Viconics VT8600 Series User manual

1
Version 11
VT8600 Series User Interface Guide
Rooftop Unit, Heatpump and Indoor Air Quality Controller

2
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Table of Contents
Section 1
Introduction 4
User and Integrator Screens 4
Disclaimer 5
HMI Display 7
Section 2
User HMI for Hospitality 11
User HMI for Commercial 12
System Mode 13
Fan Mode Settings 13
Heating Only Configuration 14
Setpoint Adjustment Cooling 14
Setpoint Adjustment Heating 15
Other Functions 15
Customizable Color Options 16
Network Settings 18
ZigBee Network Settings 22
BACnet Network Settings 22
Modbus Network Settings 24
Configuration Screens 26
Setpoint Screens 49
Display Screens 54
Service View Screens 59
Test Outputs Screens 70
Language Selection Screens 73
Schedule Screens 75
ADR Screens 80
Wireless Screens 83
Lua Screens 94
Section 3
Appendix 97

SECTION 1
Introduction

4
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Introduction
This guide shows the User Interface instructions for the VT8300 Series Room Controller (Firmware Release version 1.7) for User and
Integrators.
User and Integrator Screens
The VT8300 Room Controller has dynamic screens and parameters that only appear on certain models or based on the presence of
a communication module (VCM). The LUA tab on the second menu screen, will also only show if a LUA script is uploaded to the Room
Controller.
See below legend screen details.
Read Only parameter
6/7 Configuration
Language English
Units °C
Low backlight 60 %
Night backlight 5 %
RH display Disable
Parameter Screen
Parameter XXXX
XXXXParameter
XXXXParameter XXXXParameter
Adjustable parameter
Some parameters appear only when Zig-
Bee wireless communication module is
installed, or if a LUA script is uploaded.
Change Value
Previous
screen
Next
screen Return to pre-
vious menu
Notes
1. When any change is made to a parameter, the value is permanently saved in the database when the
next parameter is selected or another screen is opened. This event is true only if a parameter was
changed locally on the Room Controller. Making changes through BACnet will not have the same
outcome. If permanent changes need to be done remotely through BACnet, use priority 1, 2 or 3, or
write to relinquish default (priority 17)
2. The ZigBee Pro communication module must be Revision 10 (R10) or later to support newly
introduced devices such as water leak sensor and the ZigBee Green Power environmental sensor.
3. The Room Controller must be running Firmware version 1.7 or later to enable the Automatic Demand
Response (ADR) feature.

5
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Disclaimer
*Disclaimer
Standby screen: The Room Controller incorporates TFT-type LCD technology, and therefore,
necessary precautions are required to prevent the phenomenon of image retention (residual
image) from occurring.
Image retention may occur when a static image is displayed on the screen for a prolonged pe-
riod of time. This can cause a faint outline of the image to remain visible on the screen when the
screen is changed via the user menu, or a different image is uploaded and selected to be dis-
played. To minimize and prevent image retention, it is recommended to select the Screen Save
setting on the Standby screen selection from the setup menu Display 1/2. This setting switches
the display during periods of inactivity from the Home Screen.
It is recommended to use a black or medium gray image, or one with light color contrasts as the
screen saver to prevent this phenomenon from occurring. If the display still exhibits this phe-
nomenon, loading an all-black or all-medium gray image as the screen saver and displaying it for
upwards of 5 hours continuously minimizes this effect.
NOTE: Avoid placing the Room Controller in poorly ventilated areas, or in areas that may
create excess heat around the display.

HMI Display and Set-up

7
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
HMI Display
The below shows a typical user interface for the hospitality industry. The User HMI is configurable and allows display functions such
as Date, Time, Humidity, Outdoor Temperature, and Setpoint to be enabled or disabled by setting various parameters.
Time
System Status
Fan Status
Increase Temperature Setpoint
Actual Setpoint
Decrease Temperature Setpoint
Indoor Humidity &
Outdoor Temperature
Indoor Temperature
Occupancy
Status
Help
Language Selection
Temperature Units
Fan Mode
System Mode
Date

