Vive TP-N-801 User manual

Installation Manual
Thermostat Application Guide
Description
Gas or Oil Heat
Electric Furnace
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (With Aux. or Emergency Heat)
Multi-Stage Systems
Heat Only Systems
Cool Only Systems
Millivolt
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Power Type
Battery Power
Hardwire (Common Wire)
Hardwire (Common Wire) with
Battery Backup
Table of Contents
Installation Tips
Thermostat Quick Reference
Wiring
Wiring Diagrams
Technician Setup
Specications
Page
A trained, experienced
technician must install this
product.
Carefully read these
instructions. You could damage
this product or cause a
hazardous condition if you fail
to follow these instructions.
Una version en español de este
manual se puede descargar en
la pagina web de la compañia.
Rev. 1821
Mount Thermostat
Align the 4 tabs on the subbase with
corresponding slots on the back of the
thermostat, then push gently until the
thermostat snaps in place.
Battery Installation
Battery installation is optional if thermostat is
hardwired (R and C terminal connected to 24V
power).
Important:
High quality alkaline batteries are recommended.
Rechargeable batteries or low quality batteries
do not guarantee a 1-year life span.
Insert 2 AA
Alkaline batteries
(included). High
quality alkaline
batteries are
recommended.
Installation Tips
4
5
9-12
12
2-3
Installation Tips Thermostat Quick Reference
Getting to know your thermostat
Fan Button
System Button
Setpoint Buttons
LCD
The low battery indicator is displayed when the
AA battery power is low. If the user fails to
replace the battery within 21 days, the screen
will only show the low battery indicator but
maintain all functionality. If the user fails to
replace the batteries after an additional 21 days
(days 22-42 since rst“low battery”display) the
setpoints will change to 55˚F (Heating) and 85˚F
(Cooling). If the user adjusts the setpoint away
from either of these, it will hold for 4 hours
then return to either 55˚F or 85˚F. After day 63
the batteries must be replaced immediately to
avoid freezing or overheating because the
thermostat will shut the unit o until the
batteries are changed.
Important
Removing The Private
Label Badge
Gently slide a screwdriver into the
bottom edge of the badge. Gently turn
the screwdriver counter clockwise. The
badge is held on by a magnet in the well
of the battery door. The badge should pry
o easily. DO NOT USE FORCE.
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the
company website to learn more about our free private label program.
Magnet in door
Use the bevel on lower ridge
Subbase Installation
The thermostat should be installed approximately 4 to 5 feet above the
oor. Select an area with average temperature and good air circulation.
• Close to hot or cold air ducts
• That are in direct sunlight
• With an outside wall behind
the thermostat
• In areas that do not require
conditioning
• Where there are dead spots
or drafts
(in corners or behind doors)
• Where there might be
concealed chimneys or
pipes
Wall Locations
Vertical Mount
Horizontal Mount
For vertical mount put one screw on the top
and one screw on the bottom.
For horizontal mount put one screw on the
left and one screw on the right.
All of our products are mercury free.
However, if the product you are
replacing contains mercury, dispose of
it properly. Your local waste
management authority can give you
instructions on recycling and proper
disposal.
Pick an installation location that is easy for
the user to access. The temperature of the
location should be representative of the
building.
Installation Tip
Mercury Notice
Do not install
thermostat in locations:
Failure to disconnect the power before
beginning to install this product can
cause electrical shock or equipment
damage.
Installation Tip:
Electrical Hazard
U.S. Registered Trademark. Patents pending
Copyright 2018 All Rights Reserved.
Displays the
user selectable
setpoint
temperature.
Low Battery Indicator:
Replace
batteries when
indicator is shown.
Keypad
Lockout
Indicator
6-8
Indicates the
current room
temperature
Fan and System
Options
These system
operation
indicators will
display when
COOL, HEAT
or FAN is ON.
NOTE: The
compressor delay
feature is active
if these icons are
ashing. The
compressor will
not turn on until
the 5 minute
delay has elapsed.
Battery Cover
Vive Comfort
Toll Free : 888-776-1427
Web: www.vivecomfort.com
Hours of Operation: M-F 9AM - 6PM Eastern
TP-N-801
Temperature
FCOOL ON
O
Auto Cool
P.O. Box 3377
Springeld, MO 65804

Technician Setup
Tech Setup Steps Adjustment Options Default
LCDWill Show
Power supply
Factory-installed jumper. Remove only when installing on
2-transformer systems.
Typical 1H/1C System: 1Transformer
Wiring Diagrams
Use either O or B terminals for changeover valve.
Use a small piece of wire (not supplied) to connect W andY terminals.
Typical 1H/1C Heat Pump System
1. To enter Tech Setup Menu, press and hold and together for 3 seconds.
2. Use or to select desired setting for each option.
3. Use the System and Fan buttons to move through the steps.
4. To exit Tech Setup press and hold and together for 3 seconds.
Wiring
Technician Setup
Wiring Tips
RH & RC Terminals
For single transformer systems, leave the
jumper wire in place between RH and RC.
