Vitocrossal 200, CM2 400, 500, 620 and 620 TX Service
Safety Instructions
General Information
Checking the high limit safety cut-out setting
The high limit safety cut-out is preset to 210° F (99° C).
If this temperature needs to be changed, this can only be
done by changing the coding card.
See the control section of the Installation
Instructions.
If you smell flue gas
■Shut down the heating system.
■Ventilate boiler room.
■Close all doors in the living space
Working on the system
■Where gas is used as the fuel, close the main gas
shut-off valve and safeguard it against unintentional
reopening
■Isolate the system from the power supply (e.g. at the
separate fuse or a main switch) and check that it is
de-energized
■Safeguard the system against reconnection.
Target group
These instructions are intended exclusively for qualified
contractors.
■Work on gas installations must only be carried out
by a licensed professional heating contractor.
■Work on electrical equipment must only be carried
out by a qualified electrician.
■The system must be commissioned by the system
installer or a qualified person authorised by the installer.
■This appliance has not been designed to be operated
by individuals other than those qualified and trained.
Regulations
Observe the following when working on this system:
■Statutory regulations regarding the prevention of accidents
■Statutory regulations regarding environmental protection
■Codes of practice of the relevant trade associations.
If you smell gas
■Do not smoke. Prevent naked flames and sparks. Do not
press any switches for lights or electrical appliances.
■Close the gas shut-off valve.
■Open windows and doors.
■Remove all people from the danger zone.
■Notify your gas or electricity supply utility from outside
the building.
■Shut off the electricity supply to the building from a
safe place (outside the building).
WARNING
Escaping gas can lead to explosions which may result
in serious injury.
WARNING
Flue gas can lead to life threatening poisoning.
Repair work
Note: Repairing components that fulfil a safety function
can compromise the safe operation of your system.
Replace faulty components only with original
Viessmann spare parts.
Auxiliary components, spare and wearing parts
Note: Spare and wearing parts that have not been tested
together with the system can compromise its function.
Installing non-authorised components and making
non-approved modifications or conversions can
compromise safety and may invalidate our warranty.
For replacements, use only original spare parts
supplied or approved by Viessmann.
Note: Electronic assemblies can be damaged by
electrostatic discharges. Before beginning work,
touch grounded objects, such as heating or water
pipes, to discharge static loads.
CSD-1 Field Testing of High Limit Switches for Vitocrossal 200
CM2 boilers (models 400 to 620) – where required by law.
VIESSMANN IS NOT RESPONSIBLE FOR ANY DAMAGES
THAT THE FOLLOWING TEST PROCEDURE MAY RESULT
IN BY OVERHEATING THE SYSTEM.
The Vitocrossal 200 boilers are equipped with 2 RTD
temperature sensors that when activated on temperature
rise (high fixed limit of 210° F (99° C) disable the burner
to operate.
The fixed high limit, when tripped, produces a fault that
will require manual reset of the boiler control.
Fixed High Limit test procedure:
1 Install a jumper switch in GW5B control on terminals 2-3
of 146 plug. (this will simulate a call for heat)- for boilers
used with Vitotronic 300-K cascade control, simply use
the emission test switch on GW5B control (top left corner
switch with ladder sign)
2 Set coding address 9B (external heat demand) to a max.
of 241°F (116°C), as an example, higher than fixed
high limit temperature setting (if using emission test
switch, skip this step)
3 As described in the table on page 9, adjust item #4 “Max.
boiler water temperature” under menu 6 of the burner
control (GC310) to a max. setting of 243°F (117°C), as
an example, higher than fixed high limit temperature setting
[factory default setting is 203°F (95°C)].
4 Initiate a call for heat with the jumper switch on plug 146
(as in item 1 above) or press/activate emission test switch
if applicable, the burner will start.
5 Gradually and slowly throttle the water flow to the boiler
6 Observe temperature on the GW5B control
7 Once the temperature reached the fixed high limit setting,
burner control will have a hard lock out with F F2 fault
displayed. Burner fan stays on for 10 min. The fault can
only be manually reset once the water temperature in the
boiler drops.
8 Reset to original settings as needed (item #4 under
menu 6 and external heat demand under address 9B).