Verderflex iDura 5 Technical manual

Peristaltic Industrial Hose Pump
Version 2.0v-02/2023
Supplementary
document
iDura 5-80

2 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
Version 2.0v-02/2023
The information in this document is essential for the safe operation and servicing of Verderex®
iDura pumps. This document must be read and understood thoroughly prior to installation
of unit, electrical connection and commissioning.

3 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
1. Declaration of Conformity..................................................................................................................... 5
2. About This Document............................................................................................................................ 7
2.1 Target groups ................................................................................................................................................7
2.2 Warnings and symbols..................................................................................................................................7
3. Safety ...................................................................................................................................................... 8
3.1 Intended use .................................................................................................................................................8
3.2 General safety instructions............................................................................................................................8
3.2.1 Product safety...............................................................................................................................8
3.2.2 Obligation of the operating company ............................................................................................8
3.2.3 Obligation of personnel.................................................................................................................9
3.3 Specic hazards............................................................................................................................................9
3.3.1 Hazardous pumped liquids ...........................................................................................................9
3.3.2 Lubricants .....................................................................................................................................9
3.3.3 Sharp edges..................................................................................................................................9
4. Transport, Storage and Disposal.......................................................................................................... 9
4.1 Transport.......................................................................................................................................................9
4.1.1 Unpacking and inspection on delivery ..........................................................................................9
4.1.2 Lifting ............................................................................................................................................9
4.2 Storage conditions ........................................................................................................................................9
4.3 Interim storage after using the pump ..........................................................................................................10
4.4 Interim storage before using the pump .......................................................................................................10
4.5 Disposal ......................................................................................................................................................10
5. Electrical Safety ................................................................................................................................... 10
5.1 Electrical connection ...................................................................................................................................10
5.2 Electric shock hazard..................................................................................................................................10
5.3 Connecting to the power supply..................................................................................................................11
6. Weather Canopy................................................................................................................................... 11
7. Operation (supplementary) ................................................................................................................. 12
8. Maintenance ......................................................................................................................................... 12
8.1 Hose change...............................................................................................................................................12
8.1.1 Draining lubricant........................................................................................................................12
8.1.2 Hose change using inverter ........................................................................................................12
8.1.3 Hose change manually ...............................................................................................................13
8.1.4 Re-installing the hose, port anges, lubricant rell and tting the inspection window ................13
9. Service and Inspection of Electrical Components............................................................................ 13
10. Troubleshooting for the iDura (inverter range) ................................................................................. 13
10.1 Hose burst detection and vent kit................................................................................................................13
10.2 iDura inverter functionality...........................................................................................................................14
11. TechnicalSpecications ..................................................................................................................... 16
11.1 Pump specications ....................................................................................................................................16
11.2 Ambient conditions......................................................................................................................................16
11.3 Tightening torques ......................................................................................................................................16
11.4 Preservatives ..............................................................................................................................................16
11.5 Lubricants....................................................................................................................................................16
11.6 Rotor options...............................................................................................................................................16
Table of Contents

4 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
Listofgures
Figure 1. - Fastening apparatus gear to pump 9
Figure 2. - Single phase wiring 11
Figure 3. - Three phase wiring 11
Figure 4. - Weather canopy 11
Figure 5. - iDura inverter overview 12
List of tables
Table 1. - Target groups 7
Table 2. - Warnings used in the manual 7
Table 3. - Symbols used in the manual 7
Table 4. - iDura inverter parameters 15
Table 5. - Pump specications 16
Table 6. - Tightening torques 16
Table 7. - Rotor options 16
12. Trademarks ........................................................................................................................................... 17
13. Document History ................................................................................................................................ 17

