1
1. Einleitung
•Die deutsche Fassung der
Montageanleitung ist das Original.
•Alle Sicherheitstexte und Hinweise
sind kursiv gesetzt.
•Bewahren Sie diese
Montageanleitung auf, sie ist Teil
der Dokumentation der
Kälteanlage.
•Die jeweils aktuelle Fassung dieser
Montageanleitung kann auf
unserer Website
http://inst.walterroller.de
heruntergeladen werden.
Introduction
•This mounting instruction ia a
translation of the german original
Montageanleitung
•All safety information and advice is
printed in italics
•Keep these instructions. They are
part of the refrigeration plant.
•You can download the latest
revision of these mounting
instructions on our website
http://inst.walterroller.com.
Introducción
•Estas Instrucciones de Montaje
han sido traducidas del original en
alemán Montageanleitung.
•Las indicaciones e instrucciones de
seguridad se han escrito en letra
cursiva.
•Conserve estas instrucciones, son
parte de la información técnica de
la instalación frigorífica.
•Puede Vd. descargar la última
edición de estas instrucciones de
montaje en nuestra página web:
http://inst.walterroller.com.
2. Normen / Richtlinien
•Die Normenreihe EN 378
"Kälteanlagen und Wärmepumpen
- Sicherheitstechnische und
umweltrelevante Anforderungen"
dokumentiert die Anforderungen,
die der Errichter sowie der
Betreiber der Kälteanlage erfüllen
müssen.
Insbesondere bei A2L/A3
Kälteanlagen sind folgende Absätze
zu beachten:
oEN 378-1, Absatz 6, maximal
zulässige Kältemittel-Füllmenge
oEN 378-3, Absatz 7.3,
elektrische Betriebsmittel in
Maschinenräumen für
Kälteanlagen mit brennbaren
Kältemitteln
oEN 378-3, Absatz 9.3.2,
Kältemitteldetektoren für
Kältemittel der Klassen A2, A2L,
B2L (außer R-717), B2, A3 und
B3
Die Abnahme erfolgt bauseitig.
•Die Luftkühler sind nach EN 378-2
Absatz 5.2.1 eine Rohrschlange
mit Luft als Sekundärfluid, und
entspricht den Anforderungen von
EN 14276-2 mit Punkt 5.2.2.2 der
EN 378.
•Je nach Art der Errichtung der
Kälteanlage ergeben sich
unterschiedliche Anforderungen an
die elektrische Absicherung. Eine
der folgenden Normen muss zur
Bewertung der
sicherheitstechnischen
Anforderung herangezogen
werden:
oEN 60335-2-40,
oEN 60335-2-89
ooder EN 60204-1
Standards / Directives
•The standard series EN 378
"Refrigerating systems and heat
pumps- Safety and environmental
requirements" documents the
requirements, which the builder
and the operator of the
refrigeration plant have to comply.
For A2L/A3 refrigeration systems in
particular, the following paragraphs
must be observed:
oEN 378-1, paragraph 6,
Maximum permissible
refrigerant charge quantity
oEN 378-3, paragraph 7.3,
Electrical equipment in
machinery spaces for
refrigeration systems with
flammable refrigerants
oEN 378-3, paragraph 9.3.2,
Refrigerant detectors for
refrigerants of classes A2, A2L,
B2L (except R-717), B2, A3
and B3
Acceptance is carried out by the
customer.
•Unit air coolers are coils with air as
secondary fluid according to EN
378-2 paragraph 5.2.1. It fulfills the
requirements of EN 14276-2 and
paragraph. 5.2.2.2 of EN 378.
•Depending on the type of
refrigeration system there are
different requirements for electric
safety. One of the following
standards has to be obeyed, when
designing and installing the plant:
oEN 60335-2-40,
oEN 60335-2-89
oor EN 60204-1.
Normas / Directivas
•La Normativa EN 378 "sistemas de
refrigeración y bombas de calor-
seguridad y requisitos
ambientales" documenta los
requisitos que deben cumplir el
fabricante y el técnico de la
instalación frigorífica.
Para los sistemas de refrigeración
A2L/A3 en particular, se deben
observar los siguientes párrafos:
oEN 378-1, párrafo 6, Cantidad
máxima de carga de refrigerante
permitida
oEN 378-3, párrafo 7.3, Equipo
eléctrico en espacios de
máquinas para sistemas de
refrigeración con refrigerantes
inflamables
oEN 378-3, párrafo 9.3.2,
Detectores de refrigerantes para
refrigerantes de las clases A2,
A2L, B2L (excepto R-717), B2,
A3 y B3
La aceptación se realiza in situ.
•Los evaporadores son una batería
frigorífica que utiliza el aire como
fluido secundario, según la norma
EN 378-2 párrafo 5.2.1. Cumple
con los requisitos de la EN 14276-
2 y el párrafo. 5.2.2.2 de la EN
378.
•Dependiendo del tipo de sistema
de refrigeración existen diferentes
Normas de seguridad eléctrica.
Una de las siguientes Normas
tiene que ser de obligado
cumplimiento, en el diseño e
instalación de la planta:
oEN 60335-2-40,
oEN 60335-2-89
oo la EN 60204-1.