Westell PROACT Series User manual

Equipment Issue B
030-101527 Rev. B, July 2004
Section 311-580-20B
0407IBRB
Page 1 of 26
Copyright 2004 Westell, Inc. All rights reserved. Printed in the United States of America.
*CLEI is a trademark of Telcordia Technologies. 200 MECHANICSin a registered trademark of
and PROACTis a trademark of Westell, Inc.
DS1 Network Interface Unit with Performance Monitoring
Model 3115-80 Issue B
Part of the Westell PROACTtFamily
CLEI* Code: T1S1ABTAAA
CONTENTS PAGE #
1. GENERAL 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. APPLICATIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. TRANSMISSION FEATURES AND OPTIONS 3. . . . .
4. LOOPBACK FEATURES AND OPTIONS 5. . . . . . . . .
5. SECTIONALIZATION ALARM FEATURES 7. . . . . . .
6. PERFORMANCE MONITORING & REPORTING 8.
7. HARDWARE OPTIONS & FEATURES 11. . . . . . . . . .
8. INSTALLATION 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9. SET-UP AND OPERATION 13. . . . . . . . . . . . . . . . . . . .
10. TESTING & TROUBLESHOOTING 21. . . . . . . . . . . . .
11. CUSTOMER & TECHNICAL SERVICES 22. . . . . . . .
12. WARRANTY & REPAIRS 22. . . . . . . . . . . . . . . . . . . . . .
13. SPECIFICATIONS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. GENERAL
1.1 Document Purpose
This document describes the Westell 3115-80 DS1 Network In-
terface Unit (NIU) with Performance Monitoring, shown in
Figure 1.
1.2 Document Status
Whenever this practice is updated, the reason will be stated in
this paragraph. The Revision B practice adds Paragraph 6.11.3,
and updates Paragraphs 9.2.4.4 through 9.2.4.7, Paragraph
9.2.9, Table 7, Table 11, Table 12, Figure 13, Figure 15,
Figure 16, Figure 17, Figure 25 and Figure 27. The Issue B
equipment provides the following improvements:
Manufacturability
ESF & B8ZS LEDs added
SPRM generation added
XMT LBO with Auto Binder added
RCV LBO added
RCV (FAC-to-CPE) regeneration added
Test pattern generation added
Craft accessible Log Reports added
Alarm thresholds added
Application modes combined
Figure 1. 3115-80 NIU with Performance Monitoring
B90-311580
126270
NIU-PM
PWR
ESF
FLOS
CLOS
LB
C
P
E
M
O
N
TP1
TP2
MAN
LB
F
A
C
M
O
N
B8ZS
- NOTE -
Hereafter, the 3115-80 DS1 Network Interface Unit with
Performance Monitoring also may be referred to as the NIU,"
the unit," or 3115-80."
1.3 Product Purpose and Description
The Westell 3115-80 Issue B T1 Network Interface Unit with
real-time Performance Monitoring serves as an interface be-
tween a T1 metallic span, or a customer premises-based fiber
multiplexer, and the intra-building Customer Premises Equip-
ment (CPE). The 3115-80 Issue B is a member of the Westell
PROACTfamily of T1 NIUs that provide standard mainte-
nance loopback plus collection and reporting of DS1
performance statistics. These performance monitoring capabili-
ties allow service providers to PROACTively" respond to facility

Section 311-580-20B 030-101527 Rev. B
20407IBRB
performance degradation, thereby improving the availability of
Hi-Cap T1 circuits.
1.4 Product Mounting
The 3115-80 is a 200 MECHANICSNIU and makes electrical
connections to the Facility and CPE sides of the circuit through
a 56-pin card-edge connector of a 200- or 400-mechanics type
mounting, using industry-standard pin assignments. The mount-
ing assembly is usually mounted on an equipment backboard at
the customer location, after the building entrance terminal and
primary protection. Westell offers a wide range of single and
multiple slot mountings available in both backboard (wall) and
rack mount versions for NIUs. In some applications it may be de-
sirable to situate the NIU in outside plant cabinets or enclosures.
The NIU is fully qualified for operating over the temperature
range of -40 to +65°C (temperature hardened).
1.5 Product Features
The 3115-80 offers the following features.
Full-featured T1 NIU loopback device plus detailed T1 per-
formance monitoring and reporting at the customer facility
interface
Loopback activation and deactivation using inband (un-
framed or SF/ESF framed) or ESF Data Link codes
Addressed loopback control with 16-bit pattern for TER
(T1 Extension Repeater) applications
CPE-to-Facility LBO provisionable from 0 to 22.5dB in 7.5
dB increments
Alternate self-aligning CPE-to-Facility LBO that automati-
cally protects the network from a mis-optioned customer
LBO
Enhanced sectionalization capabilities via AIS-CI and
RAI-CI alarm signals as defined by T1.403-1998
Derives and maintains DS1 performance statistics inde-
pendently for each direction of transmission
Supports both 30-day stored as well as real-time perfor-
mance reporting modes
Flexible DS1 performance reporting options:
Local, non-intrusive access to PM parameters via a
front-panel local craft interface port
Remote, intrusive access during loopback to PM pa-
rameters via TL1 commands and responses in the ESF
Data Link
Remote, non-intrusive access to PM parameters via
TL1 commands and responses in the Data Link, by use
of a Test Head, without affecting customer payload
Remote, non-intrusive real-time reporting of PM pa-
rameters via 1-second NPRM or SPRM reports in the
Data Link per ANSI T1.403-1998
On board test pattern generator
Notepad craft screen for documenting information about
the circuit
User-configurable alarm threshold craft screen
Integral real-time clock provides time stamping of all per-
formance information
Selectable powering option (via jumper option) for span or
local power
Front-panel test points for measuring span current
Monitor-type bantam jacks on FAC IN and FAC OUT ports
for transmission path monitoring
Front-panel craft interface port (serial RS-232, VT-100) for
local, non-intrusive PM extraction, unit set up, test code
generation and circuit maintenance
Remote provisioning and query of options (TL1 non-intru-
sive or 16-bit intrusive)
Front-panel LEDs indicate status of:
PWR (Power)
LB (Loopback)
FLOS (Facility Signal Status)
CLOS (CPE Signal Status)
ESF (ESF Framing detected from the facility)
B8ZS (B8ZS detected from the facility)
Internal per-circuit local power fusing
Compliant with: UL 60950, CAN/CSA C22.2 No. 60950-00,
and NEBS
Operates over the -40 to +65C temperature range allow-
ing deployment in outside plant (OSP) enclosures and
cabinets; Temperature Hardened
2. APPLICATIONS
The NIU can be used to terminate a T1 metallic span facility or
as an adjunct to a lightwave multiplexer when DS1 circuits are
extended to a customer location on fiber facilities. The CPE con-
nections are intra-building.