5 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
1. Declaration of Conformity
We,
VERDER Ltd., Unit 3 California Drive, Castleford
hereby declare that the following machine adheres to the relevant EC directives detailed below:
Designation
EC directives:
Applicable harmonized standards:
The pump, to which this declaration refers, may only be put into operation after it has been installed in the way
prescribed by the manufacturer and, as the case may be, after the complete system of which this pump forms
part, has been made to full the requirements of Machinery Directive 2006/42/EC.
EC declaration of conformity according to machinery directive, appendix II A
Manufacturer
VERDER Ltd.
Unit 3 California Drive
Castleford
WF10 5QH
UK
Authorised Representative Established in EU
(in accordance with Article 4, Regulation (EU) 2019/1020)
Verder Liquids B.V
Utrechtseweg 4a
3451 GG Utrecht
Netherlands
Company Stamp / Signature:
Anthony Beckwith
Head of Engineering
Date: 28/ 02/ 2023
iDura MK IV 05
iDura MK IV 07
iDura MK III 10
iDura MK III 15
iDura MK III 25
iDura MK III 35
• BS EN ISO 12100:2010 - Safety of machinery - General principles for design - Risk assessment and risk
reduction
• Machinery Directive (2006/42/EC)
• Low-voltage Directive (2014/35/EU)
• EMC Directive (2014/30/EU)
• RoHS Directive (2011/65/EU) and Delegated Directive (2015/863/EU)
(EC)
iDura 45
iDura MK III 55
iDura 55HF
iDura 65
iDura 80

6 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
Manufacturer VERDER Ltd.
Unit 3 California Drive
Castleford
WF10 5QH
UK
Company Stamp / Signature:
Anthony Beckwith
Head of Engineering
Date: 28/ 02/ 2023
The following designated standard(s) has been applied:
The pump, to which this declaration refers, may only be put into operation after it has been installed in the way
prescribed by the manufacturer and, as the case may be, after the complete system of which this pump forms
part, has been made to full the requirements of The Supply of Machinery (Safety) Regulations 2008.
• Supply of Machinery (Safety) Regulations 2008
• The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment
Regulations 2012
• Electrical Equipment (Safety) Regulations 2016
• Electromagnetic Compatibility Regulations 2016
• BS EN ISO 12100:2010 - Safety of machinery - General principles for design - Risk assessment and risk
reduction
Declaration of Conformity (UK)
In accordance with the UK Supply of Machinery (Safety) Regulations 2008, No 1597 ANNEX II, Part I,
Section B
We,
VERDER Ltd., Unit 3 California Drive, Castleford
hereby declare that the following machine adheres to the relevant UK legislation detailed below:
Designation
UK Legislation:
iDura MK IV 05
iDura MK IV 07
iDura MK III 10
iDura MK III 15
iDura MK III 25
iDura MK III 35
iDura 45
iDura MK III 55
iDura 55HF
iDura 65
iDura 80

7 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
2. About This Document
This manual is a guideline for qualied users for the safe operation and maintenance of Verderex® iDura pumps. This is a
supplementary document to the Dura operating manual and the Inverter instruction manual. The operating manuals must be read
and understood both by the installing personnel and the responsible trained personnel / operators prior to following additional
guidelines in this document.
Instructions in this manual should be read in conjunction with instructions and guidelines in pump, motor, gearbox and inverter
operating manuals.
2.1 Target groups
Target Groups Duty
Operating company XKeep this manual available at the operating site of the pump.
XEnsure that personnel read and follow the instructions in this
manual and any other applicable documents, especially all safety
instructions and warnings.
XObserve any additional rules and regulations referring to the
system.
Qualied personnel, tter XRead, observe and follow this manual and the other applicable
documents, especially all safety instructions and warnings.
Table 1. - Target groups
2.2 Warnings and symbols
Warning Risk Level Consequences of disregard
DANGER
Immediate risk Death, serious bodily harm
WARNING
Potential acute risk Death, serious bodily harm
CAUTION
Potential hazardous situation Potential damage to the pump
Note
For information Possible incorrect use
maintenance of pump
Table 2. - Warnings used in the manual
Symbol Meaning
Safety warning sign in accordance with DIN 4844-W9
XTake note of all information highlighted by the safety warning sign
and follow the instructions to avoid injury or death.
XInstruction
1., 2., Multiple-step instructions
Checklist
gCross-reference
Information
Table 3. - Symbols used in the manual

