VES t-line 120 Manual

VES Ref. ID.944
November 2021
Original Instructions
Eagle Close, Chandlers Ford Industrial Estate, Chandlers Ford, Eastleigh, Hampshire, SO53 4NF
Tel: +44 (0) 2380 46 11 50 email: inf[email protected] web: www.ves.co.uk
Issue G
Operation & Maintenance Manual
t-line 120
Extract Units

2
www.ves.co.uk
This manual must be read in full before Installation, Operation and Maintenance of the units
supplied
Please ensure that this document is passed to the end user. This manual forms an integral part of
the product and should be kept for the working life of the product. Additional copies of this and
supporting documents are available by contacting VES or by visiting www.ves.co.uk and following
the 'Download O & M's' link.
The following symbols used within this document refer to potential dangers, advice for safe
operation or important points of reference
Indicates hazards associated with electric current and high voltages
Indicates hazards that require safety advice for personnel or potential unit/property damage
Indicates important information
Warning
Caution
Important
Important
Conventions
Contents
1Introducon ....................................................................................................................
Page
2Nomenclature .................................................................................................................
3
4
5
6
7
8
Receipt of Goods/Handling ..........................................................................................
Installaon .......................................................................................................................
Set-up .................................................................................................................................
Wiring ................................................................................................................................
Controls ............................................................................................................................
Maintenance ...................................................................................................................
3
3
4
4
7
9
14
15
t-line Extract Units

3
www.ves.co.uk
-3
Point descripon Point Variants Details
Typical example
Part Number Coding
The T-Line is a range of direct drive duct mounted extract fans, designed typically for
arduous condions i.e hot air with high grease content. The standard ambient operang
temperature of the unit is -20 to +35°C, with in-duct airflow temperature up to 120°C.
For further technical details regarding dimensions and weights, contact VES andover Ltd. on
08448 15 60 60, quong the sales order (SO) number and the unit type as found on the unit
name plate or visit www.ves.co.uk.
Introducon
Nomenclature
1
2
1 Product TLL T-Line 120 Extract Unit
2 Unit Size 250
350
400
450
500
560
630
710
800
Unit size determined by
impellor size
3 Number of motor
po les
/2
/4
/6
2 Pole
4 Pole
6 Pole
4 Motor effciency 1
2
3
IE1 (EFF2)
IE2 (EFF1)
IE3
5 Phase -3 Three Phase
9 Powder coat type Null
/IT
/BT
Galvanised plantroom/RAL7004
weatherproof
Internally only as colour
Both internally and externally
coated as colour
6 Unit configuraon /PH
/PL
/WH
/WL
Plantroom straight through
Plantroom c/w boom inlet
Weatherproof straight through
Weatherproof c/w boom inlet
8 Colour Null
R7004
Galvanised plantroom /
RAL7004 weatherproof
Powder coat finish to any colour
1 2 3 4 5 6 8 9
TLL 350 /4 1 /BT/PH /R7004
7Enclosure
Opons
Null
/AE
Standard configuraon
Acousc Enclosure
7
t-line Extract Units
Important An Inverter Speed controller is required for the operaon of this fan

4
www.ves.co.uk
t-line Extract Units
Immediately upon receipt of goods, check for possible damage in transit. Also check to
ensure that any ancillary items are included. These will be supplied fied or taped to the
unit (in the case of small items). In the event of any damage having occurred or if any item
is found to be missing, it is essenal to inform VES Andover Ltd. within 3 working days of
delivery, quong the sale s order (SO) number, and the unit type as found on the unit
nameplate. Aer this period VES Andover Ltd. will be unable to accept any claim for
damaged or missing goods.
Receipt of Goods
When moving the unit, handle with care and in such a manner liming damage to the
casework. Parcular care must be taken when moving weatherproof units, any damage to
the external powder coat finish may reduce the ability to resist corrosion. Units are to be
rigged and lied using spreaders, taking into account the weight of the unit, liing gear
should be arranged so as not to bear on the casework.
Installaon
Safety for the enre system must be considered when installing the unit and it is the
responsibility of the installer to ensure that all of the equipment is installed in
compliance with the manufacturer’s recommendaons, with due r egard to the current
HEALTH AND SAFETY AT WORK ACT and conform to all relevant statutory regulaons.
Precauons should be in place so that in the unlikely event of component failure the risk of
personnel injury is reduced. For opmum unit performance, careful consideraon must be
paid to the locaon of the unit in relaon to the ductwork and associated items; i.e placing
the unit directly adjacent to a bend in the ductwork will impede airflow and reduce
performance.
Duct Connecons
Liing and Connecng
to Duct
Cauon
3
Important The unit should NOT be lied by handles, lids, housings, sha, motor or drive.
Only experienced engineers should undertake this work.
Secure liing cable through the liing lugs.
Ensure fan plate is securely in place before
liing the unit.
It is recommended that the unit is lied
using the supplied liing lugs.
(For illustraon
purposes only)
3
4
Recommended only with fied
turning vanes
RecommendedRecommended
Fig. 1
Fig. 2
Important An Inverter Speed controller is required for the operaon of this fan