The unit is situated at the customer’s premises and functions as
a maintenance interface between the T1 metallic span or fiber
multiplexer facility and the CPE. In addition to conventional
NIU functions such as loopback, the NIU collects performance
data for both directions of the facility, stores the information and
reports it to the remote test center either on demand via TL1
commands or on a real-time basis via NPRMs. This perfor-
mance information can also be locally accessed via the
front-panel RS-232 craft interface port.
- NOTE -
Real-time Performance Monitoring retrieval will initially require
that the test head be updated to monitor the Facility Data Link
non-intrusively for performance information.

Section 311-580-20B
030-101527 Rev. B
3
0407IBRB
2.1 Transmission Design
2.1.1 T1 Span - Copper Applications
2.1.1.1 Normal T1 span design allows from 0 to 15dB of loss
from the last repeater in the span to the customer interface and
a maximum loss of 7.5dB for inside wiring to the CPE (see
Figure 2). This represents a total loss of 22.5dB. This mode pro-
vides a receive transmission path that can be configured to pass
the signal from the span to the CPE with either no net regenera-
tion or with the optional regenerator to 0dB DSX. The optional
regenerator in this path can be used in applications where the
maximum loss of 22.5dB to the CPE cannot be achieved other-
wise, or in special situations where the customer requires a 0dB
DSX handoff.
2.1.1.2 The unit’s transmit path from the CPE to the Network
provides a selectable 0 to 22.5 dB LBO as well as an automatic,
self-aligning LBO (Line Build Out) circuit to meet route junc-
tion and end section design requirements in T1 span
applications.
2.1.2 T1 Fiber Applications
When T1 service to a customer is provided via fiber, the unit can
be configured to serve as a maintenance interface between the
fiber mux and the CPE. The unit can be located up to 220 feet
from the mux. See Figure 3. In this mode, the unit can be provi-
sioned for CPE-to-FAC regeneration which will regenerate
CPE input levels that have been attenuated from 0 to 30dB to a
normal 0dB DSX. This is useful due to the fact that the DS1 low-
speed tributary ports of most multiplexers are designed to
accommodate input levels that have been attenuated no more
than 3dB from 0dB DSX. This feature allows for greater section
losses to be accommodated. The CPE-to-FAC regeneration fea-
ture allows the unit to be used in applications that previously
required a T1 Extension Repeater.
2.2 Power
2.2.1 Local Power
The NIU can be powered either from the T1 span or from a local
external supply. When locally powered, the supply should be 22
to 56Vdc and can be either a positive or negative ground refer-
ence. This allows the NIU to operate from +24Vdc supplies at
certain wireless and PCS (Personal Communication Service)
sites. In the local power mode, the NIU completes the T1 span
simplex power loop and drops negligible span voltage.
2.2.2 Span Power - Loop Mode
When optioned for Span Power - Loop Mode, the unit is pow-
ered remotely from the last serving office via the transmission
simplex leads. The unit will operate with a simplex current rang-
ing from 57 to 63 mA and will drop 24 Volts nominal at 60mA.
In addition, in the Span Power - Loop Mode, the unit will serve
as a termination device for span power by looping the simplex
current back on the FAC OUT simplex lead.
3. TRANSMISSION FEATURES & OPTIONS
The NIU can be configured to operate in multiple applications.
The specific transmission provisioning is dependent on the ap-
plication. To facilitate this discussion, refer to Figure 4 for a
simplified diagram of the NIU transmission path during normal
operation.
3.1 RCV Path: Facility to CPE (A to Z Direction)
3.1.1 The incoming DS1 bit stream from the facility enters
the NIU on the FAC IN port and is transformer coupled into the
receive path circuitry. To facilitate circuit testing, a front-panel
bantam jack (FAC MON) provides monitor access to the receive
path.
3.1.2 The FAC-to-CPE path is continuously monitored for
loss of signal, control codes and performance statistics by vari-
ous detectors that operate over an input signal range of 0 to
-30dB DSX, and are unaffected by cable length or terminations
on any port or signal state of the CPE. If the FAC IN signal level
goes below -30dBDSX for more than 150ms, a FAC-to-CPE
path Loss-Of-Signal condition is declared, the front-panel
FLOS LED lights solid red and an Alarm Indication Signal
(AIS) is sent to the CPE.
