manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Veris Industries
  6. •
  7. Security Sensor
  8. •
  9. Veris Industries HW Series User manual

Veris Industries HW Series User manual

Z205863-0C PAGE 1 ©2012 Veris Industries 01122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
ENVIRONMENTAL SENSORS INSTALLATION GUIDE
Wall Mounted Humidity Sensors
with Protocol Communication
Installer’s Specifications
Input Voltage 12 to 30VDC, 24VAC; 100mA max.
Operating Temperature Range 0° to 50°C (32° to 122°F)
Housing Material High impact ABS plastic , UL 94 VO
Protocol BACnet or Modbus (selectable)
Connection 2-wire RS-485
Data Rate 9600, 19200, 38400, 57600 (Modbus), bps (selectable)
9600, 19200, 38400, 76800 (BACnet), bps (selectable)
Parity None/Odd/Even (selectable-Modbus)
None (BACnet)
Address Range 1-127
RH Transmitter:
HS Sensor Replaceable digitally proled thin-lm capacitive
(32-bit mathematics); U.S. Patent 5,844,138
Accuracy* ±1% from 12 to 60% RH; ±2% from 10 to 80% RH;
NIST traceable multi-point calibration
Reset Rate** 24 hours
Stability ±1% @ 20°C (68°F) annually for two years
Hysteresis 1.5% typical
Operating Humidity Range 0 to 100% RH, noncondensing
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Coecient ±0.1% RH/°C above or below 25°C (typical)
Temperature Transmitter Option:
Sensor Type Solid-state, integrated circuit
Accuracy ±0.5°C (±1°F) typical
Resolution 0.1°C (0.2°F)
Range 10° to 35°C (50° to 95°F)
Setpoint Slider Resolution Option 1% full scale
Override Button Option Remotely readable and resettable
* Specied accuracy with 24VDC supplied power with rising humidity.
** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
Note: RTD/Thermistors in wall packages are not compensated for internal heating of product.
HW Protocol HW Protocol
DIMENSIONS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
QUICK INSTALL
1. Select a mounting location away from ventilation sources. The sensor should be
mounted on a vertical wall, about 4 1/2 feet above the oor.
2. Ax the backplate to the wall.
3. Wire the device. Refer to wiring diagram.
4. Install Cover.
HW
Local Display
L = LCD
X = No Display
Protocol
= Protocol
P
RH Option
1 = RH 1% NIST
2 = RH 2% NIST
H = RH 2%
Temp. Option
X = No temp. option
T = Temp. Transmitter
Temp. Cal. Cert.
X = No
1 = 1 pt. cal. cert.*
2 = 2 pt. cal. cert.*
3 = 3 pt. cal. cert.*
Option
Blank = None
1 = Pushbutton override
2 = Setpoint slider
3 = Pushbutton override +
set point slider
Housing
Blank = Cloud white
B = Black
4.8"
(122 mm)
1.2"
(30 mm)
3.5"
(89 mm)
T
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
* Only available if temperature option is selected.
Z205863-0C PAGE 2 ©2012 Veris Industries 01122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
HW PROTOcOL INSTALLATION GUIDE
correct incorrect
Five screwholes available; use a mini-
mum of two for secure mounting.
INSTALLATION
1. Remove the cover by pressing the tab at the top of the sensor while
pulling outward from the top of the cover.
2. Remove the backplate by unfastening the sensor from the bottom
of the backplate and pivoting the sensor outward.
3. Punch out openings in the backplate.
4. Position the sensor vertically on
the wall, 4 1/2 feet above the
oor.
5. Mount the backplate onto the wall using the screws provided.
6. Wire the backplate.
Wire the RS-485 connections with shielded, twisted-pair wire, such as Belden Cable
1120A or equivalent. With 2-wire cable, connect the shield at one end only to the
RS-485 SHIELD terminal.
POWER SUPPLY
12-30VDC, 24VAC
CONTROL SYSTEM
COMMON
RS-485+
RS-485 -
SHIELD
PWR
GND
RS-485+
RS-485-
SHIELD
+
-
-
DIP switches, located on backside of board,
Top row: Address switches
Bottom row: Conguration switches
Select Address DIP switches
1. Up for Modbus, Down for BACnet.
2. Up to add 64 to network address.
3. Up to add 32 to network address.
4. Up to add 16 to network address.
5. Up to add 8 to network address.
6. Up to add 4 to network address.
7. Up to add 2 to network address.
8. Up to add 1 to network address.
The network address is the sum of the values selected by placing switches 2
through 8 in their UP position. E.g.: If switches are D D D U D U D D, then BACnet
communication is selected, and the address is 16 + 4, for a total of 20. Valid Modbus
addresses are 1 to 127, and valid BACnet addresses are 0 to 127. Each device on the
daisy chain must have a unique address.
Select Configuration DIP switches
Conguration DIP switches 1 and 2 control the parity settings for Modbus and have
no eect on BACnet communication, which never has parity.
Switch 1 Switch 2 Parity
Down Down None (2 stop bits)
Down Up Odd
Up Up Even
Up Down None (1 stop bit; common but non-standard)
Conguration DIP switches 3 and 4 control the data rate for both Modbus and BACnet
modes.
Switch 3 Switch 4 Data Rate
Down Down 9600 bps
Down Up 19200 bps
Up Down 38400 bps
Up Up Modbus: 57600 bps; BACnet: 76800 bps
Ground each unit via the power supply GND terminal or the RS-485 SHIELD terminal
if the power supply is oating. Grounding is necessary to minimize common mode
voltage on the signal lines and to minimize radio frequency emissions that can
interfere with the operation of nearby radio equipment.
Daisy-chain devices with 120Ω termination resistors between RS-485+ and RS-485-
on the last device at each end of the chain. Maximum of 63 devices on one daisy
chain.
7. Congure the sensor.
Set the DIP switches on the backside of the
board.
Z205863-0C PAGE 3 ©2012 Veris Industries 01122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
HW PROTOcOL INSTALLATION GUIDE
Modbus Configuration
The list of supported Modbus function codes and the Modbus Point Map are in the
Point Map section of this document. The capabilities for controlling the TWxP are
identical with those for BACnet. The functions are summarized here.
Function Description
Coils Used to set temperature (Fahrenheit scale) and override button coil. *
Discrete
input
Indicates whether the relay is on.
Input
registers
Used to read the sensor options: RH (in units of 0.1%), temperature (in units
of 0.1°), and the slider (in units of %full scale). **
Holding
registers
