
4
Viconics
T
echnologies
Inc.
www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150028-0427-11 October 2018
Introduction
This guide shows the User Interface instructions for the VT8300 Series Room Controller (Firmware Release version 1.7) for User and
Integrators.
User and Integrator Screens
The VT8300 Room Controller has dynamic screens and parameters that only appear on certain models or based on the presence of
a communication module (VCM). The LUA tab on the second menu screen, will also only show if a LUA script is uploaded to the Room
Controller.
See below legend screen details.
Read Only parameter
6/7 Configuration
Language English
Units °C
Low backlight 60 %
Night backlight 5 %
RH display Disable
Parameter Screen
Parameter XXXX
XXXXParameter
XXXXParameter XXXXParameter
Adjustable parameter
Some parameters appear only when Zig-
Bee wireless communication module is
installed, or if a LUA script is uploaded.
Change Value
Previous
screen
Next
screen Return to pre-
vious menu
Notes
1. When any change is made to a parameter, the value is permanently saved in the database when the
next parameter is selected or another screen is opened. This event is true only if a parameter was
changed locally on the Room Controller. Making changes through BACnet will not have the same
outcome. If permanent changes need to be done remotely through BACnet, use priority 1, 2 or 3, or
write to relinquish default (priority 17)
2. The ZigBee Pro communication module must be Revision 10 (R10) or later to support newly
introduced devices such as water leak sensor and the ZigBee Green Power environmental sensor.
3. The Room Controller must be running Firmware version 1.7 or later to enable the Automatic Demand
Response (ADR) feature.