3.1.3 FAC-to-CPE Regen
With FAC-to-CPE Regen enabled, the NIU will regenerate in-
put levels that have been attenuated from 0 to 30dB to a nominal
0dB DSX to the customer interface. The FAC-to-CPE Regen is
a selectable option that can be set remotely via TL1 or 16-bit
commands or locally via the craft terminal interface port. With
Figure 2. Metallic T1 Span Applications
CPE
15dB 7.5dB
22.5dB
Network
Interface
NIU
LINE
RPTR
Figure 3. Lightwave/Mux Fiber Applications
CPE
15dB 7.5dB
22.5dB
Network
Interface
M
U
X
NIU
LBO
220 feet

Section 311-580-20B 030-101527 Rev. B
40407IBRB
5
15
CT1
CR1
7
13
41
47
55
49
CT
CR
FAC
IN
FAC
OUT
CPE
IN
CPE
OUT
T
R
T1
R1
Figure 4. 3115-80 Block Diagram Overview
FAC
MON
TO/FROM
TELCO
FACILITY
DIS
CPE
MON
FLOS
PERFORMANCE
MONITOR & LOS
DETECTOR
(CPE-to-FAC PATH - Z-A)
PERFORMANCE
MONITOR & LOS
DETECTOR
(FAC-to-CPE PATH - A-Z)
PERFORMANCE
REGISTERS
Note: Switches shown are for illustrative purposes
only - options are provisioned electronically
CONTROL CODE
DETECTORS
FAC-to-CPE
REGEN
TO/FROM
CUSTOMER
INTERFACE
(CPE)
CLOS
CPE-to-FAC
REGEN
EN
DIS
EN
Provisionable/
Self-Aligning
LBO
22.5 dB
15 dB
0 dB
7.5 dB
AB15 dB
AB22.5 dB
LBO
15
7.5
0
the FAC-to-CPE Regen disabled, the receive transmission path
provides no net regeneration from input to output. In this case,
the NIU has a nominal insertion loss of 1.5dB.
3.1.4 FAC-to-CPE LBO
3.1.4.1 The fixed LBO circuit provides from 0 to -15dB of sig-
nal attenuation in 7.5dB increments. The FAC-to-CPE LBO is
a selectable option that can be set remotely via TL1 or 16-bit
commands or locally via the craft terminal interface port.
3.2 XMT Path: CPE-to-FAC (Z to A Direction)
The DS1 signal from the CPE enters the NIU via the CPE IN
port and is transformer coupled into the transmit path circuitry.
The transmit path is continuously monitored for loss of signal
and DS1 performance from the customer. If the CPE IN signals
goes below -30dBDSX for more than 150ms, a CPE-to-FAC
path Loss-Of-Signal condition is declared and the front-panel
CLOS LED lights solid red.
3.2.1 CPE-to-FAC Regen
When placed behind a multiplexer (i.e., fiber applications), the
unit functions as a T1 Extension Repeater and requires the CPE-
to-FAC Regen to be enabled. With FAC Regen enabled, the
NIU will regenerate input levels that have been attenuated from
0 to 30dB to a nominal 0dB DSX to the facility interface. The
CPE-to-FAC Regen is a selectable option that can be set re-
motely via TL1 or 16-bit commands or locally via the craft
terminal interface port. With the CPE-to-FAC Regen disabled,
the receive transmission path provides no net regeneration from
input to output. In this case, the signal is connected directly to
the CPE-to-FAC LBO circuit.
3.2.2 CPE-to-FAC LBO
3.2.2.1 LBO (Line Build Out) is an artificial line used to meet
T1 span and end-section design requirements. The 3115-80 pro-
vides a fixed LBO circuit as well as a self aligning LBO circuit.
3.2.2.2 The fixed LBO circuit provides from 0 to 22.5dB of sig-
nal attenuation in 7.5dB increments. The CPE-to-FAC LBO is
a selectable option that can be set remotely via TL1 or 16-bit
commands or locally via the craft terminal interface port.
3.2.2.3 As an alternative to the fixed LBO settings, the "Auto-
Binder" feature can be selected (AB15 and AB22.5). The
auto-binder option only introduces loss when necessary, auto-
matically protecting the network from mis-optioned customer
equipment - specifically, mis-optioned customer LBO settings.
3.2.2.4 At installation, the NIU/PM will have it’s "Auto-Bind-
er Level" circuitry optioned to match the circuit’s binder level
requirement .... e.g. -22.5 dB (AB22.5). The "Auto-binder Lev-
el" circuitry measures the signal level arriving from the facility
as well as the signal level arriving from the customer. Based on
these levels, the NIU/PM’s "Auto-Binder Level" circuitry will
automatically insert the appropriate amount of additional loss
required to ensure the customer’s signal arrives at the binder
group’s common termination point at the correct level. For a set-
ting of "AB22.5", a level of -22.5 dB is maintained. The
"Auto-binder Level" circuitry constantly monitors the input lev-
els from the network and customer and adjusts how much
additional LBO is required to keep the binder level at the neces-
sary level.
- NOTE -
The Auto-Binder Level" circuitry only introduces additional
loss when the customer fails" to meet the signal level require-
ments set forth by the RBOC. The additional loss is only inserted
when the customer’s signal threatens to interfere with other, adja-
cent T1 service by introducing crosstalk problems. Additionally,
sufficient hysteresis is provided to prevent the Auto-Binder" cir-
cuitry from oscillating in and out.
Examples:
If FAC IN level is 0dB and CPE IN level is 22.5dB, and
Binder Level selection is set for 22.5dB, the LBO circuit
would adjust itself to 0dB.