Used to specify the temperature oset and RH oset. Initial settings are 0°F,
and 0%, respectively. Settings are retained if power is lost.
* The temperature scale is maintained if power is lost. When delivered, temperature in Farenheit
and calibration lockout is on. Pressing the override button turns the override button coil on. It can
only be turned o remotely.
** If any sensor option is not installed, the reading for that sensor will be 0.
The various registers are still present even without the corresponding options
installed. In particular, the discrete input function can be used to see if the CO2
setpoint has been reached even if the relay is not in use.
BACnet Configuration
The list of BACnet objects and their implemented properties is in the BACnet
Descriptions section of this document. The capabilities for controlling the CWxP
are identical with those for the Modbus conguration. However, BACnet has some
additional protocol-related settings.
The Device Object must have a unique name. This is set at the factory to the model
name, followed by the device’s serial number. The name can be changed if desired.
The device object must also have a unique object identier number. By default, this
is 133nnn where nnn is the current network address. This number can be changed
and the new number will be remembered. Setting the number to -1 (normally not
allowed) will reset the device to the default.
The Reliability property of the analog inputs for temperature, relative humidity, and
slider can be read to determine whether the device has these options installed.
8. Install the sensor onto the backplate.
9. When installation is complete, install the cover
and snap into place.
VISUAL INDICATORS
The RX light will ash while data is being received. If it isn’t blinking, it can indicate a
bad connection or that the RS-485+ and RS-485– wires are connected backwards.
The TX light will ash while data is being transmitted. For Modbus, if this light isn’t
blinking it can mean that the device isn’t being selected (wrong address) or the
communication parity or bit rate is set improperly.
In a BACnet installation, both the RX and TX lights will ash repeatedly even if no
communication is being performed. In a Modbus installation, no lights will ash if
there is no communication activity.
MODBUS POINT MAP
Function code Function
01 Read coils
03 Read holding registers
04 Read input registers (if any sensor is not installed, the reading for that
sensor will be 0)
05 Write single coil
06 Write single register
07 Diagnostics (sub-function 00 returns query data)
15 Write multiple coils
16 Write multiple registers
17 Report slave ID (returns manufacturer, model name, and serial number)
All of these values correspond to BACnet objects with the same name. See the BACnet
Descriptions section for denitions.
Coils
1 Fahrenheit (else Celsius)
2 Override (use override button to turn on)
Input Registers
1 Humidity (in tenths of a percent)
2 Temperature (in tenths of a degree; units set by coil 1)
3 Slider (in percent)
Holding Registers
1 Temp Oset (in tenths of a degree, current units)
2 RH oset (in tenths of a percent)
Z205863-0C PAGE 4 ©2012 Veris Industries 01122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
HW PROTOcOL INSTALLATION GUIDE
BACNET DESCRIPTIONS
All properties read-only unless otherwise noted. Preserved means it is non-volatile.
Present_Value Range Restrictions
Object Name Minimum Value Maximum Value
Device_Instance 0 (but see description, above) 4,194,302
Temp_Oset -5 5
RH_Oset -10 10
Standard Object Types Supported
Object Type Supported Optional
Properties
Writable Properties
Analog Input
-- AI
Description*, Reliability
Analog Value
-- AV
Description* Present_Value
Binary Value
– BV
Description* Present_Value
Device -- DEV Description*, Location APDU_Timeout, Description, Location,
Max_Master, Object_Identier,
Object_Name
* Description is the same as the Object_Identier. Reliability is “No Sensor” if no sensor is installed
(applies to humidity, temperature, and slider).
Objects Table
Object
Name
Type and
Instance
Description of Present_Value Property
Humidity AI 1 Humidity in percent
Temperature AI 2 Temperature in Fahrenheit or Celsius
Slider AI 3 Slider position in percent.
Device_
Instance
AV 1 Alternative way to change object_identier property of
device. A negative value will restore the default device
instance (133nnn). Fractional values are truncated.
Temp_
Oset
AV 2 Temperature oset.Value rounded to nearest tenth of a
degree. Units are current units. Initial value is zero.
RH_Oset AV 3 Relative Humidity oset. Value rounded to the nearest tenth of
a percent. Initial value is zero.
Fahrenheit BV 1 1 if temperature in Fahrenheit, 0 if in Celsius. Initially 1
Override BV 2 1 if override button pressed. Store 0 to reset. Initially 0. Volatile
CONFORMANCE STATEMENT
Vendor Name: Veris Industries
Product Name: Veris HWxP Environmental Sensor
Product Model Number: HWxPxxx
Application Software Version: 1
Firmware Revision: x.x
BACnet Protocol Revision: 2
Product Description: Environmental Sensor
BACnet Standardized Device Prole (Annex L): BACnet Application Specic Controller
(B-ASC)
List all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B,DS-RPM-B,DS_WP-B,DM-DDB-B,DM-DOB-B,,DM-DCC-B
Segmentation Capability: Segmentation not supported
Standard Object Types Supported:
No dynamic creation or deletion supported
No proprietary properties or object types
(other information about objects on preceding pages)
Data Link Layer Options: MS/TP master (Clause 9), baud rates: 9600, 19200, 38400,
76800
Device Address Binding: Static device binding is not supported. (No client functional-
ity is included).
Networking Options: None
Character Sets Supported: ANSI X3.4
Device Objects Table
Object
Name
Type and
Instance
Object
Property
Description
HWxPxxx Device
133nnn
Object_Identier
(R/W)
Unique value where nnn initially is MS/TP
Object_Name
(R/W)
Unique name, initially a combination of
model and serial number. Maximum length
is 64 characters
APDU_Timeout Default is 3000, maximum value is 60000
Max_Master Default is 127
Description Maximum length is 64 characters
Location Maximum length is 64 characters

