresh-r® with rectangular duct on top 28
15.1.3 Outer wall template 29
15.2 Fresh air everywhere®: connect to your in-house ventilation system 30
15.2.1 Rectangular duct dimensions 31
15.2.2 Rectangular right angle duct dimensions 31
15.2.3 Rectangular ro round duct dimensions 32

4
1. Intended use
The fresh-r®On-The-Wall is a decentral ventilation unit with heat recovery. The fresh-r®takes
heat from the stale air it expells and uses it to warm up the fresh air it brings in from outside.
It improves air quality for a healthy indoor air quality and at the same time reduces your energy
bill. No ducting is needed for this unit, which makes installation easier than a conventional HRV
system. The fresh-r®is equipped with CO², RH and temperature sensors and has an intelligent
control system and other than conventional HRV’s the fresh-r®also works ecient at sub zero
temperatures.
The fresh-r®On-The-Wall may only be installed on a wall.
2. Target group
The manual describes how to install the fresh-r®. The installation must be done by contractors
who are familiar with local building regulations.
Connecting the fresh-r®to the mains electricity supply must be done by a qualied electrician.
3. Symbols used in this manual
3.1 Safety symbols
DANGER
Indicates an immediate risk of irreversible injury or death when
not observed.
WARNING
Indicates a risk of severe personal injury and/or serious damage
to the product if the procedures are not followed carefully.
CAUTION
Indicates that the product may be damaged if the procedures are
not followed carefully.
NOTICE
Alerts the user to additional information and possible problems.
3.2 Other symbols
CE marking: This is the CE logo indicating that the fresh-r®meets the legal
requirements.

5
4. General safety instructions
DANGER
• Connecting the fresh-r®to the mains electricity supply must be done by a qualied
electrician.
• Risk for electric shocks or electrocution. Turn o the mains electricity supply in the
distribution box before connecting the fresh-r®electrically.
• The person responsible for installing the fresh-r®should be familiar with the local
building regulations.
5. Main components
AB
C
D
E
F
G
H
g. 1 Main components
top side
A. ON/OFF switch
B. Power connection wire
C. Unibody
D. Front door (connected to the Unibody)
E. Grilles
F. Grille cover
G. Grille assembly (2pcs)
H. Duct pipes with EPP covers (2pcs)

6
I
J
g. 2 Main components
I. Fresh air input socket, with fan (for upper duct pipe)
J. Stale air output socket (for lower duct pipe)
6. Tools needed for the installation
• Equipment to drill 2 round holes (Ø 160 mm) in the wall (typically water-cooled
diamond core drill)
• Pozidriv nr. 3 screwdriver
• 8 mm masonry drill
• PVC cement (this is standard glue for hard PVC)
• Spirit level (or another tool to check for a prefect vertical position)
• Deburring or grinding tool, such as a le
• EPP Glue and expanding foam
7. How to install the fresh-r®?
DANGER
• The person responsible for installing the fresh-r®should be familiar with the local
building regulations.
Please follow steps 1 to 10.
1 Check the contents
1 × Cardboard wall-cut/drilling template 2 × Grilles assembly
1 × Front door 3 × Bags with content:
2 × PVC pipe • Bag A, 4 screws 6 x 120 and 4 plugs
2 × EPP pipe • Bag B, Mounting kit for grilles
1 × User manual • Bag C, Spare parts kit
1 × Installation manual

7
2 Prepare the wall
You will need two round holes (Ø 160 mm) in the outer wall of the building, for the air
pipes; the lowest hole needs to have a slope of 2 degrees. You also need four holes in
order to attach the fresh-r®on the wall with four screws 6 x 120.
For ecient ventilation place the unit centrally in the room, ideally at least at 80 cm from
the oor level, but not too high. You must be able to see the controls easily.
Mark the openings using the cardboard wall-cut/drilling template supplied. See g. 3 and g. 4.
Draw the holes
To draw the holes, do the following:
1. Place the template against the outer wall, make sure it’s vertically leveled.
2. Tape the template on the wall. Use removable tape in the corners.
Make sure “UP” is visible and is pointing upwards.
3. Mark the centres of the big holes by tracing the four notches around the hole.
Use a pencil and a ruler to make two crosses. The crosses mark the centres of the
holes.
4. Mark the centre of the four corner holes.
5. Remove the template.
Check the centre distance of the two big holes.
The centre distance should be 897 mm.
UP UP
g. 3 Ensure the template is vertically leveled g. 4 Draw two centres using the template
897 mm