Section 311-580-20B
030-101527 Rev. B
5
0407IBRB
Figure 5. 3115-80 Detailed Block Diagram
FAC-to-CPE
Regen
OFF
ON
17
5
15
55
49
CT1
CR1
CPE Out
CT
CR
CPE In
7
13
T
R
TP1
TP2
GND
P201 SPAN
LOCAL SPAN
P201
LOCAL
T1
R1
41
47
PWR
LB
FAC Out
FAC
MON
System
Controller And
PM Registers
Provisionable/
Self-Aligning
LBO
LB
Relay
10 Ω
LB
LB
CPE
MON
Power
Converter
LOCAL SPAN
P201
TO CPE
FROM CPE
TO
FACILITY
FROM
FACILITY
RCV In
35
MAN
LB
LB1
LB1
LB1
Relay
Network
Loopback
CPE
Loopback
ESF
CPE-to-FAC
Regen
22.5 dB
15 dB
27 FRM GND
-V
OVER CURRENT
PROTECTION
Control
Code
Detector
Performance
Monitor &
LOS Detector
FLOS
AIS to CPE
Generator
LB
CPE LOS
(LB/AIS/Idle/RAI-CI)
Generator
0 dB
7.5 dB
AB15 dB
AB22.5 dB
OVER CURRENT
PROTECTION
OFF
ON
Performance
Monitor &
LOS Detector
CLOS
DB-9
Craft Port
PROTECTION
SURGE
PROTECTION
SURGE
LBO
15
7.5
0
B8ZS
If FAC IN level is 0dB and CPE IN level is 15dB, and the
Binder Level selection is set for 22.5dB, the LBO circuit
would adjust itself to 7.5dB.
3.2.2.5 The resulting signal is then output over the FAC OUT
port toward the Telco Facility. To facilitate circuit testing, a
front-panel bantam jack (CPE MON) provides monitor access
to the path.
3.3 Monitored Line Coding - AMI/B8ZS
The Monitored Line Code option determines if B8ZS octets and
8 consecutive 0’s are reflected in the Line Errored Seconds and
B8ZS Errored Second performance parameters. This option
does not effect the unit’s transmission path. When the Moni-
tored Line Coding is set for AMI, occurrences of 16 consecutive
0’s will be disregarded and occurrences of B8ZS octets will be re-
flected in the B8ZS Errored Count. When the Monitored Line
Coding is set for B8ZS, the front panel B8ZS LED is illuminated
(green) and occurrences of B8ZS octets will be disregarded and
occurrences of 8 consecutive 0’s will be reflected in the Line Er-
rored Seconds.
3.4 Monitored Framing - ESF/SF
The Monitored Framing option determines the framing refer-
ence that the performance monitoring (PM) section of the NIU
will use in it’s PM calculations. If the option is set for ESF", val-
id ESF-framing bits and CRC-bits are expected. Note, the
setting of this option does not affect the unit’s ability to pass sig-
nal. That is, if this option is set to "SF", the NIU shall still have
the ability to pass ESF framed signals AND inject NPRM’s into
the ESF data-link - despite the fact that the PM section will be
reporting Severe Errored Frame events due to the framing mis-
match (i.e. Monitored Framing = SF, Actual FACILITY
Framing = ESF). This option can be set remotely via TL1 or
16-bit commands or locally via the craft interface.
4. LOOPBACK FEATURES AND OPTIONS
Loopback can be used during maintenance and circuit trouble-
shooting to verify the integrity of the Telco DS1 facility up to, and
including, the NIU. Loopback, when activated, loops the entire
DS1 payload from the receive facility back towards the transmit
facility. Also, when the unit is in loopback the front-panel Loop-
back LED (LB) will be on, and a loopback timeout circuit, if

Section 311-580-20B 030-101527 Rev. B
60407IBRB
enabled, is activated. Figure 6 shows a simplified view of the cir-
cuit during loopback .
4.1 Facility Loopback
During Facility Loopback, the LB LED is solid yellow and the
receive T1 bit stream from the facility enters the NIU on the
FAC IN port. The signal is then routed through the loopback
path to the opposite path and is passed back to the network via
the FAC OUT port. During Network-side Loopback, AIS is sent
toward the CPE.
4.2 CPE Loopback
CPE Loopback is available via the NIU craft port STATUS
menu. By using the <Ctrl> and <C> keys simultaneously, the
NIU can activate the CPE loopback. During CPE Loopback, the
signal from the CPE is routed through the loopback path back
to the CPE. When CPE Loopback is activated, the LB LED is
solid yellow.
4.3 Dual Loopback
Dual Loopback is available to simultaneously loop back signals
to the facility and then back to the CPE. Dual Loopback can be
activated via inband codes, via the MLB front panel switch, and
via the NIU craft port STATUS menu. When Dual Loopback is
activated, the LB LED is blinking yellow.
4.4 Loopback Activation/Deactivation
Loopback can be activated/deactivated by one of four ways:
1. Remotely, on-demand, via control codes (inband or ESF
Data Link) in the DS1 signal from a network test location,
2. Locally, on demand, via the front-panel MAN LB push but-
ton switch,
3. Locally, on demand, via the front-panel RS-232 craft termi-
nal interface port, or
4. Automatically, when the NIU detects a loss of signal from
the CPE and CPE LOS response is optioned for LB (see
Part 5).
4.5 Remote Loopback Activation/Deactivation
Loopback activation/deactivation is done from a remote test
center, such as a Hi-Cap Center or Central Office, by sending in-
band or ESF Data Link loopback control codes toward the NIU
for the proper duration. These control code sequences are listed
in Table 1.
Function Code Type
DS1/T1 Activate 11000 Unframed, SF or ESF
(Loop Up) 0001 0010 1111 1111 ESF DATA LINK1
DS1/T1 11100 Unframed, SF or ESF
Deactivate
(Loop Down)
0010 0100 1111 1111
or
0011 1000 1111 1111
ESF DATA LINK1
Addressed LB
Activate
1101 0011 1101 0011
(D3D3)
SF or ESF
Note 1: Right-most bit sent first.
