Vega VEGACONNECT User manual

Operating Instructions
Interface adapter between PC and
communication-capable VEGA
instruments
VEGACONNECT
Wired interface adapter with connection box
USB - HART/I²C
Document ID: 66081

2
Contents
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
Contents
1 About this document ............................................................................................................... 3
1.1 Function ........................................................................................................................... 3
1.2 Target group ..................................................................................................................... 3
1.3 Symbols used................................................................................................................... 3
2 For your safety ......................................................................................................................... 4
2.1 Authorised personnel ....................................................................................................... 4
2.2 Appropriate use................................................................................................................ 4
2.3 Warning about incorrect use............................................................................................. 4
2.4 General safety instructions............................................................................................... 4
2.5 Safety instructions for Ex areas ........................................................................................ 5
3 Product description................................................................................................................. 6
3.1 Conguration.................................................................................................................... 6
3.2 Principle of operation........................................................................................................ 7
3.3 Adjustment ....................................................................................................................... 8
3.4 Packaging, transport and storage..................................................................................... 8
4 Connection ............................................................................................................................. 10
4.1 Connection to the PC ..................................................................................................... 10
4.2 Connection of the sensor/controller................................................................................ 10
5 Connection examples............................................................................................................ 12
5.1 Connection by insertion into the device.......................................................................... 12
5.2 Connection via HART interface ...................................................................................... 13
5.3 Connection via I²C interface........................................................................................... 15
6 Setup ....................................................................................................................................... 16
6.1 Adjustment ..................................................................................................................... 16
7 Diagnostics and servicing .................................................................................................... 17
7.1 Maintenance .................................................................................................................. 17
7.2 Software update ............................................................................................................. 17
7.3 How to proceed if a repair is necessary.......................................................................... 17
8 Recycling and disposal ......................................................................................................... 18
8.1 Disposal ......................................................................................................................... 18
9 Certicatesandapprovals.................................................................................................... 19
9.1 Approvals for Ex areas ................................................................................................... 19
9.2 EU conformity................................................................................................................. 19
9.3 Environment management system ................................................................................. 19
10 Supplement ............................................................................................................................ 20
10.1 Technical data ................................................................................................................ 20
10.2 Dimensions .................................................................................................................... 21
10.3 Industrial property rights................................................................................................. 22
10.4 Trademark ...................................................................................................................... 22
Editing status: 2021-12-14

3
1 About this document
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
1 About this document
1.1 Function
This instruction provides all the information you need for mounting,
connection and setup as well as important instructions for mainte-
nance,faultrectication,theexchangeofpartsandthesafetyofthe
user. Please read this information before putting the instrument into
operation and keep this manual accessible in the immediate vicinity
of the device.
1.2 Target group
This operating instructions manual is directed to trained personnel.
Thecontentsofthismanualmustbemadeavailabletothequalied
personnel and implemented.
1.3 Symbols used
Document ID
This symbol on the front page of this instruction refers to the Docu-
ment ID. By entering the Document ID on www.vega.com you will
reach the document download.
Information, note, tip: This symbol indicates helpful additional infor-
mation and tips for successful work.
Note: This symbol indicates notes to prevent failures, malfunctions,
damage to devices or plants.
Caution: Non-observance of the information marked with this symbol
may result in personal injury.
Warning: Non-observance of the information marked with this symbol
may result in serious or fatal personal injury.
Danger: Non-observance of the information marked with this symbol
results in serious or fatal personal injury.
Ex applications
This symbol indicates special instructions for Ex applications.
• List
The dot set in front indicates a list with no implied sequence.
1 Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of bat-
teries and accumulators.

4
2 For your safety
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
2 For your safety
2.1 Authorised personnel
All operations described in this documentation must be carried out
onlybytrained,qualiedpersonnelauthorisedbytheplantoperator.
During work on and with the device, the required personal protective
equipment must always be worn.
2.2 Appropriate use
The instrument is an interface adapter for connecting a Windows PC
to communication-capable sensors.
Youcannddetailedinformationabouttheareaofapplicationin
chapter " Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.
2.3 Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-
tion-specichazards,e.g.vesseloverllthroughincorrectmounting
or adjustment. Damage to property and persons or environmental
contamination can result. Also, the protective characteristics of the
instrument can be impaired.
2.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives.The instrument must only be operated in a
technicallyawlessandreliablecondition.Theoperatorisresponsi-
ble for the trouble-free operation of the instrument.When measuring
aggressive or corrosive media that can cause a dangerous situation
if the instrument malfunctions, the operator has to implement suitable
measures to make sure the instrument is functioning properly.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regula-
tions.
The safety instructions in this operating instructions manual, the na-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.Forsafety

5
2 For your safety
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
reasons,onlytheaccessoryspeciedbythemanufacturermustbe
used.
To avoid any danger, the safety approval markings and safety tips on
the device must also be observed.
2.5 Safety instructions for Ex areas
For applications in explosion-proof areas (Ex), only devices with cor-
respondingExapprovalmaybeused.ObservetheEx-specicsafety
instructions.These are an integral part of the operating instructions
and are enclosed with every device with Ex approval.

