Verkada AC12 User manual

Document
Document Details
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
V1.0 (20231031)
(V1.0 first published 20231031)
Firmware
Firmware version can be verified on
Verkada Command command.verkada.com.
Product Models
This install guide pertains to AC12-HW.
UL294 Performance Levels
●Attack Level: Level 1
●Endurance Level: Level 1
●Line Security Level: Level 1
●Standby Power Level: Level 1
CAN/ULC-60839-11-1
●Environmental Level: Outdoor
●Grade Assignment: Grade 1
2

Introduction
Recommended Testing
3
Installation and/or maintenance of this product shall be performed by trained
professionals only.
To ensure ongoing functionality of the AC12, we recommend that you check these
interfaces every 6 months:
●Short each input to its adjacent GND port and verify that LED illuminates.
●Use multimeter to confirm expected impedance across relay outputs.
○Closed across NC and COM
○Open across NO and COM
●Use multimeter to verify correct voltage is supplied at 12V AUX output, relay contact
outputs, and reader power outputs.
●Check the shielding cables of the readers and other AUX wiring, if any, for proper
connection to the grounding screw(s) on the chassis.
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.

4
Introduction
AC12 Technical Specifications
Power Consumption 60W maximum
Power Input IEEE 802.3af/at/bt PoE, PoE+, PoE++ (37VDC — 57VDC), 600mA maximum
per pair; 12VDC with 2.5A minimum current
Inputs 2x REX dry inputs
1x DPI dry input
1x AUX dry input
Readers
2x 12VDC @ 250mA reader ports (Verkada/RS-485 or Wiegand)
Note: Each of the 2 reader ports can power a maximum of 1 reader with
current consumption of at most 250mA.
PoE Output IEEE 802.3af/at PoE, PoE+ (37VDC–57VDC), 600mA maximum
Relay Outputs
1x wet relay for door with switch-selectable power:
●12VDC operation @ 700mA maximum
●24VDC operation @ 350mA maximum
●Dry operation
1x dry relay for auxiliary output with maximum pass-through power of
24VDC @ 2A (resistive load)
DC Power Output 1x 12VDC @ 100mA maximum
Dimensions 175.5 x 175.4 x 55.3 mm (6.91 x 6.91 x 2.18 in)
Weight 2.87 lb (1.30 kg)
Tamper Detection Yes
Operating Temperature 0 °C-50°C, 5-85% humidity
Compliance
FCC Part 15B Class B, ICES-003 Class B, CE, UKCA, VCCI, RCM, UL 294,
CAN-ULC 60839-11-1, UL 62368-1, and CSA C22.2 No. 62368-1, IK06,
Compliant with Requirements of UL2043, Indoor Use Only, to be used in
controlled, protected, and/or restricted access areas.
Installation and operation of the electronic access control system (EACS)
shall not prevent the functionality of the emergency exit functions.
Connectivity Ethernet: 10/100/1000 Mbps RJ-45 for network connection
USB 2.0
Included Accessories T10 Security Torx screwdriver, mounting hardware kit
Mounting Options Wall, Ceiling, or Plenum Mount
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.

5
Introduction
AC12 Power Options
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
PoE++
Single Reader
and
USB Disabled
PoE++
In/Out Door
and/or
USB Enabled
PoE+ PoE DC Only
Reader 1 12VDC @
250mA max 12VDC @
250mA max 12VDC @
250mA max 12VDC @
250mA max 12VDC @ 250mA
max
Reader 2 No 12VDC @
250mA max 12VDC @
250mA max 12VDC @
250mA max 12VDC @ 250mA
max
Wet Lock
12VDC @
700mA max
or
24VDC @
350mA max
12VDC @
700mA max
or
24VDC @
350mA max
12VDC @
700mA max
or
24VDC @
350mA max
12VDC @
500mA max
or
24VDC @
250mA max
12VDC @ 700mA
max
or
24VDC @ 350mA
max
USB No 5VDC @ 250mA
max 5VDC @ 250mA
max No 5VDC @ 250mA
max
DC Power
Out 12VDC @ 100mA
max 12VDC @ 100mA
max 12VDC @ 100mA
max No 12VDC @ 100mA
max
PoE Out Up to 30W Up to 27W Connectivity
only, no power Connectivity
only, no power Connectivity
only, no power
This chart outlines the available power options on the AC12. All power outputs and inputs
of this controller are Power-Limited/Class 3.