Table 1. Loopback Control Codes
4.5.1 Inband Codes
Inband codes are repetitive patterns at the 1.544Mb rate and
may be unframed, SF framed or ESF framed. The Inband code
pattern must be sent for a minimum of five seconds. The unit will
reject the pattern if it is less than five seconds in duration or if
the error rate is greater than 10-3.
4.5.2 ESF Codes
ESF codes are bit-oriented messages sent in the ESF Data Link
and must be sent for a minimum of four consecutive repetitions
(approximately 16ms). The unit will reject the pattern if it is less
than four consecutive repetitions in duration or if the error rate
is greater than 10-3.
4.6 Addressed Loopback Mode
4.6.1 When installed in SONET/Mux applications, the NIU
can be configured for addressed loopbacks. This allows the craft
to test locations at the service interface (SI) then subsequently
loop the NIU adjacent to the SONET or Mux Interface. The ad-
dressed loopback mode is an option that can be set remotely via
TL1 or 16-bit commands or locally via the craft interface port.
5
15
CT1
CR1
7
13
41
47
55
49
CT
CR
FAC
IN
FAC
OUT
CPE
IN
CPE
OUT
T
R
T1
R1
Figure 6. Transmission Path During Loopback Operation
FAC
MON
TO/FROM
TELCO
FACILITY
CPE
MON
FLOS
LOS DETECTOR
(CPE-to-FAC PATH - Z-A)
LOS DETECTOR
(FAC-to-CPE PATH - A-Z)
AIS
GENERATOR
Note: Switches shown are for illustrative purposes
only - options are provisioned electronically
THRU
REGEN
FAC-to-CPE
REGEN
TO/FROM
CUSTOMER
INTERFACE
(CPE)
CLOS
CONTROL CODE
DETECTORS
X
CPE (Dual)
Loopback
Only
CPE-to-FAC
REGEN
DIS
EN
Provisionable/
Self-Aligning
LBO
22.5 dB
15 dB
0 dB
7.5 dB
AB15 dB
AB22.5 dB
LBO
15
7.5
0

Section 311-580-20B
030-101527 Rev. B
7
0407IBRB
4.6.2 To loop back the unit when it is configured for
addressed loopback operation, the test person first sends the in-
band or ESF Data Link Loop-Up command (see Table 1) for the
proper duration. This will loop up the distant NIU and serve as
an arming code for the 3115-80. When the unit is armed, the LB
LED will flash yellow.
4.6.3 The test person then sends the 16-bit repeating pattern
1101 0011 1101 0011 for five seconds minimum. Upon receiving
the code, the unit enters loopback and 10 seconds later returns
an acknowledgement of 232 bit errors indicating the NIU is
looped.
4.7 Manual Loopback
The NIU loopback state can be controlled by pressing the front-
panel MAN LB push button. Depression of the MAN LB push
button will cycle through the loopback states.
When first depressed, the LB LED will go off and remain
off during the first 3 seconds that the MAN LB is depressed.
If released during this 3 second period, all existing loopback
conditions will be deactivated.
If depressed for 3 to 5 seconds, the LB LED will be on solid
(yellow). If released in this interval, the Network Loopback
will be activated.
If depressed for greater than 5 seconds, the LB LED will be-
gin blinking (yellow). If released after 5 seconds, the Dual
Loopback will be activated.
4.8 Loopback Timeout
4.8.1 The unit provides a timeout feature that can be config-
ured to release a code-activated loopback condition either 20,
60, 120 or 1440 minutes (24 hours) after initial activation.
4.8.2 The loopback condition can be released before the
timeout expiration period by: 1) sending loop-down code to the
NIU from the network test location, 2) through the craft inter-
face port, or 3) by pressing the front-panel MAN LB switch for
less than 3 seconds. Loopback timeout can be permanently dis-
abled via an option provisioned locally from the craft interface
port or remotely from the network test location.
4.9 CPE (Dual) Loopback Activation
4.9.1 To activate CPE loopback, the unit must first be in net-
work-side loopback from the remote test location. At this point,
re-application of loop-up code will operate CPE loopback allow-
ing the customer or craft personnel to evaluate the integrity of
the circuitry on the CPE-side of the demarcation point. The unit
can be placed in CPE loopback via the front-panel MAN LB
push button (see Paragraph 4.7). CPE Loopback can also be ac-
tivated and deactivated from the Circuit Status Menu via the
craft interface port.
4.9.2 When CPE loopback is activated, it will remain acti-
vated until:
1. the NIU detects a loop-down command from the Network-
side,
2. when the timeout release feature expires,
3. when released via the craft interface port, or
4. when the MAN LB switch is pressed for > 5 seconds.
5. SECTIONALIZATION ALARM FEATURES
The NIU is equipped with features that allow a network moni-
toring location to differentiate between fault conditions that are
beyond the NIU (i.e., CPE or inside wiring) and those that are
legitimate network problems.
5.1 CPE LOS Modes
5.1.1 LB Upon CPE LOS
In this mode, the unit continuously monitors the DS1 signal
from the CPE for customer loss of signal, and upon detecting a
loss will change the CLOS LED from green to red and cause the
unit to enter Loopback toward the network. When the signal
from the CPE is restored the unit will return to normal opera-
tion. LB upon CPE LOS is an option that can be set remotely via
TL1 or 16-bit commands or locally via the craft interface port.
When set to enter loopback upon detecting a loss of signal from
the CPE, the NIU will assume the transmission path as shown in
Figure 6.