5
www.ves.co.uk
The T-Line unit is de signed to be mounted in a range of orientaons. The unit can be
suspended from the cei ling using drop-rods, or bolted to the plant room floor. It is the
installer’s responsibility to ensure that there is sa fe working access provided to the unit f or
maintenance. The ins taller must also c onsider, adequate illuminaon of the unit, in order
for safe maintenance to be carried out .
•Motor on top
•Access on both sides
•Feet mounted on
boom
•Motor on side
•Access on both sides
•Feet mounted either
side of the access sides
•Motor on side
•Access on top
and boom
•Feet mounted on
boom access side
T-Line Unit
Orientaon
Fix mounng feet to the correct side dependant on the orientaon of the unit.
Ensure ALL fixings are used; if reposioning the feet, ensure all fixings are reinstated.
Fixing Feet
Installaon
Units should only be supported using the support feet as provided by VES Andover Ltd.
with the unit. Contact VES Andover Ltd. before aempng to support the unit using
alternave methods. Only experienced engineers should undertake this work.
Take necessary safety precauons when w orking in ele vated posions.
Cauon
The electrical supply must be fully isolated before aempng to complete any work on
this unit. All electrical connecons to any unit must be carried out in accordance with
the current edion of the I.E.T Regulaons and only competent electricians should be
allowed to carry out any electrical work to our units.
Warning
Connued
4
All Sizes 250 -710 only (not for 800)
Important
Fig. 3
Fig. 4
t-line Extract Units

6
www.ves.co.uk
On weatherproof units the motor must be guarded, this is done by rotang the motor guard
to the correct orientaon. (Meshed edges facing the ground).
2
Important
Changing the handing of the isolator consists of removing the bracket fixings, re-aaching
the bracket to the opposite side.
For units with plugs, ensure pins are correctly paired when connecng the plug to the isolator
Warning
Handing Isolator
Plate
Handing Motor Guard
Installaon Connued
4
123
2
As standard, isolators are hard-wired to the motor. Older units may feature plugged connecon.
Important
Fig. 5
Fig. 6
t-line Extract Units

7
www.ves.co.uk
Before aempng to carry out any maintenance work, invesgave work, or repair work
on our units, the unit MUST BE COMPLETELY ISOLATED from its electrical supply. Ensure a
minimum of two minutes aer electrical disconnecon before removing access panels.
Warning
Before aempng to carry out any work on our units, all accompanying documentaon
including warning labels on the unit must be referenced.
Should it be necessary to remove any component ensure that these are secured into
posion once reinstalled. It is crical that aer any maintenance work has been
conducted that all components removed/replaced are refied correctly by a competent
engineer.
When accessing the unit always use the handles to ensure the access panels are
handled/opened in a controlled manner so as to avoid damage to the unit or injury to
personnel. This is parcularly important with boom access units.
Cauon
Remove the access panels and loosen the bolts holding the inlet eye in place. Align the
inlet eye and impeller ensuring the inlet eye is central to the impellor and make sure gap
‘A’ is constant. Hand ghten the bolts and rotate the impellor to ensure the it runs
smoothly, secure into posion b y ghtening the retaining bolts.
A
Ensure that the clearance gap “A” between fan and inlet eye is constant. Misalignment
may cause undue wear on the impeller and inlet eye.
Always make sure the fan is rotang in the
correct direcon (an-clockwise when viewed
from the motor). Direcon of airflow is
indicated on the unit.
Impeller/Inlet Eye
Alignment
The impeller should r otate freely, this posion is f actory set. In the unli kely event of
movement during transit realign the impellor with the inlet eye.
Important
Impeller rotaon
Cauon
Before starng the unit ensure the following set-up procedures are completed. Work to
be carried out by a competent engineer.
Important
Note: Motor rotaon can be seen on the motor
cooling fan on the end of the motor.
WP units may require the temporary removal of
the motor cover.
Set-up 5
Fig. 7
Fig. 8
t-line Extract Units