8 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
3. Safety
The manufacturer does not accept any liability for
damage resulting from disregard of this documentation
or the manuals for the pump, motor, gearbox and inverter.
3.1 Intended use
XOnly use the pump to handle compatible uids as
recommended by the manufacturer (g11. Technical
Specications ).
XAdhere to the operating limits.
XConsult the manufacturer regarding any other use of the
pump.
XInverters should be wired to the power supply before use
and this should be completed only by qualied personal
and in accordance with the provisions of EMC Directive
and EC Machinery Directive 2006/42/EC.
Prevention of obvious misuse (examples)
XNote the operating limits of the pump with regard to tem-
perature, pressure, ow rate, motor speed and frequency
(g11. Technical Specications ).
XDo not operate the pump with any inlet/outlet valves
closed
XInstall the inverter as recommended in this manual, in
conjunction with instructions in the pump, motor, gearbox
and inverter instruction manuals. For example, the
following are not allowed:
– Installing the pump without proper support.
– Installation in the immediate vicinity of extreme hot or
cold sources.
3.2 General safety instructions
Observe the following before carrying out any work:
3.2.1 Product safety
• These operating instructions contain fundamental
information which must be complied with during
installation, operation and maintenance. Therefore,
this operating manual must be read and understood
both by the installing personnel and the responsible
trained personnel / operators prior to installation and
commissioning, and it must always be kept easily
accessible within the operating premises of the machine.
• Not only must the general safety instructions laid down
in this chapter on “Safety” be complied with, but also the
safety instructions outlined under specic headings.
• Operate the pump only if it and all associated systems are
in good functional condition.
• Only use the pump and inverter as intended, fully aware
of safety and risk factors involved and the instructions in
this manual.
• Keep this manual and all other applicable documents
complete, legible and accessible to personnel at all times.
• Refrain from any procedure or action that would pose a
risk to personnel or third parties.
• In the event of any safety-relevant faults, shut down the
pump immediately and have the malfunction corrected by
qualied personnel.
• The installation of the pump must comply with the
requirements of installation given in this manual and any
local, national or regional health and safety regulations.
• The pump and drive unit must not be mounted in direct
sunlight or exposed to rain without suitable shade cover
which is well ventilated.
3.2.2 Obligation of the operating company
Safety-conscious operation
• Ensure that the following safety aspects are observed and
monitored:
– Adherence to intended use
– Statutory or other safety and accident-prevention
regulations
– Safety regulations governing the handling of
hazardous substances if applicable
– Applicable standards and guidelines in the country
where the pump is operated
• Make personal protective equipment available pertinent to
operation of the pump.
Qualiedpersonnel
• Ensure that all personnel tasked with work on the pump
have read and understood this manual and all other
applicable documents, including the safety, maintenance
and repair information, prior to use or installation of the
pump.
• Organise responsibilities, areas of competence and the
supervision of personnel.
• Have all work carried out by specialist technicians only.
• Ensure that trainee personnel are under the supervision
of specialist technicians at all times when working with the
pump.
Safety equipment
Provide the following safety equipment and verify its
functionality:
• For hot, cold and moving parts: safety guarding should be
provided by the operating company.
• For potential build-up of electrostatic charge: ensure
appropriate grounding if and when required.
Warranty
The warranty is void if the customer fails to follow any
Instruction, Warning or Caution in this document. Verder has
made every eort to illustrate and describe the product in this
document. Such illustrations and descriptions are, however,
for the sole purpose of identication and do not express or
imply a warranty that the products are merchantable or t
for a particular purpose, or that the products will necessarily
conform to the illustration or descriptions.