5.1.2 AIS Upon CPE LOS
In this mode, the unit continuously monitors the DS1 signal
from the CPE for customer loss of signal, and upon detecting a
loss will change the CLOS LED from green to red and send an
unframed, all-ones Alarm Indication Signal (AIS) to the net-
work. When the signal from the CPE is restored the unit will
return to normal operation. The AIS upon CPE LOS mode is an
option that can be set remotely via TL1 or 16-bit commands or
locally via the craft interface port.
5.1.3 Idle Code Upon CPE LOS
In this mode, the unit continuously monitors the DS1 signal
from the CPE for customer loss of signal and upon detecting a
loss will change the CLOS LED from green to red and send an
Idle code toward the network. When signal from the customer
is restored, the NIU returns to normal operation. The specific
format in which the Idle signal is sent toward the network facility
is dependent on the format of the DS1 signal received from the
network facility:
1. If the received signal is SF, the Idle signal will be SF and will
provide a 0001 0111 repeating pattern in each of the 24 DS0
time slots,
2. If the received signal is ESF, the Idle signal will be ESF and
provide a 0001 0111 repeating pattern in each of the 24 DS0
time slots. In addition, the ESF Data Link will contain the
ESF yellow alarm signal 1111 1111 0000 0000, interrupted
each second with a 100ms burst of LAPD idle code 0111
1110,
3. If no signal is received from the network or if the DS1 signal
is unframed, the NIU will default to the SF Idle mode.
The Idle Code upon CPE LOS mode is an option that can be set
remotely or locally via TL1 or 16-bit commands or via the craft
interface port.
5.2 CPE Loss Of Signal Override
5.2.1 When the NIU detects a loss of signal from the CPE
and if the CPE Loss of Signal option is enabled, the NIU will re-
spond in accordance to the setting of the CPE LOS option.
These options are as follows:

Section 311-580-20B 030-101527 Rev. B
80407IBRB
enter loopback upon loss of signal from the CPE
send AIS to the network upon loss of signal
send Idle to the network upon loss of signal
send AIS-CI to the network upon loss of signal
5.2.2 No matter what action the NIU takes upon detecting
a loss of signal from the CPE, that mode can be remotely over-
ridden by sending a loop-down command to the NIU. Hence,
CPE LOS Override.
5.2.3 Upon detecting the loop-down command, the NIU will
disable the CPE LOS function and operate as if the CPE LOS
function is actually set for disable. During this mode, the NIU
will respond to normal loop-up and loop-down commands. The
CPE LOS Override feature will time out in 20 minutes. At the
end of 20 minutes, the NIU will re-enable the CPE LOS function
and respond accordingly. That is, if a loss-of-signal condition
from the CPE still exists, the NIU will, again, respond according
to how the CPE LOS option is set (LB/AIS/Idle/AIS-CI).
5.3 RAI-CI and AIS-CI Alarms
In this mode, the unit continuously monitors both the signal
from the customer and from the network facility in order to de-
termine what type of alarm signal to send back toward the
network monitoring location. This capability, along with the
uniquely-identifiable Remote Alarm Indication - Customer In-
terface (RAI-CI) and Alarm Indication Signal - Customer
Interface (AIS-CI) signals, allows test personnel to accurately
sectionalize network facility problems versus CPE problems.
5.3.1 RAI-CI
If the unit sees a Remote Alarm Indication signal coming from
the customer equipment (SF or ESF framed), and does not de-
tect an Alarm Indication Signal (AIS), Loss of Frame (LOF) or
Loss of Signal (LOS) on the network, the unit will send a Remote
Alarm Indication (RAI-CI) toward the network if the network
is ESF.
5.3.2 AIS-CI
5.3.2.1 If the unit sees an Alarm Indication Signal coming
from the customer equipment (AIS-CI), and does not detect a
Loss of Frame (LOF), or Loss of Signal (LOS) on the network,
the unit will send a unique Alarm Indication Signal (AIS-CI) to-
ward the network.
5.3.2.2 Both AIS-CI and RAI-CI are backwards compatible
with existing network devices and will appear as normal AIS or
RAI.
5.3.2.3 Upon detecting a loss of signal on the network side of
the unit, the unit will send an Alarm Indication Signal (AIS) to-
ward the customer equipment. The customer equipment, in
turn, will send a Remote AIarm Indication (RAI) signal back to-
wards the network.
6. PERFORMANCE MONITORING/REPORTING
The unit continuously monitors the DS1 bit stream in both the
Network-to-CPE (A-Z) and CPE-to-Network (Z-A) direction
for performance statistics, and maintains these statistics inde-
pendently for each direction. Performance primitives are
collected and stored as performance parameters which are avail-
able for remote retrieval or local retrieval via the front-panel
craft terminal interface port.
6.1 Performance Primitives
Performance primitives are basic error events, or other perfor-
mance-related occurrences, monitored by the unit and stored as
performance parameters.
Line Performance Primitives
Bipolar Violation BPV
Excessive Zeros EXZ
Loss of Signal LOS
Path Performance Primitives
CRC Error (ESF) CRC6
Frame Bit Error (SF) FE
Out of Frame OOF
Severely Errored Frame SEF
Alarm Indication Signal AIS
6.2 Performance Parameters
The unit monitors, processes and stores the span’s performance
primitives as Line, Path and Miscellaneous parameters.
Line Performance Parameters
Coding Violation Line CVL
Errored Seconds Line ESL
Severely Errored Seconds Line SESL
Loss of Signal Seconds Line LOSS-L
Path Performance Parameters
Coding Violation Path CVP
Errored Seconds Path ESP
Severely Errored Seconds Path SESP
Unavailable Seconds-Path UASP
Miscellaneous Parameters
Pulse Density Violation Seconds PDV-SEC
B8ZS Violation Seconds B8ZS-SEC
Monitored Seconds MSEC
6.3 Status Register (STAT)
The unit provides a Status Register for both directions of trans-
mission indicating various events that have occurred during a
particular monitoring window. The Status Register consists of
an 8-bit word with a 1" indicating an occurrence of a particular
event.