6
3 Product description
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
3 Product description
3.1 Conguration
The scope of delivery encompasses:
• Interface adapter VEGACONNECT 4
• Connection box with two connection cables
• USB cable type A to type C
• HART resistance
• 2 x suspension catch
• Magnetic pen
• Bluetooth USB adapter
• Documentation
– This operating instructions manual
– Ex-specic"Safety instructions" (with Ex versions)
– Ifnecessary,furthercerticates
VEGACONNECT consists of the following components:
4 5
8
7
9
6
2
1
3
OPEN
TWIST
USB
LOCK
CONNECT
Fig. 1: Conguration VEGACONNECT
1 USB cable type A to type C
2 VEGACONNECT 4
3 Connection box with storage space
4 I²C bus cable
5 HART cable with 2 mm pins
6 2 x suspension catch for cable with 2 mm pins
7 Bluetooth USB adapter
8 HART resistance
9 Magnetic pen
On the back of the connection box there is a fold-out hook to hang the
device on a pipe, for example, if there is no place to put it. In addition,
Scope of delivery
Constituent parts

7
3 Product description
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
two magnets are embedded in the housing to attach the connection
box to ferromagnetic objects.
2
2
1
Fig. 2: Conguration VEGACONNECT
1 Fold out hook for hanging the VEGACONNECT
2 Magnets for attaching to metallic objects
Thetypelabelcontainsthemostimportantdataforidenticationand
use of the instrument:
• Instrument type
• Information about approvals
• Technical data
• Serial number of the instrument
• QR code for device documentation
• Manufacturer information
Move to " www.vega.com"andenterinthesearcheldtheserial
number of your instrument.
Thereyoucanndthefollowinginformationabouttheinstrument:
• Order data
• Documentation
• Software
Alternatively,youcanndallviayoursmartphone:
• Scan the QR-code on the type label of the device or
• Enter serial number manually in the VEGA Tools app (available
free of charge in the respective stores)
3.2 Principle of operation
VEGACONNECT is a wired interface adapter for connection of
communication-capable VEGA instruments to the USB interface of a
PC with Windows operating system. It can also be used as a universal
HART modem for HART sensors from other manufacturers. An ad-
justment software such as PACTware with VEGA DTMs is required for
parameter adjustment of these instruments.
Type label
Documents and software
Application area

8
3 Product description
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
The VEGACONNECT can be connected to all communication-capa-
ble VEGA instruments with respective interface. All currently available
electronics versions are supported.
Connection cable, adapter and terminals for connection to the dif-
ferent instrument series are attached to all VEGACONNECT. These
adapters can be kept in the storage space of the connection box.
The Bluetooth USB adapter enables the wireless adjustment of VEGA
sensors with a Windows PC. For this, a PLICSCOM with Bluetooth
option integrated in the sensor or an instrument with integrated
Bluetooth function are required. In this case, the VEGACONNECT is
not used, here the connection box is only a preserving possibility for
theBluetoothUSBadapter.Youcanndfurtherinformationofthisap-
plication in the operating instruction of PLICSCOM or the instrument
with integrated Bluetooth function.
The magnet pen enables the adjustment of the buttons of a Blue-
tooth-PLICSCOM with closed housing lid with inspection window.
In this case, the VEGACONNECT is not used, here the connection
boxisonlyapreservingpossibilityforthemagnetpen.Youcannd
further information of this application in the operating instruction of
PLICSCOM.
The interface adapter is connected via the USB interface to a PC. It
converts signals and protocols of the USB interface into the appropri-
ate signal/protocol of the connected instrument.
The voltage supply is provided via the USB interface of the PC.
3.3 Adjustment
The adjustment is carried out via a Windows PC with a parameter
adjustment software such as PACTware with respective DTM. There
are no adjustment elements on the instrument itself.
3.4 Packaging, transport and storage
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
The packaging consists of environment-friendly, recyclable card-
board. For special versions, PE foam or PE foil is also used. Dispose
of the packaging material via specialised recycling companies.
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or con-
cealed defects must be appropriately dealt with.
Bluetooth USB adapter
Magnetic pen
Functional principle
Voltage supply
Packaging
Transport
Transport inspection

9
3 Product description
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
• Not in the open
• Dry and dust free
• Not exposed to corrosive media
• Protected against solar radiation
• Avoiding mechanical shock and vibration
• Storage and transport temperature see chapter " Supplement -
Technical data - Ambient conditions"
• Relative humidity 20 … 85 %
Storage
Storage and transport
temperature