9 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
Obtain the manufacturer’s approval prior to carrying out any
modications, repairs or alterations during the warranty period.
Only use genuine parts or parts that have been approved by
the manufacturer.
For further details regarding warranty, refer to terms and
conditions.
3.2.3 Obligation of personnel
It is imperative that the instructions contained in this
manual are complied with by the operating personnel
at all times.
XPump and associated components:
– Do not lean or step on them or use as a climbing aid
– Do not use them to support boards, ramps or beams
– Do not use them as a xing point for winches or
supports
– Do not de-ice using gas burners or similar tools
XDo not remove the safety guarding for hot, cold or moving
parts during operation.
XReinstall the safety equipment on the pump as required
by regulations after any repair / maintenance work on the
pump.
3.3 Specichazards
3.3.1 Hazardouspumpedliquids
Follow the statutory safety regulations when handling
hazardous pumped liquids (e.g., hot, ammable, poisonous or
potentially harmful).
Use appropriate Personal Protective Equipment when carrying
out any work on the pump.
3.3.2 Lubricants
Ensure that the lubricant and pumped liquid are compatible
with each other. This is a precautionary measure in case
of accidental hose burst whereby the pumped liquid comes
in contact with the lubricant. (see ‘Verderex Chemical
Compatibility Guide’, available on the Verder website and also
refer to g 11. Technical Specications for specic lubricant
limitations)
3.3.3 Sharp edges
Pump parts, such as the shims, can be sharp.
– Use protective gloves when carrying out any work on
the pump
4. Transport, Storage and
Disposal
4.1 Transport
Always transport the pump in a stable position and
ensure that the pump is securely attached to the pallet.
4.1.1 Unpacking and inspection on delivery
1. Report any transport damage to the manufacturer/
distributor immediately.
2. Retain the pallet if any further transport is required.
4.1.2 Lifting
DANGER
Death or crushing of limbs can be caused by falling loads!
1. Use lifting apparatus appropriate for the total weight to be
transported.
2. Make sure the pump and accessories are lifted and
moved by qualied lifting personnel equipped with
suitable lifting apparatus.
3. Fasten the lifting apparatus to the lifting eye as shown in
the following illustration (lifting eye on iDura 15, 25, 35,
45, 55, 55HF, 65, 80 only).
4. Do not stand under suspended loads.
Figure 1. - Fastening apparatus gear to pump
4.2 Storage conditions
1. Make sure the storage location meets the following
conditions:
– Dry, humidity not to exceed 85%, non-condensing
– Out of direct sunlight
– Frost-free; temperature range -5 °C to +45 °C
– Vibration-free
– Dust-free
2. Depending on these conditions, it may be advisable to
place a moisture-absorbing product, such as Silica gel,
inside the pump’s housing or to coat the pump’s inner
surfaces with moisture-repelling oil, such as WD40, whilst
the pump is stored.