Remove jumper wire for two transformer
systems.
Heat Pump Systems
If wiring to a heat pump, use a small
piece of wire (not supplied) to connect
terminals W and Y.
(With NO AUX or
Emergency Heat)
C Terminal
The C (common wire) terminal does
not have to be connected when the
thermostat is powered by batteries.
Wire Specications
Use shielded or non-shielded
18-22 gauge thermostat wire.
Caution:
Electrical Hazard
All components of the control
system and the thermostat
installation must conform to Class
II circuits per the NEC Code.
Warning:
Installation Tip: Do not overtighten terminal block screws, as this
can damage the terminal block. A damaged terminal block can
keep the thermostat from tting on the subbase correctly or cause
system operation issues. Max Torque = 6in-lbs.
Wiring
If you are replacing a thermostat,
make note of the terminal
connections on the thermostat
that is being replaced. In some
cases the wiring connections will
not be color coded. For example,
the green wire may not be
connected to the Gterminal.
Loosen the terminal block
screws. Insert wires then
retighten terminal block screws.
Place nonammable insulation
into wall opening to prevent
drafts.
1.
2.
3.
Failure to disconnect the power
before beginning to install this
product can cause electrical
shock or equipment damage.
Terminal Designations
C
OHeat pump changeover valve
energized in cooling
Heat pump changeover valve
energized in heating
WHeat relay
RH Transformer power for heating
RC Transformer power for cooling
GFan relay
YCompressor relay
B
Common wire from secondary side of
cooling system transformer
Set fan operation switch to electric.
Optional 24 VAC common connection when thermostat is used in battery power mode.
RC
Y
C
W
G
RH
COMPRESSOR
RELAY
HEAT RELAY
FAN RELAY
C
R
L2
L1 HOT
RC
Y
C
W
G
RH
COMPRESSOR
RELAY
FAN RELAY
C
R
L2
L1 HOT
COOL CHANGE
OVER VALVE
HEAT CHANGE
OVER VALVE
O
B
This feature allows the installer to
select the minimum run time for
the compressor. For example: a
setting of 4 will force the
compressor to run for at least 4
minutes every time the
compressor turns on, regardless of
the room temperature.
You can select the minimum
compressor run time from“o”,
“3”,“4”, or “5”minutes. If 3,4,
or 5 is selected, the compressor
will run for at least the selected
time before turning o.
0
This feature allows the installer
to change the calibration of the
room temperature display. For
example, if the thermostat reads
70˚ degrees and you would like it
to read 72˚ then select +2.
Room
Temperature
Calibration
You can adjust the room
temperature display to read
4˚above or below the factory
calibrated reading.
Minimum
Compressor
On Time
0.5
The swing setting often called
“cycle rate”,“dierential”or“
anticipation”is adjustable. A
smaller swing setting will cause
more frequent cycles and a
larger swing setting will cause
fewer cycles.
Cooling
Swing
The cooling swing setting is
adjustable from 0.2˚ to 2˚. For
example: A swing setting of
0.5˚ will turn the cooling on at
approximately 0.5˚ above the
setpoint and turn the cooling o
at approximately 0.5˚ below the
setpoint.
0FF
This feature will ash“a reminder”
in the display after the elapsed run
time to remind the user to change
the lter. A setting of “OFF”will
disable this feature.
Filter Change
Reminder
You can adjust the lter change
reminder from OFF to 2000
hours of runtime in 50 hour
increments.
F1
OFF
SE
0
The swing setting often called
“cycle rate”,“dierential”or
“anticipation”is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
The heating swing setting is
adjustable from 0.2˚ to 2˚. For
example: A swing setting of
0.5˚ will turn the heating on at
approximately 0.5˚ below the
setpoint and turn the heating o
at approximately 0.5˚ above the
setpoint.
Heating
Swing 0.4
The compressor short cycle delay
protects the compressor from
short cycling. This feature will not
allow the compressor to be turned
on for 5 minutes after it was last
turned o.
Selecting “ON”will not allow
the compressor to be turned on
for 5 minutes after the last time
the compressor was switched
o. Select“OFF”to remove this
delay.
Compressor
Short Cycle
Delay
OFF
A0FF
OF
CO
0.4
0.5
Tech Setup Steps Adjustment Options Default
LCDWill Show
0N
Keypad lockout allows you to
congure the thermostat so that
none or some of the keys do not
function.
Select OF, PA or FU. OF = (o)
Keypad Lockout will be disabled.
PA= Partial keypad lockout,
locks all the keys except the
or keys. FU= Full
Keypad lockout, locks out all
the keys. Note: Keypad lockout
instructions are at the end of
tech setup.
Keypad
Lockout OFF
OF
KEY LOCK
This feature allows you to set a
maximum heat setpoint value.