10
4 Connection
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
4 Connection
4.1 Connection to the PC
Note:
First install the software package " DTM Collection" before connecting
the VEGACONNECT to the PC.
An USB interface (1.1/2.0/3.0) is compulsory for connection of
VEGACONNECT to a Windows PC. The connection is provided with
the supplied USB cable.Voltage supply of VEGACONNECT is pro-
vided via the USB interface.
To operate the VEGACONNECT, a suitable Windows driver is re-
quired, which is included in our software package " DTM Collection".
This software package can be downloaded free of charge from our
homepage.To ensure the support of all device functions, you should
always use the latest version.
When installing the driver package " VEGA-DTM for Communication",
the suitable instrument driver is installed automatically. When con-
nectingVEGACONNECT,thedriverinstallationisnishedautomati-
cally and is ready for operation without a restart.
OPEN
TWIST
USB
LOCK
CONNECT
2
1
3
Fig. 3: Electrical connection
1 USB connection of the PC
2 USB cable type A to type C
3 Connection box with VEGACONNECT 4
4.2 Connection of the sensor/controller
The VEGACONNECT can be connected to almost any communica-
tion-capableVEGAinstrumentviadierentways.
Connection
DTM Collection

11
4 Connection
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
2 3
1
OPEN
TWIST
USB
LOCK
CONNECT
Fig. 4: Connection possibilities
1 Connection by insertion into a plics®sensor
2 Connection to 600 series controllers (I²C interface)
3 Connection to the 4 … 20 mA cable (HART protocol)
The VEGACONNECT can be inserted directly into all instruments of
the plics®series. In this case, the VEGACONNECT is removed from
the connection box and inserted ito the plics®instrument instead of
the display and adjustment module.
The connection via the sensor cable can be made with any HART
device. Depending on the power supply/processing system, an ad-
ditional HART resistor is required.The supplied HART resistor can be
used for this purpose (for details see " Connection examples - Con-
nection via HART interface").
The VEGACONNECT can be connected to the I²C bus interface of all
series 600 controllers (for details see " Connection examples - Con-
nection via I²C interface").
Connection by insertion
into the sensor
Connection via HART
Connection via I²C bus

12
5 Connection examples
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
5 Connection examples
5.1 Connection by insertion into the device
2
1
Fig. 5: Insertion into a plics®sensor
1 USB cable for connection to the PC
2 plics®device
3
2
1
Fig. 6: Insertion into VEGADIS 81
1 HART sensor
2 VEGADIS 81
3 USB cable for connection to the PC
plics®sensor
HART sensor with
VEGADIS 81

13
5 Connection examples
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
3 4
2
1
Fig. 7: Insertion into VEGADIS 82
1 HART sensor
2 VEGADIS 82
3 USB cable for connection to the PC
4 Processing system/PLC/Voltage supply
5.2 Connection via HART interface
If the resistance of the connected processing system is less than
230Ω,thedigitaladjustmentsignalisextremelydampedorshort-cir-
cuited. Digital communication with the PC is then no longer possible.
With low impedance processing systems, a resistance of at least
230Ωmustbeintegratedintothe4…20mAconnectioncable.The
connection of VEGACONNECT can be either carried out in parallel to
the sensor or via the resistor.
Note:
A HART resistor is already integrated in some controllers. These
devices have additional connection sockets for direct connection of
the 2 mm pins.
When using VEGAMET 624/625, VEGASCAN 693 controllers, the
connection cannot be carried out via the sensor cable.The parameter
adjustment of the controller as well as of the sensor can be carried
out via the I²C connection sockets.
HART sensor with
VEGADIS 82
HART communication

14
5 Connection examples
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
4
12
3
OPEN
TWIST
USB
LOCK
CONNECT
Fig. 8: Connection plics® series via HART
1 HART sensor
2 HART resistance 270 Ω (optional depending on processing)
3 Connection cable with 2 mm pins and terminals
4 Processing system/PLC/Voltage supply
Information:
The VEGACONNECT is connected directly via the 2 mm sockets of
the supplied HART resistor. Alternatively, the VEGACONNECT can
also be connected in parallel to the sensor (dashed line).
1
3
2
OPEN
TWIST
USB
LOCK
CONNECT
Fig. 9: Connection plics® series via HART to a VEGATRENN
1 HART sensor
2 Connection cable with 2 mm pins
3 VEGATRENN 141, 142, 151, 152
HART sensor on a PLC
HART sensor with
VEGATRENN

