Vega VEGACAL 63 Wiring diagram

Supplementary instructions
Screening tube adapter
for VEGACAL 63, 64/VEGACAP 63
Rod ø 16 mm
Document ID: 34849

2
1 Product description
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
1 Product description
The screening tube adapter can be used for all VEGACAP 63 and
VEGACAL 63 and 64 sensors with rod ø 16 mm (0.63 in).
Typical applications of the screening tube adapters are e.g. for con-
densation or sockets.
Apart from the standard version there is a second version for vacuum
with a special seal.
When the screening tube adapter is submerged in liquid, we recom-
mend the use of a vacuum-tight version.
The following versions of the screening tube adapter are available:
Screening against condensation
•Screening against measurement faults caused by condensation.
•Screening against high capacitances caused by installation condi-
tions. This can occur, e.g. in long sockets.
Capacitive screening, vacuum-tight
•Screening against high capacitances caused by installation condi-
tions. This can occur, e.g. in long sockets. In addition, the screen-
ing tube is vacuum-tight.
In case of strong condensation, the draining of condensed water
can change the measurement accuracy. The suitable version is the
Screening against condensation. The condensation can drain o
outside on the screening tube adapter.
In case of long sockets, the screening tube can increase the sensitiv-
ity of the probe by compensating the inuences of the socket. The
suitable version is Capacitive screening, vacuum-tight.
When the probe is mounted laterally, buildup can accumulate in the
socket. A screening tube makes the covered part of the probe inactive
and hence insensitive to inuence from buildup and socket. Hence,
the screening tube adapter excludes changing inuences caused by
the medium and ensures stable measurement conditions. The suit-
able version is Capacitive screening, vacuum-tight.
Condensation
Socket

3
2 Mounting
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
2 Mounting
2.1 Version: screening against condensation
1
2
3
4
Fig. 1: Mounting of the screening tube adapter - screening against condensation
1 Probe
2 Process seal
3 Screening tube adapter
4 Centering cone (PTFE)
Caution:
Check the insulation of the probe for deep scratches.
To ensure the seal eect of the screening tube adapter, the isolation
of the probe must be undamaged in the area of the lower screening
tube adapter end.
1. Place the process seal (2) on the thread of the probe
2. If it is harmless to the process, grease the two O-rings with an
acid-free grease so that the rod of the probe slides more easily
3. Push the rod of the probe (1) through the screening tube adapter
(3)

4
2 Mounting
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
4. Screw the screening tube adapter (3) onto the thread of the probe
and tighten with 100 Nm (74 lbf ft) (SW 46)
The mounting of the screening tube adapter is now nished. The
probe can now be installed.
You can nd the mounting procedure in the operating instructions of
the probe.
Note:
The VEGACAP probe must be re-compensated after mounting the
screening tube adapter. Use the compensation key on the electronics
module. You can nd the instructions for this in the operating instruc-
tions of the probe.
2.2 Version: capacitive screening, vacuum-tight
1
2
3
4
5
Fig. 2: Mounting of the screening tube adapter - capacitive screening, vacuum-
tight
1 Probe
2 Process seal
3 Screening tube adapter
4 O-rings (2 pcs.)
5 Pressure screw

5
2 Mounting
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
Caution:
Check the insulation of the probe for deep scratches.
To ensure the seal eect of the screening tube adapter, the isolation
of the probe must be undamaged in the area of the lower screening
tube adapter end.
1. Loosen and remove (SW 24) pressure screw (5)
2. Remove the two O-rings (4) from the screening tube
3. Place the process seal (2) on the thread of the probe
4. Push the rod of the probe (1) through the screening tube adapter
(3)
5. Screw the screening tube adapter (3) onto the thread of the probe
and tighten with 100 Nm (74 lbf ft) (SW 46)
6. If it is harmless to the process, grease the two O-rings with an
acid-free grease so that the rod of the probe slides more easily
7. Slide the two O-rings (4) over the rod of the probe
8. Slide the pressure screw (5) of the screening tube adapter onto
the probe
9. Screw pressure screw (5) with the two O-rings into the screening
tube adapter and tighten it to the stop (SW 24)
The mounting of the screening tube adapter is now nished. The
probe can now be installed.
You can nd the mounting procedure in the operating instructions of
the probe.
Note:
The VEGACAP probe must be re-compensated after mounting the
screening tube adapter. Use the compensation key on the electronics
module. You can nd the instructions for this in the operating instruc-
tions of the probe.

6
3 Supplement
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
3 Supplement
3.1 Technical data
General data
Material 316L corresponds to 1.4404 or 1.4435
Material
ƲScreening tube adapter 316L
ƲPressure screw (only with version:
capacitive screening, vacuum-tight)
316L
ƲCentering cone (only with version:
screening against condensation)
PTFE
ƲProcess seal Klingersil C-4400
ƲO-ring seal (15.6 x 1.78) FKM (Viton)
Suitable probes VEGACAP 63, VEGACAL 63, VEGACAL 64 - require-
ment: ø 16 mm (0.63 in)
Process ttings
ƲInner thread G1 A, pipe thread, cylindrical (ISO 228 T1)
ƲOuter thread G1½ A, pipe thread, cylindrical (ISO 228 T1)
Weight
ƲBasic weight (approx.) 500 g (17.64 oz)
ƲPipe weight: ø 27 mm (1.063 in) 1000 g/m (10.75 oz/ft)
Screening tube length (L1) 0.07 … 6m (0.23 … 19.69 ft)
Max. torque (process tting - thread) 100 Nm (74 lbf ft)
Process conditions
Process temperature -40 … +150 °C (-40 … +302 °F), depending on process
tting
Process pressure
ƲScreening against condensation 0… 1 bar/-100 … 100 kPa (-14.5 … 14.5 psig), depend-
ing on the process tting
ƲScreening, vacuum-tight -1 … 40 bar/-100 … 4000 kPa (-14.5 … 580 psig), de-
pending on the process tting

7
3 Supplement
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
3.2 Dimensions
Screening tube adapter against condensation for VEGACAL/VEGACAP, rod
ø 16 mm (0.63 in)
ø 27 mm
(1 1/16")
G1 1/2
G1
SW 64
L1
ø 16 mm
(5/8")
24 mm
(15/16")
Fig. 3: Screening tube adapter against condensation for VEGACAL/VEGACAP, rod ø 16 mm (0.63 in)
L1 Length, screening tube adapter - see chapter "Technical data"

8
3 Supplement
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916
Screening tube adapter, vacuum-tight for VEGACAL/VEGACAP, rod ø 16 mm
(0.63 in)
ø 27 mm
(1 1/16")
L1
G1 1/2
G1
SW 64
ø 16 mm
(5/8")
24 mm
(15/16")
Fig. 4: Screening tube adapter, vacuum-tight for VEGACAL/VEGACAP, rod ø 16 mm (0.63 in)
L1 Length, screening tube adapter - see chapter "Technical data"

9
Notes
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916

10
Notes
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916

11
Notes
Screening tube adapter • for VEGACAL 63, 64/VEGACAP 63
34849-EN-130916

Printing date:
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
34849-EN-130916
All statements concerning scope of delivery, application, practical use and operat-
ing conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice
© VEGA Grieshaber KG, Schiltach/Germany 2013
Phone +49 7836 50-0
Fax +49 7836 50-201
E-mail: [email protected]
www.vega.com