8
www.ves.co.uk
This differenal pressure compares the stac pressure in front of the fan inlet ring with the
stac pressure in the inlet ring of the narrowest point. The differenal pressure between
the stac pressures is related to the air volume via the energy conservaon rate as per the
graph below. Simply read across from the pressure measurement to the appropriate fan
curve and down to calculate the resultant air volume.
Measured differenal pressure: 1400Pa - Unit: TLL400
Reading from graph: 1.6 = Air Volume: 1.6 m³/s
Differenal pressure
tapping point
Set-up 5 Connued
Example:
0
250
500
750
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10 10.5 11
Δpw Differen"al Pressure Pa
TLL350
TLL250
TLL400
TLL450
TLL500
TLL560
TLL630
TLL710
TLL800
TLL250 = 60
TLL350 = 121
TLL400 = 154
TLL450 = 197
TLL500 = 252
TLL560 = 308
TLL630 = 381
TLL710 = 490
TLL800 = 620
k(nozzle coefficient)
1400
1.6
q Air Volume m³/sv
This measurement can also be expressed in the following calculaon:
qV is the air v olume in m³/s
k is the fan nozzle coefficient
pW is the measured differenal pressure
in Pa
q = (k
vpw) / 3600√Δ
Δ
Alternavely, to calculate a differenal pressure reading from a volume:
Δpw = (( 3600) )qv×
Example:
Measured differenal pressure: 1400Pa
Unit: TLL400
qV = (154 1400) / 3600
qV = (154 x 37.417) / 3600
qV = 5762 / 3600
qV = air volume = 1.6 m³/s
Example:
Required air volume (qV) = 1.6 m³/s
Δpw = ((1.6 3600) 154)
Δpw ²= (37.4)
Δpw = 1399 Pa
×
Fig. 9
Fig. 10
t-line Extract Units

9
www.ves.co.uk
VES supply, a fit ted pre-wired isolator, mains c ables which should be suit ably sized, refer to
table, and terminated as shown on the appropriate wiring diagram, refer to pages 10-14.
Ensure that suitable strain relief is fied to the mains supply as appropriate.
The electrical supply must be fully isolated before aempng to complete any work on this
unit. All electrical connecons to any unit must be carried out in accordance with the
current edion of the I.E.T Regulaons and only competent electricians should be allowed to
carry out any electrical work to our units.
Warning
Motor and electrical details must be checked prior to connecon to electricity supply.
All motor informaon can be found on the unit data sheet supplied aached to the unit.
It is the cus tomer’s responsibility to supply earth fault protecon through the bui lding
installaon device and a dedicated, isolated power supply with overload protecon, to
account for motor start-up currents. For specific fan details see table below
Do not connect any unit to an electrical supply voltage outside of the specificaon
Important
Standard
3 Phase Motor
Electrical Details
Wiring 6
Warning
Fig. 11
t-line Extract Units
Important An Inverter Speed controller is required for the operaon of this fan

10
www.ves.co.uk
Customer connecons 400 V AC - 3 Phase - 50Hz
3 Phase Direct on Line Isolator Wiring Diagram
Wiring 6Connued
Warning
Fig. 12
For units with plugs, ensure pins are correctly paired when connecng the plug to the isolator
Star Connecon Delta Connecon
t-line Extract Units
Important An Inverter Speed controller is required for the operaon of this fan

11
www.ves.co.uk
1 Ph - 3 Ph Inverter Isolator Wiring Diagram
Customer connecons
230 V AC - 1 Phase - 50Hz
Customer connecons
400 V AC - 3 Phase - 50Hz
3 Ph - 3Ph Inverter Isolator Wiring Diagram
Warning
Wiring 6Connued
Fig. 13
For units with plugs, ensure pins are correctly paired when connecng the plug to the isolator
t-line Extract Units
Important An Inverter Speed controller is required for the operaon of this fan