Introduction
What’s in the box
What you’ll need
●A working internet connection
●A smartphone or laptop
●A #2 Phillips screwdriver or
power drill with a #2 Phillips driver bit
●1/4 inch (6.5mm) drill bit for wall anchors
●1/8 inch (3mm) drill bit for pilot holes
●A shielded Cat5E or better Ethernet cable with
a .2–.25 in (5-6.5mm) outside diameter
●Flathead screwdriver
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
Cover
(Attached to controller)
6
Mount Plate
(Attached to controller)
#6-32 Machine Screws (4 pcs)
Length: 25.4mm Drive: #2 Phillips
M4 Wall Screws (4 pcs)
Length: 25mm Drive: #2 Phillips
Connect
For easy registration and setup, scan
the QR code on the product.
If you prefer to manually register your
product, go to verkada.com/start.
T10 Security Torx
Screwdriver
Controller
Wall Anchors (4 pcs)
Length: 25mm Drive: NO

Introduction
Overview
7Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
LED Lights
Status, Network,
PoE Out
Wiegand
Reader (1)
Third-Party
Voltage
Selection Switch
Disconnect power
before using the
selection switch
Mount Plate
Security Screw
QR Code
Scan to register
device in Verkada
Command
PoE
In/Out 12V DC
In/Out USB
AUX
AUX In/Out, REX2
Door 1
Door Output Relay,
REX1, DPI
Verkada
Reader (1)
Wiegand
Reader (2)
Third-Party
Verkada
Reader (2)

Solid Magenta
Power input is 802.3af PoE, so
some functionality may be
limited. See Install Guide Pg 5
for details.
Flashing Magenta
Unknown issue. Please
contact our 24/7 Technical
Support Team.
Introduction
8
LED Behavior 1/3
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
Solid Blue
Running and healthy
Flashing Blue
Network issue. See Network LED
for diagnosis.
Solid Orange
Booting up
Flashing Orange
Updating firmware
Status LED

Introduction
9
LED Behavior 2/3
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
Solid Orange
Camera is on and booting up.
Flashing Orange
Camera is updating firmware.
Solid Blue
Camera is running, connected,
and recording data.
Flashing Blue
Generic network error. Contact support.
Network LED
1 Blue, 1 Orange
Camera is connected with PoE, but
unable to connect to the switch.
1 Blue, 2 Orange
Camera has not received an IP address.
1 Blue, 3 Orange
Camera is unable reach the configured
Gateway.
1 Blue, 4 Orange
Camera has detected duplicate IP
addresses on the LAN.
The LED will flash in a specific order,
depending on the error state. You will
see 1 blue flash, followed by a number of
orange flashes.
Example of 1 Blue, 5 Orange flash sequence
1 Blue, 5 Orange
Camera is unable to resolve Verkada
hostnames.
1 Blue, 6 Orange
Camera is unable to receive a response
from the NTP Server.
1 Blue, 7 Orange
Camera is unable to certify the SSL
connection, likely due to SSL inspection.
1 Blue, 8 Orange
Verkada endpoints are unreachable
after boot up.
–

Introduction
10
LED Behavior 3/3
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
Solid Orange
Camera is on and booting up.
Flashing Orange
Camera is updating firmware.
Solid Blue
Camera is running, connected,
and recording data.
Flashing Blue
Generic network error. Contact support.
Solid Blue
Data and power up
to 30W
Solid Green
Data and power up to
27W
Magenta
Data only
No Light
PoE Out disabled via
Command
Blinking Amber
Data only
PoE Out LED

Installation
Preparation 1/2
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
11
Lay the controller on a flat surface.
Loosen the captive security screw,
using the provided T10 Security Torx
screwdriver.
Pull up the pull-tab to lift the cover.
Remove the sticker from the cover.

Installation
Preparation 2/2
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
12
Use the provided T10 Security Torx
screwdriver to loosen the captive
security screw.
With the security screw loosened, the
mount plate can slide off the
controller.