The setpoint temperature cannot
be raised above this valve.
Use the or key to select
the maximum heat setpoint.
Range 44˚F - 90˚F
Heating
Temperature
Setpoint
Limit
90˚
HE
HEAT LIMIT
90
This feature allows you to set a
minimum cool setpoint value.
The setpoint temperature cannot
be lowered below this value.
Use the or key to select
the minimum cool setpoint.
Range 44˚F - 90˚F
Cooling
Temperature
Setpoint
Limit
44˚
CO
COOL LIMIT
44
Select F for Fahrenheit read out
or select C for Celsius read out.
˚F for Fahrenheit
˚C for Celsius
F˚ or C˚ F˚
74
F
Select GAS for systems that
control the fan during a call for
heat.
Select ELEC to have the
thermostat control the fan
during a call for heat.
Gas
or
Elec
Fan
Operation GAS
ELEC
COOL SWING
HEAT SWING

Wiring Diagrams
Typical Heat-Only System
Typical Cool-Only System
Reminder Note
Once a reminder has been turned on and set, the elapsed time can be
checked by navigating to it’s Technican Setup step with a press of the
SYSTEM BUTTON, the elapsed time will be displayed. It can also be reset at
the time by a press and hold of the FAN BUTTON for 3 seconds. Resetting
an expired reminder can be done without entering tech setup, by a press
and hold of the FAN BUTTON for 3 seconds.
Technician Setup
Wiring Diagrams
RC
Y
C
W
G
RH
HEAT RELAY
FAN RELAY
C
R
L2
L1 HOT
Typical Heat-Only SystemWith Fan
REMOVE JUMPER
Typical 1H/1C System: 2Transformer
L2
L2
L1 HOT
L2
L2
L1 HOT
L2
C
R
C
R
RC
Y
C
W
G
RH
COMPRESSOR
RELAY
HEAT RELAY
FAN RELAY
RC
Y
C
W
G
RH
HEAT RELAY
C
R
L2
L1 HOT
L2
RC
Y
C
W
G
RH
COMPRESSOR
RELAY
FAN RELAY
C
R
L2L2
L1 HOT
The display light can be cong-
ured to come on when any key
is pressed or only when the light
key is pressed.
OFF congures display light to
come on only with the light key,
which will save battery power.
On congures the display light
to come on when any key is
pressed.
Display
Light ON
dL
Tech Setup Steps Adjustment Options Default
LCDWill Show
Allows you to put your phone
number in the display. Selecting
“ON”will enable this feature.
“OFF”will disable this feature.
If selected on, you will see the
input screen after pressing
SYSTEM key. Use the key
to move from one character to
another. Use the key to
change the blinking character.
Press SYSTEM key when nished.
Contractor
Call Number OFF
OFF CALL
When any key is pressed ab
audible beep will sound.There is
an ON or an OFF.
If ON is selected the beep will
sound.
If OFF is selected, there is not
sound.
Beep ON
b
ON
You can congure the system
switch for the particular
application:
Heat - O - Cool,
Heat - O,
Cool - O,
Heat - O - Cool-Auto
Auto - Autochangeover
Use the or key until the
desired application is ashing.
System
Switch
HEAT
OFF
COOL
HEAT
OFF
COOL
This will remind the user to
change the humidity pad.
Use the or key to select
OFF, 600, 1000, 1500, 2000.
These represent hours of heat
operation.
Humidity
Pad
Reminder
OFF
Will remind the user to change
the UV light bulb. Use the or key to select
OFF 1 YEAR, 2 YEAR.
UV Lamp
Reminder OFF
OFF
HUM PAD
OFF OFF
UV LAMP
OFF
Will remind the user to change
the PHI Cell after 25,000 hrs. Use the or key to select
OFF, or 250. (Stands for 25000
hours).
IAQ Cell
Reminder OFF
IA9 CELL
OFF
OF
Technician Setup & Specications
Specications
The display range of temperature ... 41˚F to 95˚F (5˚C to 35˚C)
The control range of temperature.... 44˚F to 90˚F (7˚C to 32˚C)
Load rating.................................................1 amp per terminal, 1.5 amp
maximum all terminals combined
Swing (cycle rate or dierential) ...... Heating is adjustable from 0.2˚ to 2.0˚
Cooling is adjustable from 0.2˚ to 2.0˚
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz
for hardwire
Battery power from 2 AA Alkaline
batteries
Operating ambient ............................... 32˚F to +105˚F (0˚C to +41˚C)
Operating humidity .............................. 90% non-condensing maximum
Dimensions of thermostat ................. 4.7”W x 4.4”H x 1”D
A Note About Keypad Lockout:
The function of activating your lockout choice takes place after you have
exited tech setup to lock or unlock the keypad hold down the FAN and
SYSTEM for 3 seconds.
Other manuals for TP-N-801
2
Table of contents
Other Vive Thermostat manuals