8
The big holes
To drill the lower big hole (160 mm), do the following:
1. Drill through the outer wall(s) at a downward angle of 2 degrees.
This is to allow the condensate to drain towards outside.
To drill the upper big hole (160 mm), do the following:
1. Drill straight through the wall(s).
A
A
g. 5 Make sure the wall is well prepared
2. Remove dust and other materials from the holes.
3. Get a duct pipe (this is the blue PVC pipe) with EPP cover (this is a foam tube) and
try if it ts the holes.
The four corner holes
To drill the four corner holes, do the following:
1. Check the dimensions as shown in g. 6.
2. Drill the four corner holes. Use a 8 mm masonry drill.
3. Place plugs into the four corner holes.
You’ll nd the plugs in bag A.
2 degrees
160 ± 2 mm
897± 2 mm
Inside the
house
Outside the
house
Section cut AA
160 ± 2 mm

9
g. 6 Check the dimensions of the corner holes before drilling
243 mm
105 mm
111 mm
1055 mm

10
3 Cut the duct pipes
NOTICE
Make sure if you cut the duct pipes, the part you want to keep has a lip.
To cut the duct pipes, do the following:
1. Remove the EPP covers.
2. Cut the upper duct pipe (input fresh air) to the total width of the
wall (D1) + 15 mm.
Tip: Use a wide tape or two paper sheets taped together to mark the duct pipes and get a
perpendicular cut.
3. Cut the lower duct pipe (output stale air) to the total width of the
wall(s) (D1) + 55 mm.
4. Deburr the duct pipes. Use a deburring tool, such as a le.
D1
D1 + 15 mm
D1 + 55 mm
g. 7 Determine D1 g. 8 Make the duct pipes to the correct size

11
4 Place the duct pipes in the Unibody
NOTICE
Use the provided EPP glue for the lower duct pipe. The lower duct pipe is the condensate
drain and needs to be water tight. Apply PVC glue to the last 3 cm of the duct and to
the white ring. Make an airtight connection: the air in the ducts can be very cold. No
warm, moist indoor air may reach the cold ducts.
1. Put PVC glue on the white ring which is located in the inside of the stale air output
socket (see g. 9). Do not put PVC glue on the freh air input tube.
g. 9 Put PVC glue in the stale air output socket on the white ring only
2. Place the duct pipes into the Unibody.
Make sure the lips are pointed towards the bottom side of the Unibody.
These are needed to mate with the outside wall grills.
g. 10 Place the PVC duct pipes into the Unibody
PVC glue
NO PVC glue
Bottom side

12
3. Put EPP glue on the Unibody around the PVC duct pipes
g. 11 Put EPP glue on the Unibody around the PVC duct pipes
4. Place the EPP covers on the duct pipes.
g. 12 Place the EPP covers
Epp glue
Epp glue

13
5. Put EPP glue around the edges of EPP covers of the upper duct pipe and the lower
duct pipe.
NOTICE
The connection of the lower duct pipe and the upper duct pipe to the Unibody needs to be
airtight because air leaks can create unwanted condensation.
g. 13 Put EPP glue around the edges of the covers
6. Cut the Epp covers. They need to cover the whole duct pipe.
The lips need to extend beyond the covers.
g. 14 Cut the EPP covers
g. 15 The lips need to extend beyond the covers
Epp glue
Epp glue