Installation
Mount Plate
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
13
Use the mount plate as a template and
mark the correct hole pattern needed.
A Direct wall/ceiling mount
B Square Junction Box (4 in [101.6mm])
C Single Gang Junction Box
D Round Junction Box (4 in [101.6mm) and
3½ in[88.9mm])
E Double Gang Junction Box
F European Junction Box
Through mounting surface or junction box Along the mounting surface
Cable Routing Options

Installation
Placement
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
14
Depending on the environment, and preference, AC12 can be mounted to either wall or ceiling.
Please note
Make sure to leave 6” of
clearance ….
6 in
(152mm)
To maintain unobstructed access to the captive security
screw, located on the cover of the controller, be sure to leave
a minimum of 6 in (152mm) of clearance from the bottom
edge of the device when mounting.
Security Screw Access
Wall Mounting
Ceiling
Mounting

Installation
Mounting 1/2
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © Verkada Inc. All rights reserved.
15
For wall mounting, drill pilot holes
using pattern ‘A’ on mount plate.
For a solid material like wood or
metal, drill ⅛-in (3.17mm) pilot
holes.
Drive the mounting screws
directly into the pilot holes.
For drywall, plaster or masonry,
separate wall anchors may be
required.
Once mount plate is firmly
attached to surface, bring the
cables through the mount plate.
Align the hook features of the
mount plate to the corresponding
cavities on the controller.
Gently set the controller into
position and slide it downwards.

Installation
Wiring Requirement
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © Verkada Inc. All rights reserved.
16
Do not route wires on top of controller,
or cover will not be able to attach.
Ensure wires are routed in between
mount plate and controller for
organization and to allow cover to
attach.

Installation
Mounting 2/2
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © Verkada Inc. All rights reserved.
17
Secure the controller to the mount
plate by tightening the captive
security screw.
Detachable terminal blocks
When wiring, terminal blocks can be
detached from the device for ease of
installation.

The door port’s Form C relay can be driven dry or wet.
AC12 is rated to power 12V locks up to 700mA and 24V
locks up to 350mA.
None/Dry
The AC12 does not provide power to the locking
hardware (typically used with external power supplies).
Wet
The AC12 provides 12V or 24V power to the locking
hardware.
18
1. Wire Fail Secure and Fail Safe
Locking Hardware
Fail secure and fail safe are ways of
configuring locking hardware:
●Fail secure hardware locks when power is
interrupted. Typically uses Normally Open
(NO) configuration.
●Fail safe hardware unlocks when power is
interrupted. Typically uses Normally Closed
(NC) configuration.
Installation
Connecting a Door 1/5
Ensure power is disconnected from the
AC12 and locking hardware before
wiring, removing or inserting readers,
locks or any other peripherals.
Warning
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.

19
2a. Connect the Lock (Dry)
When using an external power supply which accepts a dry contact, ensure
that “NONE” is selected on the door power selection switch.
Fail Secure
Fail Safe
2b. Connect the Lock (Wet)
In a Wet configuration, ensure that power selection
switch is set to the correct voltage as outlined by
the locking hardware specifications.
●Set it to “12VDC” for 12 volt locking hardware
●Set it to “24VDC” for 24 volt locking hardware
The AC12 is rated to power:
12V locks up to 700mA and 24V locks up to 350mA.
Fail Safe
LOCK (+) positive goes into NC
LOCK (-) negative and ground wire goes into COM
Fail Secure
LOCK (+) positive goes into NO
LOCK (-) negative and ground wire goes into COM
Installation
Connecting a Door 2/5
When connecting the lock in the Wet
configuration, ensure the negative of
the lock goes into the COM port as
shown in the diagrams below.
Warning
AC12
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
Input Output
IN
GND
NC
NO
COM
Input Output
IN
GND
NC
NO
COM
AC12 Access Power Controller Lock
AC12 Access Power Controller Lock
Lock AC12 Lock

20
Verkada/
RS-485
Reader
Standard
Wiegand
Reader
Verkada/RS-485 Reader Wiegand Reader
Wire Color Signal
Green Data 0
White/Gray Data 1
Brown Red LED
Orange Green LED
Red 12V Power+
Black 12V Power-
Wire Color Signal
Red 12V Power+
Black 12V Power-
Green B
White A
3. Connect the Reader
The AC12 is rated to power readers at 12V up to 250mA via the + (VIN) and – (GND) connection.
Reader power outputs are fuse protected up to 750mA. The reader cable shield should be secured
to the nearest drain wire screw on the AC12.
Installation
Connecting a Door 3/5
AC12 Shielded LV Cable Verkada Reader
AC12 Shielded LV Cable Wiegand Reader
Verkada Inc. 406 E 3rd Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2023 Verkada Inc. All rights reserved.
RED = 12V Power Positive
BLACK = 12V Power Negative
WHITE = A
GREEN = B
Drain
Wire
Drain
Wire
GREEN = Data 0
WHITE/GREY = Data 1
BROWN = Red LED
ORANGE = Green LED
RED = 12V Power Positive
BLACK = 12V Power Negative
Table of contents