10 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
3. Hoses should be stored as supplied in their wrapper and
should be stored away from direct sunlight, at without
any bends or kinks and at room temperature with end
caps tted.
4. Lubricants should be stored under normal warehouse
conditions with their caps securely fastened.
5. Gearboxes may require intermittent attention as indicated
by the gearbox manufacturer’s recommendations.
4.3 Interim storage after using the
pump
XThe hose should be removed from the pump.
XThe pump housing lubricant should be drained.
XThe pump housing should be washed out, allowed to dry
and any external build-up of product removed.
4.4 Interim storage before using the
pump
CAUTION
Pump damage caused by interim storage!
XAllow the pump to reach ambient temperature before use.
XPlease observe the storage recommendations and use
by dates which apply to the hose you may wish to bring
into service after storage.
4.5 Disposal
With prolonged use, pump parts can be contaminated by
hazardous pumped liquids to such an extent that cleaning may
be insucient.
WARNING
Risk of poisoning and environmental damage by the
pumped liquid or oil!
XUse suitable personal protective equipment when
carrying out any work on the pump.
XPrior to disposal of the pump:
– Drain and dispose of the lubricant in accordance with
local regulations.
– Collect and dispose of any leaking pumped liquid or
oil in accordance with local regulations.
– Neutralize residues of pumped liquid in the pump.
XDispose of the pump and associated parts in accordance
with local regulations.
5. Electrical Safety
5.1 Electrical connection
DANGER
Risk to health due to electric shock!
XAll electrical work must be carried out by qualied
electricians.
Death or crushing of limbs caused by falling loads!
XUse lifting gear appropriate for the total weight to be
transported.
XDo not stand under suspended loads.
XEnsure the travel plug is removed and disposed correctly
before the motor and gearbox is attached to the pump.
1. The Inverter uses high voltages and currents, carries
a high level of stored electrical energy, and is used to
control mechanical plant that may cause injury. Close
attention is required to system design and electrical
installation to avoid hazards in either normal operation or
in the event of equipment malfunction.
2. Only qualied electricians are allowed to install and
maintain this product. System design, installation,
commissioning and maintenance must be carried out
only by personnel who have the necessary training
and experience. They must carefully read this safety
information and the instructions in this Guide and
follow all information regarding transport, storage,
installation and use of the Inverter, including the specied
environmental limitations.
3. Do not perform any ash test or voltage withstand test on
the Inverter.
4. In order to protect inverter and motor from high voltage
or transient damage, it is recommended to use suitable
Surge Protection Device (SPD) when wiring the inverter.
5.2 Electricshockhazard
1. Disconnect and ISOLATE the inverter before attempting
any work on it.
2. High voltages are present at the terminals and within
the drive for up to 10 minutes after disconnection of the
electrical supply. Always ensure, by using a suitable
multimeter, that no voltage is present on any drive power
terminals prior to commencing any work.
3. Where supply to the drive is through a plug and socket
connector, do not disconnect until 10 minutes have
elapsed after turning o the supply.
4. Ensure correct earthing connections. The earth cable
must be sucient to carry the maximum supply fault
current which normally will be limited by the fuses or
MCB. Suitably rated fuses or MCB should be tted in
the mains supply to the drive, according to any local
legislation or codes.

11 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
5. Ensure correct earthing connections and cable selection
as dened by local legislation or codes. The drive
may have a leakage current of greater than 3.5mA;
furthermore the earth cable must be sucient to carry
the maximum supply fault current which normally will be
limited by the fuses or MCB.
6. Suitably rated fuses or MCB should be tted in the mains
supply to the drive, according to any local legislation or
codes.
7. Do not carry out any work on the drive control cables
whilst power is applied to the drive or to the external
control circuits.
5.3 Connecting to the power supply
Select the correct specication of cable for connecting
the inverter (gRefer to the Invertek manual for cable
installation guidance)
1. Remove the terminal cover from the inverter (Phillips
screwdriver)
2. With power isolated, remove the plug in the gland and
feed the supply cable through.
3. Connect earth to the closest earth point within the
terminal cavity.
4. Connect phases as denoted by “A” in the Figure 2 Wiring
Diagram - Single and 3 Phases Supply (varies on supply
phase).
5. Terminal screw Torque values are provided in the Invertek
manual supplied with the pump USB memory stick.
6. Check connections and glands are secure by tugging
lightly on the cable.
7. Replace terminal cover and set isolator switch to 1. This
will turn on the device and output connections may be
live.
8. Check pump rotational direction matches up with the
directional switch on the inverter, refer to g5 Operation
(supplementary).
CAUTION
If the pump turns in the opposite direction to the switch,
change the pair of motor phases to change the motor direction
(e.g. switching connection of cable in terminal U to terminal V.
Ensure that inverter is isolated from the electrical supply
before doing so.
Single Phase Supply
Figure 2. -
L1 L3 EMCL2/N U V W
1 2 3 4 5 6 7 8 9
10
11
I0I0I I0I0I
AB
C
Single phase wiring
A: Incoming power connection
B: Motor connection
C: Control terminal connection
Three Phase Supply
Figure 3. -
L1 L3 EMCL2/N U V W
1 2 3 4 5 6 7 8 9
10
11
I0I0I I0I0I
AB
C
Three phase wiring
A: Incoming power connection
B: Motor connection
C: Control terminal connection
6. Weather Canopy
Verderex iDura 45-80 have the option of a weather canopy to
protect the inverter against harsh weather conditions (extreme
snow, rain, sun). This can be ordered separately.
Figure 4. - Weather canopy

