2213-66251540-EN - V2.0 - 10/10/22
6
2213 Remote Relay - Technical Manual
2213 Remote Relay for the VX2200 System
INSTALLATION NOTES
When installing the 2213LIFT remote relay follow the list of installation checks below:
• Check that all components are free from damage before installing, do not proceed with the installation in the event of
damage.
• Keep all packaging away from children (please dispose of any excess waste and packaging responsibly).
• Do not obstruct the ventilation openings or slots on any of the devices.
• All connections to mains voltages must be made to the current recognised national standards: I.E.T. Wiring Regulations,
Eighteenth Edition BS7671:2018 for the UK or the appropriate standards of your country if installing overseas.
• Install an appropriate fused spur or isolation switch to isolate the mains supply.
• Isolate the mains supply before carrying out any maintenance work on the system.
• Avoid water ingress into the module.
• If an electric lock is to be tted to the system it is important to power the lock release from a dedicated fused supply to avoid
a short in the device cabling. Remember to power down the lock release when tting it.
• All intercom and access control cables must be routed separately from the mains.
LOCK RELEASE WIRING AND BACK EMF PROTECTION
When tting an electric lock release back EMF protection will be required. If tting an AC lock release then a 100nF ceramic disc
capacitor should be tted across the terminals of the lock, shown in Fig.5. If tting a DC lock release (fail secure or fail safe) then a
1N4002 diode should be tted across the terminals on the lock, shown in Fig.6.
12V AC
LOCK RELEASE
100nF
CAP
A varistor (MOV) can be tted
to either an AC or DC lock
across the lock terminals and
is not polarity conscious
DIODE
1N4002
12V DC
LOCK RELEASE
Fig. 5 Fig. 6
If a 100nF ceramic disc capacitor or a 1N4002 diode are not available then a 14 - 20V MOV (metal oxide varistor) can be tted across
the lock terminals instead (refer to Fig.5 above) and can be tted on both an AC and DC lock. A lock release connection example
can also be seen in Fig.7 wiring diagram on page 7.
TECHNICAL SPECIFICATION
Input voltage: 12V - 14Vdc power input (+/-10%)
Current (standby): 6.4mA (max.)
Curent (during operation): 41mA (max.)
PTE input open voltage: 5Vdc
PTE input closed voltage: 0V
Databus voltage: 7.5V - 8Vdc (L/-)
Maximum cable resistance: 7Ω
Relay contacts: CO, NO and NC (10A @ 24Vdc, 12A @ 120Vac, 5A @ 250Vac)
Programming: Programming via 8 way dip-switches: device ID setup ID.1 - ID.16, relay activation time setup
(1, 2, 4, 6, 8, 10, 12 or 15 seconds), operating mode local mode (default) or main mode (to
operate with 2206N bus exchange devices).
Enclosure material: ABS plastic (white)
Enclosure dimensions (mm): 66 (W) x 60 (H) x 22 (D)
Mounting: Surface, direct wall xing