This manual suits for next models

8

Popular Security Sensor manuals by other brands

CARLO GAVAZZI Guardian 1 Original user manual

CARLO GAVAZZI

CARLO GAVAZZI Guardian 1 Original user manual

GJD Dual Tech GJD360 installation manual

GJD

GJD Dual Tech GJD360 installation manual

FGD FlameSpec IR3-H2-HD user manual

FGD

FGD FlameSpec IR3-H2-HD user manual

RKI Instruments 35-3010RKA-04H Operator's manual

RKI Instruments

RKI Instruments 35-3010RKA-04H Operator's manual

ELRO PRO Sensus4H instruction manual

ELRO

ELRO PRO Sensus4H instruction manual

Bticino HA/HB/L4619 manual

Bticino

Bticino HA/HB/L4619 manual

CDP CDP-001F manual

CDP

CDP CDP-001F manual

Pilz PSEN sc M 3.0 08-17 operating manual

Pilz

Pilz PSEN sc M 3.0 08-17 operating manual

C-LOGIC 645-MD instruction manual

C-LOGIC

C-LOGIC 645-MD instruction manual

DBI SALA ROLLGLISS R550 User instruction manual

DBI SALA

DBI SALA ROLLGLISS R550 User instruction manual

Cabletech URZ0420 owner's manual

Cabletech

Cabletech URZ0420 owner's manual

AVS Electronics BF100 R manual

AVS Electronics

AVS Electronics BF100 R manual

THORLABS APD110 Series Operation manual

THORLABS

THORLABS APD110 Series Operation manual

STEINEL HF 3360-R AP WS COM1 Information

STEINEL

STEINEL HF 3360-R AP WS COM1 Information

Autonics PR Series product manual

Autonics

Autonics PR Series product manual

Greenlee 1110 instruction manual

Greenlee

Greenlee 1110 instruction manual

TRIGA TR-PC2RL Installation and maintenance instructions

TRIGA

TRIGA TR-PC2RL Installation and maintenance instructions

HANK Electronics HKWL-DWS02W user manual

HANK Electronics

HANK Electronics HKWL-DWS02W user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.