12 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
7. Operation (supplementary)
1. Check inverter directional switch (1) is in central “0”
position and that power is available to the inverter.
2. Switch on the inverter using the built-in isolator switch and
check no errors are displayed on screen. (2)
3. Directional switch governs which direction the pump will
turn. When set to the right position, the pump should turn
clockwise. (if not, refer to g 4.3 Connecting to the Power
Supply)
4. Speed dial allows governance over pump rotor speed,
between a minimum and a maximum set by the
manufacturer. A speed of 0 RPM is achieved by setting
directional by setting directional switch to zero.
Note
The pump will still turn when the speed dial is set to the
minimum position.
5. The display can show motor parameters such as power
consumption (kW), current draw (A) and speed (4). The
custom parameter “C” shows nominal ow rate of the
pump. To switch between which parameter is displayed,
press hexagonal button for <1s and repeat until desired
parameter is displayed. (5)
6. Additional control methods can be programmed if desired,
e.g. modbus/4-20mA control. Refer to the included
Invertek manual and consult your local Invertek supplier
for guidance on how to do this.
SpecicparameterswhichifchangedwillvoidVerderex
warranty, so consult with Verder distributor before
changing parameters.
Figure 5. - iDura inverter overview
8. Maintenance
Only trained service technicians should be employed for
tting and repair work. Present a pumped medium
certicate (DIN safety data sheet or safety certicate)
when requesting service.
8.1 Hose change
WARNING
Risk of injury!
XAlways isolate the power supply before working on the
pump.
XIf inspection cover is removed for cleaning the pump
cavity, isolate the inverter until inspection cover is
replaced.
The hose change involves removal and re-installing the
port anges.
Disconnect inlet and outlet pipework. Clear the area to
provide safe working space and clearance to replace the
hose.
8.1.1 Draining lubricant
Checklist:
Motor isolated
System secured against being switched back on again.
WARNING
Sliphazardduetospiltlubricant!
XCare must be taken when lubricant is drained into a
container.
XDispose of used lubricant in accordance with local laws
and good environmental practices.
1. Remove the drain plug at the rear of the pump.
2. Drain the lubricant into a suitable container.
3. Remove the lower ange and allow any excess lubricant
to drain out.
8.1.2 Hose change using inverter
CAUTION
Risk of injury if the hose is expelled too quickly!
XKeep body parts clear of the rotor which presents an
entrapment risk.
XSet speed dial to minimum position. Disable and
disconnect any remote control that has been
programmed into the inverter.
XSlowly remove the hose by using the inverter to turn the
pump at low speed.
1. Remove both the anges. Remove and dispose of both
clamp rings (where tted).
2. Set directional dial to whichever direction is preferable,
and the speed dial to minimum setting.