8
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Touch and hold this point
for 3 seconds to enter setup mode
Note: If a conguration/installer
password is activated to prevent
unauthorised access to the
conguration menu parameters, a
password entry prompt shows to
prevent access to device
conguration components.
Enter Set-up Screen
SET UP 1/2
Return to
previous menu
1/2 Setup
Network
Configuration
Setpoints
Display
Service view
Test Outputs
Discover Mode shows wireless
ZigBee network. Icon not shown if
ZigBee communication module not
installed
BACnet MS/TP, Modbus and ZigBee network settings (ZigBee
network settings appear only if a communication module is installed)
Parameter configuration menu
Setpoint settings
Status display (Read Only)
Display settings
Test outputs settings

9
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
SET UP 2/2
2/2 Setup
Clock - Schedule
LUA
Wireless
Language Selection
ADR
Automatic Demand Response
LUA scripting (shows only if LUA script uploaded)
Wireless Ecosystem settings (shows only if ZigBee
communication module installed)
Select language
Set clock, schedule and occupancy

SECTION 2
Customized Screens

11
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
• Setpoint adjustment
• System mode setting
• Fan mode setting
• Local unit scale
adjustment
• Local user language
• User help menu
• Setpoint adjustment
• System mode setting
• Fan mode setting
• User help menu
• Local unit scale
adjustment
• Local user language
• User help menu
• Setpoint adjustment
• User help menu
Parameters are model dependent and may not appear on certain models.
• Fully locked interface
with no user settings
• Setpoint adjustment
• System mode setting
• User help menu
• Setpoint adjustment
• System mode setting
• Fan mode setting
• Local unit scale
adjustment
• User help menu
• Setpoint adjustment
• System mode setting
• Fan mode setting
• unoccupied mode
overdrive
• User help menu
0 (Hospitality) 1 (Hospitality) 2 (Hospitality) 3 (Hospitality)
4 (Hospitality) 5 (Hospitality) 6 (Hospitality) 7 (Commercial)
User HMI for Hospitality

12
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
• Setpoint adjustment
• Unoccupied mode
override
• Local user language
• User help menu
• Setpoint adjustment
• Unoccupied mode
override
• User help menu
• Unoccupied mode
override
• Setpoint adjustment
• System mode setting
• Unoccupied mode
override
• User help menu
Parameters are model dependent and may not appear on certain models.
Note:
The day/night setback button appears only in unoccupied mode from 7 to 11 in HMI Commercial.
If UI17 input is congured as “override”, the day/night setback button does not show.
8 (Commercial) 9 (Commercial) 10 (Commercial) 11 (Commercial)
Commercial User HMI
12 (Commercial)
• Offset setpoints
adjustment
• System mode setting
• User help menu
+ 1.5

13
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
System Mode
The following apply in System Mode.
Mode Signicance and Adjustments
System mode Off Off
Heating, Cooling and Dehumidification demands are ignored
System mode Auto Auto
Room Controller automatically toggles between Heating and Cooling modes to satisfy both Heating and
Cooling demands. Dehumidification is allowed
System mode Cool Cool
Room Controller only satisfies Cooling demands, Heating demands are ignored. Dehumidification is
allowed
System mode Heat Cool
Room Controller only satisfies Heating demands, Cooling demands are ignored. Dehumidification is
allowed
Fan Mode Settings
Fan Mode Setting
Mode Signicance and Adjustments
Fan mode ON On
Fan is on continuously, even when system mode is OFF.
Fan mode Auto Auto
Fan cycles on a call for heating or cooling for both occupied & unoccupied periods.
Fan mode Smart Smart
During occupied periods, fan is on continuously. In unoccupied mode, fan cycles on a call for heating or
cooling.

14
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Time and Date show only when a
network time synchronisation command is
received.
Setpoint value shows if main
display parameter is set to
Setpoint.
On/Off icon is used instead
of system mode icon when
sequence of operation is set
to either heating on or
cooling only.
Cooling mode or cooling only sequence of
operation.
Heating only Configuration
Setpoint Adjustment for Cooling Mode
In Cooling mode, the setpoint displayed in the bar is the current occupied cooling setpoint. During occupied setpoint adjustment, the
large digits are temporarily used to show occupied cooling setpoint while it is adjusted.
Normal temperature display resumes after setpoint is adjusted and actual occupied cooling setpoint shows in setpoint bar.