12
www.ves.co.uk
Warning
Customer connecons 400 V AC - 3 Phase - 50Hz
3 Phase Star/Delta Isolator Wiring Diagram
Star/Delta Connecon for units
with motors 7.5kW larger.
Wiring 6Connued
Fig. 14
For units with plugs, ensure pins are correctly paired when connecng the plug to the isolator
t-line Extract Units
Important An Inverter Speed controller is required for the operaon of this fan

13
www.ves.co.uk
Customer connecons 400 V AC - 3 Phase - 50Hz
3 Phase Delta Isolator Wiring Diagram
Warning
Delta Connecon for units
with motors 7.5 kW larger.
Wiring 6 Connued
Fig. 15
For units with plugs, ensure pins are correctly paired when connecng the plug to the isolator
t-line Extract Units
Important An Inverter Speed controller is required for the operaon of this fan

14
www.ves.co.uk
t-line Extract Units
VES offer a range of controls suited for the control of selected motors used on the T-Line
range. Three phase speed controllers use frequency drivers that offer 0-100% stepless
control from a wide range of input signals.
Note: Inverters can cause interference to nearby electronic equipment and must be
installed correctly to avoid this happening.
Inverter with comprehensive range of
funcons and IP54 enclosure.
•Sized to match T-Line 3 phase motor.
•Complete with operaonal keypad.
•Oponal advanced keypad with built-in
me clock.
•IP54 protecon for indoor or external use.
•BMS control, remote pot,
temperature, constant pressure, humidity
and CO2/VOC control.
•Main isolang switch with lockable handle.
•Panel live indicator.
•Damper control.
•Volt free run and trip indic aon.
•Connecons for motor thermal cutout safety
interlock.
•Easy customer installaon.
Low cost inverter with IP21 enclosure.
Suitable for internal locaon.
•Sized to match T-Line 3
phase motor.
•Complete with operaonal
keypad.
•IP21/NEMA1 protecon for
indoor use.
•On/off control at inverter pad
with built-in pot for easy
adjustment, and BMS
control. Remote pot control
available (CFSC1).
IP21 Inverter IP54 Inverter
IP21 Inverter Specificaon IP54 Inverter Specificaon
The electrical supply must be fully isolated before aempng to complete any work on
this unit. All electrical connecons, to any unit, must be carried out in accordance with the
current edion of the I.E.E Regulaons, and only competent Electricians should be allowed
to carry out any electrical work to our units.
Warning
Controls 7
Important For informaon regarding associated components (speed controllers, controls) please
refer to the relevant accompanying O&M
Fig. 16
Important An Inverter Speed controller is required for the operaon of this fan

15
www.ves.co.uk t-line Extract Units
Before aempng to carry out any maintenance work, invesgave or repair work on our
units, the unit MUST BE COMPLETELY ISOLATED from its electrical supply. Ensure a minimum
of two minutes aer electrical disconnecon before removing access panels.
Warning
Before aempng to carry out any work on our units, all accompanying documentaon
including warning labels on the unit must be referenced.
Should it be necessary to remove any component ensure that these are secured into
posion once reinstalled. It is crical that aer any maintenance work has been conducted
that all components removed/replaced be refied correctly by a competent engineer
Important
In general, this series of units require lile maintenance. Regular inspecon for damage
and cleaning. In the unlikely event of component failure, spares are available from stock
at VES.
Ensure the unit has been allowed to completely cool before aempng any work to the
unit.
Cauon
Ensure impellor has been allowed to completely stop before aempng to carry out any
work on this unit.
When accessing the unit always use the handles to ensure the access panels are
handled/opened in a controlled manner so as to avoid damage to the unit or injury to
personnel. This is parcularly important with boom access units.
Once maintenance has been carried out ensure the motor assembly is secured correctly
before restarng the unit.
Remove the access panels and loosen the bolts holding the inlet eye in place Align the
inlet eye and impeller ensuring the inlet eye is central to the impeller and make sure gap
‘A’ is constant. Hand gh ten the bolts and rotate the impeller to ensure the it runs
smoothly, secure into posion b y ghtening the retaining bolts.
Impeller/Inlet Eye
Alignment
The impeller should rotate freely and this posion is factory set. In the unlikely event of
movement during transit or operaon realign the impeller with the inlet eye.
Important
Maintenance 8
A
Fig. 17
Cauon
Ensure that the clearance gap “A” between fan and inlet eye is constant. Misalignment
may cause undue wear on the impeller and inlet eye.
Cauon