13 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
3. The motor will slowly drive out the hose. If at this point
you are performing inspection on the rotor or pump cavity,
turn o inverter and lock-out using an appropriate lock-
out-tag-out.
4. Clean the pump housing.
5. Inspect the anges for damage and signs of wear.
8.1.3 Hose change manually
CAUTION
Risk of injury if the hose is expelled too quickly!
XWhen performing a hose change manually, turn
directional switch on inverter to central “0” position, power
o and lock out the inverter using the isolator switch.
Allow 10 minutes for internal circuits to de-energise.
1. Remove both the anges. Remove and dispose of both
clamp rings (where tted).
2. Remove the fan cover and turn the fan shaft by hand
or using suitable leverage. Care must be taken not to
damage the fan blades when using this method.
3. Clean the pump housing.
4. Inspect the anges for damage and signs of wear.
8.1.4 Re-installing the hose, port anges,
lubricant rell and tting the inspection
window
1. Apply lubricant to new hose surface and insert into the
pump inlet.
2. When the hose is installed by using the inverter controls
in the opposite direction will turn the rotor to drive the
hose into the pump.
3. When the hose is installed manually, turn motor cooling
fan in opposite direction to drive the hose into the pump.
CAUTION
Ensure the hose is installed as indicated in the Dura 05-35
operating manual, Section 6.6 Flange Assembly.
4. Follow step by step the instructions listed in Dura 05-35
operating manual for how to install the port anges, rell
the lubricant and t the inspection window.
9. Service and Inspection of
Electrical Components
It is understood that electrical components must be
periodically inspected to ensure site health and safety
regulations. Only a trained electrician should service the
pump’s electrical components. When doing so, ensure
the following:
1. Power to the inverter is disconnected and locked out
2. The inverter has been turned o and locked out
3. The speed dial is set to minimum and directional dial is
set to zero
4. The inverter has been allowed at least 10 minutes to de-
energise.
10. Troubleshooting for the
iDura (inverter range)
A comprehensive list of error messages and their causes
can be found in the Invertek OptiDrive E3 operation
manual.
Below are the typical troubleshooting error messages that may
be received based on Verder factory settings and relate to the
pump conguration:
1. “E-TriP” - the hose burst sensor has been triggered.
Check for a hose burst.
2. “l_t_trP” - suspected motor overtemperature. Allow motor
to cool and restart inverter.
10.1 Hose burst detection and vent
kit
Hose burst sensor supplied as standard with the iDura,
have been pre-wired to the inverter. No further wiring has
to be done by the user to use the hose burst detection.
Verderex hose burst detector and vent kit provide three basic
functions:
1. Stops the pump in conjunction with the inverter, in case of
accidental hose burst;
2. Detect over pressure inside the pump;
3. Release excess pressure from pump housing
The calibrated sensor detects any increase in the pressure
inside a pump casing. As the pressure threshold is reached,
the sensor changes state and this can be used to turn-o
the pump. The system has a detection threshold of 0.4 Bar
(5.8 P.S.I) and when the casing pressure exceeds this, it
initiate triggers the inverter to stop the pump. In the event of a
pressure rise inside the pump casing exceeding 2bar, the vent
kit helps to release this excess pressure from the pump.

14 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
10.2 iDura inverter functionality
Values set during assembly at Verder should not be changed. These have been determined to be specic to the selected
hardware. Some functionality in the inverter can be set by the customer to make it work with their system and control method,
though the following parameters should not be changed and will result in warranty being voided if changed:
Parameter Description User can change?
1Maximum speed/frequency limit No
2Minimum speed/frequency limit No
3 Acceleration ramp time Yes
4 Deceleration ramp time Yes
5 Stopping mode/mains loss response Yes
6 Energy optimiser No
7Motor rated voltage DELTA/STAR No
8Motor rated current DELTA/STAR No
9Motor rated frequency No
10 Motor rated speed No
11 Low frequency torque boost No
12 Primary command source Yes
13 Operating mode select No
14 Extended/Advanced menu access code Yes
15 Digital input function select Yes
16 Analog input 1 signal format Yes
17 Maximum eective switching frequency No
18 Output relay function select Yes
19 Relay threshold level Yes
20 Speed 1 Yes
21 Speed 2 Yes
22 Speed 3 Yes
23 Speed 4 Yes
24 2nd ramp time (fast stop) Yes
25 Analogue output function select Yes
26 Skip frequency hysteresis band Yes
27 Skip frequency centre point Yes
28 V/F characteristic adjustment voltage No
29 V/F characteristic adjustment frequency No
30 Start mode, automatic restart, re mode operation Yes
31 Keypad start mode select No
32 DC injection mode and duration No
33 Spin start Yes
34 Brake chopper enable (not size 1) No
35 Analog input 1 scaling/slave speed scaling Yes
36 Serial communications conguration Yes
37 Access code denition Yes*
38 Parameter access lock Yes
39 Analog input 1 oset Yes

15 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
Parameter Description User can change?
40 Display scaling No
41 PI controller proportional gain Yes
42 PI controller integral time Yes
43 PI controller operating mode Yes
44 PI reference source select Yes
49 PI control wake up error level No
50 User output relay hysteresis Yes
51 Motor control mode Yes
52 Motor parameter autotune Yes
53 Vector mode gain No
54 Max current limit in vector control No
55 Motor stator resistance No
56 Motor stator d-axis inductance No
57 Motor stator q-axis inductance No
58 DC injection speed No
59 DC injection current No
60 Motor overload management Yes
Table 4. - iDura inverter parameters
iDura inverter functionality (cont.)

