Automatic Curtain Adjustment
The next 3 settings allow an automatic increase in the on-time when the room
temperature is quite distant from the set point. There are times when the outdoor
temperature can change quite suddenly and a slow moving curtain can take a
long time to compensate for this sudden change. Then next 3 parameters can
greatly speed up the response of a curtain to a sudden and significant change in
temperature. Examine the parameters and the diagram and example on the
following page to understand how these parameters work. These settings will
affect the on and off times of both curtains in the same manner.
CCnA
Curtain Timer Compensation No Adjust Band
The value entered here indicates the temperature range above and below the
Dead Band where the Curtain Open On-Time (Parameter OPn.1) and Curtain
Close On-Time (Parameter CLo.1), follow the On-Times set in Parameters OPn.1 and
CLo.1. This parameter is disabled if parameters CMOT and CCPb are set to 0.
CMOt
Maximum On-Time
The value entered here indicates the Maximum On-Time that the curtain will use.
If the Maximum On-Time entered here is greater than the [Open On-Time
(Parameter OPn.1) +Off-Time (Parameter Off.1)], or greater than the [Close On-
Time (Parameter CLo.1) + Off-Time (Parameter O .1)], the controller will give the
Off-Time a value of 5 seconds. Otherwise, the on time is increased and the off
time is decreased as needed.
CCpb
Timer Compensate Proportional Band
The value entered here indicates the bandwidth over which the curtain goes from
(Minimum On-Time, Maximum Off-Time) to (Maximum On-Time, Minimum Off
Time).
For example: Parameter SEt.1 (Set Point) 70.0°F
Parameter db.1 (Curtain Dead Band) 5.0°F
Parameter OPn.1 (Curtain Open On-Time) 60 sec.
Parameter O .1 (Curtain Off-Time) 60 sec.
Parameter CCnA (Cur. Timer Comp. No Adjust Band) 1.0°F
Parameter CMOt (Max. On-Time) 90 sec.
Parameter CCpb (Timer Comp. Prop. Band) 2.0°F
Using example settings: When the Temperature in the room increases and
reaches 72.5°F (Parameter Set.1 + 1/2 of Parameter db.1), the curtain starts to
cycle Open for 60 sec. (Parameter OPn.1) Off for 60 sec. (Parameter Off.1). The
curtain will continue to cycle Open 60 sec., Off 60 sec. for another 1.0°F increase
in temperature (73.5°F), since this is the value set in Parameter CCnA (No adjust
band setting). If the temperature continues to rise in the room (73.6°F to 75.5°F,
2.0°F bandwidth set in Parameter CCPb), the controller will gradually increase
the Open On-Time and decrease the Off Time until the Max. Open On-Time is 90
sec. (Parameter CMOt). The Off time would be reduced to 30 seconds. These
settings are only an example of how the controller is capable of lengthening the
- 12 - 30-Nov-2009
Act
Manually Move All Actuators.
Press the Up Arrow
To move both curtains
Closed. Press the
Down Arrow to move
both curtains Open.
If the direction button is
held for 8 seconds or more
the curtain movement will
'latch'. To indicate this, the
display will change from
horizontal lines
to horizontal lines
with sides
when latched.
Curtains will stay latched until the Mode button is pressed (or the opposite
direction is chosen). Note that latched curtain actuators will NOT operate
automatically. To return to display room temperature while latched, the Select
Arrows must be used to return to the default display Parameter. When a curtain
is latched, the Open or Close indicator will flash.
Wind Sensor Status:
If Wind Sensor Operation has been enabled (see the wind sensor settings in the
hidden settings) then this Parameter will indicate if the wind sensor is detecting
wind, if the curtain is closing due to wind and if the open delay timer is active.
Act1 ACT2 ACT3 ACT4
Manually Move Individual Actuators
Press the Up Arrow to close the actuator for the zone. Press the Down Arrow to
open the actuator for the Zone. Individual actuators will latch if the direction
arrow is held for more than 8 seconds (See Above)
runt
Run Time
This Parameter displays the number of minutes since the last
run time reset. This parameter is to be used in combination
with the next 2 parameters allowing the operator to determine
exactly how much the heaters are running. The maximum
value is 9999 minutes (just over an hour short of a full week).
When 9999 is reached all 3 timers stop counting.
- 5 - 30-Nov-2009
Up to
Close
Down to
Open
Press
Both Up
and Down
to Reset
Run Time
Decimal Point lights up when wind sensor
f lap moves toward the sensor
Upper segment lights up to indicate
curtain is closing due to wind sensor
Lower segment indicates curtain will not
open due to open delay timer