
SECTION
II
INITIAL START UP
1. NOTB: Readtheapplicablesequenceofburner/primary
gas
control
operation,
gqspressure
switches,
etc. in Section3 Operation
and
Tr
oubI
es
hooting befo
r
e
pro
c
eeding.
2.Lay outcombustion
testequipment,manometers,stopwatch,
DC micro-
ampmeter,
andother
miscellaneoustoolsasneeded.
3.Adjust
the
primaryairshuttersetting
per
thedimensionsshown
in the
chartbelow. Removeblanking
platefrom thesideof theburner
IF thefiring
rateisover650,000(190.5kW)
BTU'son
LP ONLY. Seechart
below.
Note: Air Shutter
Opening
Dimensionsand
Gas
ManifoldPressuresareapproximate
andmustbe
properly
adjustedwithcalibratedemissions
equipment.
FIGURE
13
4.NOTE: Initial activation
oftheburnershouldbegin
withchecking
the
function of theautomatic
controlsbymeansof a "dry ntn" before
gasis
supplied
to themainburnernozzle
- througha complete
mainburner
firing
cycleanda complete
checkof all automaticsqfety
controlswith thetest
fi,ring valvein theclosed
positionthen
throughanactivated
firing cycle.
5.Temporarily
removethecovers
from
the
High andLow gas
pressure
switchesand
set
theswitchesusingthedials.Thehighgaspressure
switch
should
besetatthe
highest
"w.c.setting,
as
an
initialstarting
point. Thelow
gaspressure
switchshouldbesetat
thelowest
"'w.c.
setting,
as
astarting
point. Push
the
manualresetbuttonsonthe
gas
pressure
switches.
Note:Thesesettingsmustbere-adjustedafter
theburner
isignited.
',: l;
.: '.-l'
:iir
,.il: I
:..,r
-
1
,'
-' i;Y:]t1o';,!t
t:;t
BTU/hr
Input Air shutter Manifold
AP o'w.c. Air shutter Manifold
AP t'w.c.
Opening BlankPlatr Onenins BlankPlatr
+25,000(24.6kW 3/8"(9.53mm) yes \.7(921.6Pa5116"(l.94mm) yes ).8(946.5Pa
150,000(3l.9kw l/2"(l2.7mm) yes \,5(87I.8Pa l12"(12.7mm\ yes t.5(871.SPa
500,000(46.5kW13116"(20.64mm yes ].5(871.8Pa13l16"Q0.64mm yes t.5(811.SPa
550,000(6l.2kw l-l18"(28.58mm yes ].5(871.8Pa l"(25.4mm\ yes 1.5(81I
.8Pal
500,000(75.8kW l-3/8"04.92mm yes \.s(871.SPal-112"(38.1mm) yes 3.5(871.8Pal
550.000(l
90.5kwl-314"(l9.05mrn removed ].5(871.8Pal-314"(44.45mm yes 1.5(871.8Pa
/00.000(205.2kw
l-7/8"(47.63mm) removed ].5(871.8Pa2-118"(53.97mm) yes 1.5(871.8Pa
l5
SECTION
II
INITIAL START UP
1. NOTE:
Read
the applicable sequence
of
burner/primary gas control
operation, gas pressure switches,
etc.
in
Section 3Operation and
Troubleshooting beforeproceeding.
2.
Layout
combustion test equipment, manometers, stopwatch, DC micro-
amp meter, and
other
miscellaneous tools as needed.
3. Adjust the primary air shutter setting per the dimensions shown
in
the
chart below. Remove blankingplatefrom the side
of
the burner
IF
thefiring
rate is over 650,OOO(l90.5kW) BTU's on
LP
ONLY. See chart below.
Air shutter
olank Plate 0
3/8"(9.53mm) es 3.7(921.6Pa)
5/l6"(7.94mm)
3.8(946.5Pa)
50,OOO(131.9kW)
l/2"(12.7mm)
yes 3.5(871.8Pa)
l/2"(12.7mm)
3.5(871.8Pa)
500,OOO(
l46.5kW)
l3/16"(20.64mm)
yes 3.5(871.8Pa) 13/16"(20.64mm) yes 3.5(871.8Pa)
550,OOO(
16]
.2kW)
1-1/8"(28.58mm)
yes 3.5(871.8Pa) I
"(25.4mm)
es 3.5(871.8Pa)
600,OOO(l75.8kW) 1-3/8"(34.92mm) es 3.5(871.8Pa) 1-1/2"(38.1mm) yes 3.5(871.8Pa)
650,OOO(l90.5kW) 1-3/4"(
19.05mm)
removed 3.5(871.8Pa) 1-3/4"(
44.45mm)
es 3.5(871.8Pa)
700,OOO(205.2kW) 1-7/8"(
47.63mm)
removed 3.5(871.8Pa) 2-1/8"(53.97mm) yes 3.5(871.8Pa)
Note:
Air
Shutter
Opening
Dimensions and Gas Manifold Pressures are approximate
and
must
be
properly adjusted with calibrated emissions equipment.
FIGURE
13
4. NOTE: Initial activation
of
the burner should begin with checking the
function
of
the automatic controls by means
of
a"dry
run"
before gas is
supplied to the main burner nozzle -through acomplete main burnerfiring
cycle and acomplete check
of
all automatic safety controls with the test
firing valve
in
the closedposition then through
an
activatedfiring cycle.
5. Temporarily remove the covers from the High and
Low
gas pressure
switches and set the switches using the dials.
The
high gas pressure switch
should be set at the highest "w.c. setting, as an initial starting point. The low
gas pressure switch should be set at the lowest "w.c. setting, as astarting
point. Push the manual reset buttons on the gas pressure switches.
Note: These settings must be re-adjusted after the burner
is
ignited.
15