16 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
11. TechnicalSpecications
11.1 Pumpspecications
Size Value
Max. delivery pressure
iDura 5-7 5 bar
iDura 10-25 6 bar
iDura 35 6 bar
iDura 45 6 bar
iDura 55/55HF 6 bar
iDura 65 6 bar
iDura 80 6 bar
Temperature of pumped
liquid
< 100 °C (subject to hose
material)
Max. continuous
operation pump speeds
*(refer to pump datasheet)
Dimensions *(refer to pump datasheet)
Table 5. - Pump specications
11.2 Ambient conditions
Operation under any other ambient condition would require
approval from the manufacturer
Operating conditions
• Ambient temperature –5 °C to +45 °C
• Relative humidity (non-condensing), long-term ≤ 85 %
• All units/calculations are based on operating conditions
below 1000 m. For use above this height please check with
manufacturer or local representative for conrmation of
performance.
Storage conditions
• Ambient temperature +10 °C to +50 °C
• Relative humidity (non-condensing), long-term ≤ 85 %
11.3 Tightening torques
The tightening torques should be applied in addition to the
pump tightening torques indicated in the pump manual:
Position Torque Values (Nm)
Inverter terminal panel 2
Inverter power terminals 1.5
Inverter control terminals 0.5
Table 6. - Tightening torques
11.4 Preservatives
Use RUST-BAN 335 or similar preservatives on
bare metal.
11.5 Lubricants
Recommended lubricants for longer hose life are
VERDERLUBE or VERDERSIL.
Please refer to the manual of your pump for the amount of
required lubricant.
NOTE: The pump lubricant is lled to the lowest screw hole
of the inspection window.
11.6 Rotor options
Verderex iDura 5-35 range has only standard pressure rotor.
iDura 45-80 are shimmed to suit 6 bar as follows:
Pump type Rotor option (bars)
Standard
iDura 5 5 bar
iDura 7 5 bar
iDura 10 6 bar
iDura 15 6 bar
iDura 25 6 bar
iDura 35 6 bar
iDura 45 4 shims (6 bar)
iDura 55 3 shims (6 bar)
iDura 55HF 3 shims (6 bar)
iDura 65 3 shims (6 bar)
iDura 80 5 shims (6 bar)
Table 7. - Rotor options
These conditions are set with water at 20°C. Shimming may
be aected by uid, process conditions, hose material and
might need to be altered to match the application.
Refer to the pump manual for details.

17 | PageVersion 02
© Verder Liquids B.V
iDura 5-80 - Supplementary document
Original instructions (en)
12. Trademarks
VERDERFLEX® is a registered trademark of Verder Liquids B.V. No permission is granted to use any Verder, trademarks or trade
names included in this document without the prior written agreement of Verder Liquids B.V.
Tri-clamp® is a registered trademark of Alfa Laval Corporate AB.
Hypalon® is a registered trademark of RSCC Wire & Cable LLC.
13. Document History
Version Description Date Approved
02 Incorporated iDura 45-80 range. 28/02/23 ISH
Other manuals for iDura 5
1
This manual suits for next models
10
Table of contents
Other Verderflex Water Pump manuals

Verderflex
Verderflex VP-PH Series Installation manual

Verderflex
Verderflex Vantage 5000 Quick start guide

Verderflex
Verderflex Dura MK IV 05 User manual

Verderflex
Verderflex Dura 55 User manual

Verderflex
Verderflex DURA Series User guide

Verderflex
Verderflex Vantage 5000 Manual

Verderflex
Verderflex Vantage 3000 P User manual

Verderflex
Verderflex Dura 45 User manual

Verderflex
Verderflex iDura 5 Technical manual

Verderflex
Verderflex Dura 15 User manual