Event Bit
Loopback 1
Data incomplete 2
Loss of Signal 3
Reserved 4
Power Loss 5
AIS 6
RAI (alarm yellow) 7
Out of Frame 8
6.4 Event/Alarm Log
The NIU features an Event/Alarm Log that registers various
events occurring during the monitoring period. The log provides
time-stamped entries for the most important types of events
such as loss of signal, power outages, PM registers cleared, alarm
detection, and more. Several different types of events are pos-
sible in the log as listed in the examples of Table 2. The
Event/Alarm Log will retain the 100 most recent events in non-
volatile memory. The Event/Alarm Log can be viewed locally via

Section 311-580-20B
030-101527 Rev. B
9
0407IBRB
the craft interface port or can be retrieved remotely via TL1
commands.
Message Type Event/Alarm Log Message
SIGNAL STATE LOS FROM CPE
LOS FROM CPE CLEARED
LOS FROM FAC
LOS FROM FAC CLEARED
AIS FROM FAC
AIS FROM FAC CLEARED
AIS FROM CPE
AIS FROM CPE CLEARED
RAI FROM CPE
RAI FROM CPE CLEARED
LOOPBACK REMOTE LOOP UP
ACTIVITIES MANUAL LOOP UP
REMOTE LOOP DOWN
MANUAL LOOP DOWN
TIMEOUT LOOP DOWN
ANY LOOP UP
ANY LOOP DOWN
NIU POWER LOSS OF POWER
STATUS POWER UP
MAINT. RESET RESET PM REGISTERS
ACTIVITIES RESET EVENT/ALARM LOG
CHANGE CIRCUIT ID
PROVISIONING OPTION CHANGE
PROVISIONING SF FRAMING SET
ANOMALIES ESF FRAMING SET
FRAMING LOSS
Table 2. Samples of Event/Alarm Log Messages
6.5 Performance Storage Registers
The unit maintains performance parameters, Status Register
events and PIRs for both directions of transmission in 15 minute,
hourly, and daily registers as shown in Table 3.
15 Minutes 1 Hour 1 Day
Current Current Current
Previous Previous Previous
95 Additional 22 Additional 6 Additional
24 Hours Total 24 Hours Total 30 Days Total
Table 3. PM Data Storage Periods
6.6 Historical Performance Monitoring & Retrieval
Historical (30 day) PM data is provided by the unit. In the idle
or non-looped state, the DS1 bit stream (SF or ESF circuits), in
both directions of transmission, is monitored for performance
statistics. The unit records and time stamps these performance
statistics in non-volatile memory for retrieval at a later time.
These performance statistics can be retrieved on demand from
the NIU in two ways: 1) locally, and on a non-intrusive basis, via
the front-panel craft interface port or 2) remotely, via TL1 com-
mands and responses in the ESF Data Link.
6.7 PM Retrieval, SF/ESF Circuits (Craft Port)
The 3115-80 provides a front-panel RS-232 connector for local
access of performance statistics data without placing the unit
into loopback. See Paragraph 7.1.2 and Figure 10.
6.8 PM Retrieval, SF/ESF Circuits (Intrusive)
6.8.1 To access historical performance information, the test
center (Hi-Cap or CO) first accesses the circuit on a split basis,
and places the NIU in loopback. If the circuit is SF, the test con-
troller must then reconfigure for ESF framing for the duration
of the session to allow commands and responses to be exchanged
with the NIU in the ESF Data Link of the intervening facility.
6.8.2 The procedure for customer ESF circuits is identical to
SF, except the test controller does not need to change the fram-
ing format during the test session.
6.9 PM Retrieval − Inband Codes
By sending a 16-bit Query code, while the NIU is in loopback,
the unit will respond with a Bit Error Response (BER) indicat-
ing the number of Errored Seconds (ES)/Unavailable Seconds
(UAS) within the last 24 hours. The Bit Error response provides
a rough estimate on the status of the circuit. The unit will
respond to the codes shown in Table 6, within 10 seconds, with
a BER as defined Table 6.
Query Binary Hex Setting BER
CPE Errored Second
Customer to Network
1100 0110 1100 0000 C6C0 0 errored seconds 900
Customer to Network 1 to 100 errored sec. 1070
(ES-P) 101−319 errored sec. 1150
Greater than 319 1220
Greater
than
319
errored seconds
1220
CPE Unavail Second
Customer to Network
1100 0110 1100 0001 C6C1 0 unavailable seconds 900
Customer to Network 1 to 100 unavail. sec. 1070
(UAS-P) 101−319 unavail. sec. 1150
Greater than 319 1220
Greater
than
319
unavailable seconds
1220
FAC Errored Second
Network to Customer
1100 0110 1100 0011 C6C3 0 errored seconds 900
Network to Customer 1 to 100 errored sec. 1070
(ES-P) 101−319 errored sec. 1150
Greater than 319 1220
Greater
than
319
errored seconds
1220
FAC Unavail Second
Network to Customer
1100 0110 1100 0100 C6C4 0 unavailable seconds 900
Network to Customer 1 to 100 unavail. sec. 1070
(UAS-P) 101−319 unavail. sec. 1150
Greater than 319 1220
Greater
than
319
unavailable seconds
1220
Clear PM 1100 0110 1100 0101 C6C5 Clear all PM 900
Table 4. PM Retrieval - Inband Codes and BER Responses
6.10 PM Retrieval, ESF Circuits (Non-Intrusive)
6.10.1 If the Test Access Device (TAD) being used has the ca-
pability to gain splitting access only to the ESF Data Link,
performance statistics can be retrieved using TL1 commands
without affecting customer payload information. In this mode,
the unit will effectively perform a loopback" of the ESF Data
Link allowing messages to be interchanged with the test control-
ler.