14
5 Mount the Unibody on the wall
1. Remove the four corner bolts (don’t remove the middle bolts).
g. 16 Remove the four corner bolts
2. Put expanding foam around the edge of both EPP covers. Make sure the expanding
foam insulate the whole edge of the EPP covers in order to prevent air leaking
(regarding the inner wall).
g. 17 Put expanding foam around the edge of both EPP covers.
3. Place the Unibody in vertical position and open the door as far as possible.
4. Press the two storm ap levers to ensure they are open.
DON’T remove the
two middle bolts
Remove the four
corner bolts

15
g. 18 Press the two storm ap levers
The following steps need to be done by two persons.
First read step 5, 6 and 7 so you are well prepared. Then perform the actions.
CAUTION
Be carefull with the door. Giving too much pressure can damage the door or it’s hinges.
g. 19 Be carefull with the door
DON’T apply force to
the the door, when
raising the fresh-r®.

16
5. The rst person:
Hold the Unibody as shown in g. 20. Place the Unibody with the upper duct pipe
and lower duct pipe in the wall. See g. 21.
CAUTION
Hold the Unibody till it’s mounted with the four 6 x 120 screws.
g. 20 Hold the Unibody as shown in this
gure
g. 21 Place the Unibody on the wall
6. The second person:
Mount the 6 x 120 screws in each corner of the Unibody (4 ×). Use a screw driver.
CAUTION
The ducts and the holes must have an air tight seal. To establish this, it’s critical that all
four screws are properly functioning. Make sure the fresh-r®is pushed rmly to the wall
when attaching it.
NOTICE
When you are installing the fesh-r everywhere®, now use the extract ducts to make a
connection to your in-house ventilation system. See for more information Appendix 15.2.

17
7. Seal between the EPP cover and the outer wall with outdoor silicone kit. Make sure
you use enough expanding foam . Make sure the connection between the pipes and
the outer wall is airtight. This will prevent air leaking.
g. 22 Seal between the EPP cover and the outer wall with outdoor silicone kit
6 Connect the fresh-r®electrically and test its functionality
DANGER
• Connecting the fresh-r®to the mains electricity supply must be done by a qualied
electrician.
• Risk for electric shocks or electrocution. Turn o the mains electricity supply in the
distribution box before connecting the fresh-r®electrically.
Do the following:
1. Turn o the main electricity supply in the distribution box before attempting to wire
in the fresh-r®.
2. Make the electrical connection while the fresh-r®is turned OFF.
The electric cable location is on the left hand top.
g. 23 Location of the electric cable
(outside of the house)

18
3. Turn the main electricity supply ON again at the distribution box.
4. Turn the fresh-r®ON and wait for approximately 1 minute while the unit boots up.
If you see three illuminated lights and notice fans running, the unit is properly
functioning.
If not:
Check the main electricity supply. If the product still does not work, turn the unit
OFF and contact your supplier.
7 Place the grilles assembly (nd the content in Bag B)
Do the following:
1. Mount the grilles on the outer face of the outside-wall.
2. Place the covers.
NOTICE
The lip of the lower duct pipe should overlap with the edge of the grilles cover so
condensate water is guided from the outer wall.
g. 24 Place the grid assembly

19
g. 25 Lip should overlap with the edge of the grilles

20
8. Connect the fresh-r®to the internet
By connecting the fresh-r®to the internet you will benet from automatic sotware updates. You will
also have access to data graphs showing actual performance values of the air temperature and
quality.
To connect your fresh-r®to the internet do the following.
1. Switch power of the the fresh-r®OFF and switch the power ON again.
Wait for 30 seconds.
2. Press the middle button (increase fan speed) for approximately 5 seconds until you
hear a beep. Then wait 10 seconds.
3. Press the lower button (decrease fan speed) for approximately 5 seconds until you
hear a beep - the WiFi chip is now in access point mode.
The following actions must be done with your smartphone, laptop or tablet.
Do the following:
4. Start your device and go to settings.
5. Select WiFi.
6. Select WiFly-EZX-XX from the list of WiFi connections.
Your device will now connect to the fresh-r®WiFi.
7. Open an internet browser, for example Google chrome.
8. Type 192.168.1.1 and conrm.
The Microchip settings page opens.
9. Select the Network cfg tab.
This manual suits for next models
1