16
www.ves.co.uk
t-line Extract Units
Maintenance 8
Always make sure the fan is rotang in the correct direcon (an-clockwise when viewed
from the motor). Direcon of airflow is indicated on the unit.
Impeller Rotaon
Note: Motor rotaon can be
seen on the motor cooling fan
on the end of the motor.
WP units may the require
temporary removal of motor
cover.
Connued
In order to remove the motor plate for maintenance remove the fixings and secure liing
cable to lugs, also ensure the isolator has been disconnected refer to page 6. Ensure fan
assembly is gh tned before liing the mot or plate off.
Liing Fan
Assembly
Liing Haz ard: Single person li c ould cause injury. Use assistance when mo ving or liing
Cauon
Fig. 18
Fig. 19

17
www.ves.co.uk t-line Extract Units
Fan Assembly
Important
When re-assembling the fan and motor ensure the bush is secured ghtly to the motor
sha with the impeller correctly aligned. Ensure the impeller rotates freely leaving a
level gap of ‘B’ (as shown below) between the impeller and the top plate.
B
Maintenance 8 Connued
Cauon
If dismantlement is required due to a blockage ensure motor and impeller are reassembled
and installed correctly as in the following diagram.
For isolator bracket removal refer to page 6.
Bush
Impellor
Top
Plate
Lug
Gasket
Motor
Motor plate
Liing Haz ard: Single person li c ould cause injury. Use assistance when mo ving or liing
Cauon
Fig. 20
Fig. 21 Impeller Ø (mm) 250 350 400 450 500 560 630 710 800
Distance B (mm) 20 20 25 25 20 32 32 28 32
Bush Type 1210 1210 1210 2012 2012 2012 2517 2517 2517
Tightening Torque (Nm) 20 20 20 30 30 30 50 50 50
Fig. 22

18
www.ves.co.uk
t-line Extract Units
When enquiring about or ordering spares contact VES Spares Department, quong the sales
order (SO) number and unit type found on the unit name plate.
Tel: 08448 15 60 60 - Fax: 02380 26 12 04
Spares & Repairs
The fan impeller should be cleaned every 6 months. Failure to clean the fan on a regular
basis could result in loss of fan performance, or cause it to fall out of balance. If a fan is
staonary for long periods in a humid atmosphere, it should be switched ON for minimum
of two hours every month to remove any moisture that may have condensed within the
motor.
T-Line units are supplied in both unp ainted and po wder coat painted galvanised sheet
steel cases. Check all painted items to ensure that they have not deteriorated, parcularly
where adverse environmental condions prevail. Re-paint as necessary. Matching paint can
be supplied upon request.
Twelve Monthly
Checks
Six Monthly
Checks
Recommended
Checks
In order to keep the unit in good order the following maintenance roune is recommended.
Maintenance 8 Connued
WEEE Direcve At the end of their useful life the packaging and product should be disposed of via a
suitable recycling centre. Do not dispose of with normal household waste. Do not burn

Eagle Close, Chandlers Ford Industrial Estate, Chandlers Ford, Eastleigh, Hampshire, SO53 4NF
Tel: +44 (0) 2380 46 11 50 email: inf[email protected] web: www.ves.co.uk
VES is a trading name of VES Andover Ltd.
Registered in England No. 02303719.
Registered Office as above.
©VES Andover Ltd. 2021
Operation & Maintenance Manual
t-line 120
Extract Units
Table of contents
Popular Ventilation Hood manuals by other brands

Weller
Weller Zero Smog 4V Translation of the original instructions

ETNA
ETNA AO561WIT Instructions for use

Lamona
Lamona LAM2850 Instructions & installation

Miele
Miele DA 3568 Operating and installation instructions

Westinghouse
Westinghouse WRH605I Series Operation guide

DCS
DCS Professional Island Vent Hood IVS40 Use and care guide