15
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Automatic Heating/Cooling Mode
Setpoint Adjustment for Heating Mode
In automatic mode, setpoint showing at the top of the set point bar located directly under the blue line represents the actual oc-
cupied cooling setpoint.
During occupied setpoints adjustment, large digits are temporarily used to display the occupied Cooling
Setpoint or occupied Heating Setpoint. The actual setpoint is dependent on the last effective demand (heating or cooling). The
setpoint on top of the red line represents the actual occupied heating setpoint. The differential between the occupied heating and
cooling setpoint is defined by the minimum deadband configuration parameter.
Normal temperature display resumes after setpoints are adjusted and the actual occupied heating and cooling setpoints show in
the setpoint bar.
Other Functions
Local humidity only shows on models with the humidity sensor present and when enabled by conguration
property RH Display.
Outdoor temperature display is dependent on receiving a valid networked outdoor temperature value.

16
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Customizable Color Options
2018.04.18 12:54 PM 2018.04.18 12:54 PM 2018.04.18 12:54 PM
2018.04.18 12:54 PM 2018.04.18 12:54 PM

Network Screens

18
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Network Settings
User can select wired BACnet / Modbus / ZigBee wireless protocol (requires optional communication module).
Network
BACnet
Wired protocol
Optional prot.
None ZigBee card detection (Read Only)
Wired protocol (BACnet MS/TP or
Modbus)
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
Optional prot.
Read Only
Optional Protocol
Requires installation of optional ZigBee Pro communication module.
None: No ZigBee card detected
ZigBee: ZigBee card detected
Display Readings: None or ZigBee
Wired protocol
Default value: BACnet
Wired Protocol
None: No wired protocol configured
BACnet: BACnet MS/TP network protocol
Modbus: Modbus network protocol
Choices: None, BACnet or Modbus

19
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
1/2 ZigBee Network
COM address 254
Node type
PAN ID 25
Channel 15
Network status No NWK
Permit join Off
Router
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
COM address
Default value: 254
COM Address
Room Controller networking address. For wireless models, the use of the COM
address is not mandatory. The COM address is an optional way to identify a device
on the network and is recommended if used with an MPM. It is Mandatory for BACnet.
Range: 0 to 254
Node type
Default: Router
Node Type
Sets device to act as Router or Coordinator in a network.
Coordinator: Creates the network and manages the binding of wireless devices.
Router: Joins a network created by a coordinator (permit join must be set to ‘ON’).
Choices: Coordinator or Router
Pan ID
Default value: 0
ZigBee Pan ID
Personal Area Network Identification that links specific Room Controllers to specific
ZigBee coordinators. For every Room Controller reporting to a coordinator, set the
SAME PAN ID value both on the coordinator and the Room Controller.
NOTE: The default value of 0 is NOT a valid PAN ID.
NOTE: For Room Controllers running Firmware version 1.3 and earlier, the PAN ID
must be set to 501-1000 for the Room Controller to act as a coordinator.
Range: 1 to 32767
ZIGBEE NETWORK 1/2
The ZigBee Pro Network screen shows only when the optional ZigBee Pro communication module is detected in the device. When
setting up a ZigBee network to bind with multiple devices, there must first be a Coordinator to manage the initial binding between the
Router and the end devices. After successful binding, the Router becomes the parent to the end devices.
NOTE: Before binding any ZigBee devices, the network must first be created by the Coordinator.

20
Viconics Technologies Inc. www.viconics.com | [email protected]| Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0427-11 October 2018
Channel
Default value: 10
ZigBee Channel
The frequency or channel on which the ZigBee network transmits and receives data.
The channel of the Coordinator must match that of the routers to exchange data.
The default value of 10 is NOT a valid channel. The valid range of available channel is
from 11 to 25.
Using channels 15 and 25 is recommended.
Range: 10 to 25
Network status
Read Only
ZigBee Network Status
Shows the current status of the ZigBee network.
No NWK: ZigBee configured but no network joined
Joined: ZigBee network joined
Online: Communicating (Exchanging data)
Display Readings: No NWK, Joined, Online
Permit join
Default value: On
Permit Join
Changing this value to “Off” on the Coordinator prevents any new ZigBee devices
from joining the network.
Permit join can be On/Off when the Room Controller is a Coordinator, however the
parameter is read only when the Room Controller is a router. If not set to off manually
the Permit join will stay On for 3 hours.
Choices: On or Off
Other manuals for VT8600 Series
2
This manual suits for next models
1
Table of contents
Other Viconics Control Unit manuals