15
5 Connection examples
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
13
2
OPEN
TWIST
USB
LOCK
CONNECT
Fig. 10: Connection plics® series to a VEGAMET
1 HART sensor
2 Connection cable with 2 mm pins
3 VEGAMET
5.3 Connection via I²C interface
1
2
3
OPEN
TWIST
USB
LOCK
CONNECT
Fig. 11: Connection 600 series controllers via I²C interface
1 Sensor
2 I²C connection cable
3 VEGAMET/VEGASCAN 600 series
Note:
Communication with the sensor is carried out also via the front I²C
interface of the controller. The connection of VEGACONNECT directly
to the 4 … 20 mA sensor cable is not possible.
HART sensor with
VEGAMET
Controllers 600 series

16
6 Setup
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
6 Setup
6.1 Adjustment
The use and operation are described in the operating instructions of
the corresponding sensor/controller and its online help.
Information:
YoundtheVEGACONNECTDTMinthedevicecatalogueunderthe
group " Driver".When adding a HART sensors, the window " Channel
selection" appears in addition in which you have to select the connec-
tion (connection via HART or I²C).

17
7 Diagnostics and servicing
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
7 Diagnostics and servicing
7.1 Maintenance
If the device is used properly, no special maintenance is required in
normal operation.
The cleaning helps that the type label and markings on the instrument
are visible.
Take note of the following:
• Use only cleaning agents which do not corrode the housings, type
label and seals
• Use only cleaning methods corresponding to the housing protec-
tion rating
7.2 Software update
An update of the device software is possible via the USB interface.
The following components are required:
• PC/Notebook with PACTware/DTM
• Currentinstrumentsoftwareasle
Youcanndthecurrentinstrumentsoftwareaswellasdetailedinfor-
mation on the procedure in the download area of our homepage.
Caution:
Instruments with approvals can be bound to certain software versions.
Thereforemakesurethattheapprovalisstilleectiveafterasoftware
update is carried out.
Youcannddetailedinformationinthedownloadareaonourhome-
page.
7.3 How to proceed if a repair is necessary
Youcanndaninstrumentreturnformaswellasdetailedinformation
about the procedure in the download area of our homepage. By doing
this you help us carry out the repair quickly and without having to call
back for needed information.
In case of repair, proceed as follows:
• Printandlloutoneformperinstrument
• Clean the instrument and pack it damage-proof
• Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
• Ask the agency serving you to get the address for the return ship-
ment.Youcanndtheagencyonourhomepage.
Maintenance
Cleaning

18
8 Recycling and disposal
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
8 Recycling and disposal
8.1 Disposal
The device is made of recyclable materials. For this reason, it should
be disposed of by a specialist recycling company. Observe the ap-
plicable national regulations.

19
9Certicatesandapprovals
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
9 Certicatesandapprovals
9.1 Approvals for Ex areas
Approvedversionsforuseinhazardousareasareavailableorin
preparation for the device or the device series.
Youcanndtherelevantdocumentsonourhomepage.
9.2 EU conformity
ThedevicefullsthelegalrequirementsoftheapplicableEUdirec-
tives.ByaxingtheCEmarking,weconrmtheconformityofthe
instrument with these directives.
The EU conformity declaration can be found on our homepage.
9.3 Environment management system
Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental pro-
tection.Theenvironmentmanagementsystemiscertiedaccording
toDINENISO14001.Pleasehelpusfullthisobligationbyobserv-
ing the environmental instructions in chapters " Packaging, transport
and storage", " Disposal" of these operating instructions.

20
10 Supplement
VEGACONNECT • Wired interface adapter with connection box
66081-EN-211221
10 Supplement
10.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Exapproval).Insomecases,thesedatacandierfromthedatalistedherein.
All approval documents can be downloaded from our homepage.
Materials and weights
Materials
ƲHousing connection box PBT/PC Blend
ƲVEGACONNECT 4 PPE
Weight incl. cables/accessory 333 g (0.74 lbs)
Electrical data
Voltage supply from USB interface 5 V
Max. power consumption 500 mW
Galvanic separation between – HART - USB
– I²C bus - USB
Ambient conditions
Permissible ambient temperature -20 … +60 °C (-4 … +140 °F)
Storage and transport temperature -40 … +80 °C (-40 … +176 °F)
Electrical protective measures
Protection rating
ƲJunction box IP20, NEMA TYPE 1
ƲVEGACONNECT 4 IP40, NEMA TYPE 1
Connection cable
USB cable
ƲConnection to USB interface of the PC
ƲCable length 200 cm (78 in)
ƲPlug connection Plug USB-A - Plug USB-C
ƲCable insulation min. 0.65 mm (0.256 in)
I²C bus cable
ƲConnection to I²C bus interface
ƲCable length 30 cm (11,8 in)
ƲPlug connection I²C bus plug
Cable with 2 mm pins
ƲConnection to CONNECT sockets, HART resistor/cable
ƲCable length 150 cm (59 in)
ƲPlug connection 2 x 2 mm male connector
Table of contents