Section 311-580-20B 030-101527 Rev. B
10 0407IBRB
T1
ORB 3115-80
Test Access
Digroup
(Split Access)
TL1 PM Commands/Responses to
Performance Monitoring System
Figure 7. TL1 PM Retrieval Diagram - Intrusive Mode Shown
DCS or other Test
Head Device
Encapsulated
TL1 Messages
in ESF Data
Link
TL1z
Command/
Response
TEST
RESOURCES
T1 LINE
RPTR
CSU
T1
OFFICE
RPTR
3115-80 CSU
NPRM PRM
CSU
PRM
NIU
NPRM
MONITOR
NETWORK MONITOR / TEST ACCESS
TL1 Reporting to Performance
Surveillance System
Figure 8. NPRM Application Diagram
T1
LINE RPTR
6.10.2 The TL1 commands conform to standard commands
such as RTRV-PM, INIT-REG, etc. The protocol is a modified
X.25 LAPB. A generalized diagram of this procedure is shown
in Figure 7.
6.11 Real Time Performance Reporting
Real-time PM reporting from both the facility and CPE can be
provided using one of two methods, SPRMs (Supplemental Per-
formance Report Messages) or NPRMs (Network Performance
Report Messages). Both methods are similar in structure but dif-
fer in content. Both methods also conform to ANSI
Specifications described in T1.403-1998. These message for-
mats are similar to ANSI T1.403 PRMs (Performance Report
Messages) that is sent toward the network at 1-second intervals
via the ESF Data Link by the CPE CSU. The NPRM or SPRM
messages allow network equipment to determine if the T1 signal
was in error before being sent to the customer. It also indicates
if the T1 signal from the CPE contained errors before it enters
the network.
6.11.1 Network Performance Report Message
6.11.1.1 The NPRM mode operates by sending an NPRM mes-
sage toward the network once every second. This message
contains performance information that covers the last four sec-
onds of operation. This NPRM is inserted into the Data Link by
the NIU after" the 1-second PRM from the customer CSU that
is passed through the NIU. Note that the CSU may not generate
PRMs or may be operating in the PUB 54016 mode that does not
use PRMs. The NIU will always generate an NPRM whether
CSU PRMs are generated or not. In order to allow network
monitoring equipment to differentiate between CSU PRMs and
NPRMs, the NPRM is assigned a SAPI address of 16, allowing
easy differentiation from a CSU PRM that has an assigned SAPI
address of 14. A generalized network diagram of NPRM report-
ing and collection is illustrated in Figure 8.
6.11.1.2 NPRM is generally preferred to SPRM since it pro-
vides more detailed information, and does not modify the
customer CSU PRMs thereby guaranteeing compatibility with
all T1.403-1995 compliant CSUs.
6.11.2 Supplemental Performance Report Message
The Supplemental Performance Report Message (SPRM)
mode, like the NPRM mode, consists of a performance report
message that is sent toward the network at 1-second intervals.
6.11.2.1 SPRM Mode - ESF Circuits
When installed on ESF circuits and the CSU is generating
PRMs, the 3115-80 will actually modify bits in the customer-gen-
erated PRM in order to provide performance information on
the circuit at the point of the network interface. This modified
PRM is known as the Supplemental Performance Report Mes-
sage (SPRM). Typically, the R", U1" and U2" bits of the
customer PRM are the modified bits. The R bit channel is used
to flag whether or not SPRM information had been added to the
PRMs and, if so, what mode of SPRM is in use. The U1 and U2
bits are used to multiplex the additional performance informa-
tion into the PRMs.
6.11.2.2 SPRM Mode - SF Circuits
When installed on SF circuits and frame format conversion is en-
abled (i.e., network is ESF framed), the 3115-80 will generate its

Section 311-580-20B
030-101527 Rev. B
11
0407IBRB
own SPRM in order to provide performance information on the
T1 circuit at the point of the network interface. The R", U1"
and U2" bits of the 3115-80-generated PRM provide the addi-
tional performance information into the PRMs. The use of each
bit is given in the following paragraphs.
6.11.2.3 R Bit
Data is written to the R bit at a rate of 1 bit per PRM, or 1 bit per
second. Each new bit is written into the R bit associated with the
message for second t = T0". The R bit then shifts, second-by-
second, along with the other bits in the PRM until it is last seen
in the R-bit position for second t = T0 + 3". The 1 bit per sec-
ond patterns sent in the R-bit channel have the following
meanings:
000000000... No SPRM present or SPRM is disabled. This is
the status of the R bit when a CSU generates a
PRM.
111111111... SPRM added at point of generation of PRM. This
only applies when the NIU is generating its own
PRM, while in Frame Conversion mode.
10101010... Internal hardware fault detected at point of inser-
tion of SPRM.
10001000... SPRM added to PRM at intermediate point. This
mode applies when the customer equipment is
generating PRMs and the 3115-80 is modifying it
with additional information or when the 3115-80
is generating a PRM in Normal mode (frame con-
version disabled).
6.11.2.4 U1 Bit
This bit carries performance information in the DS1 signal re-
ceived from the network back to the network. This bit will be a
logic 1 if a condition is detected in the signal which would nor-
mally result in conversion of any bit in a PRM from 0 to 1. Each
U1 bit carries information for the same period as the 1-second
message in which it is embedded with such offset as is provided
by the transmission delay between the point of generation of the
PRM and the point of insertion of the SPRM.
- NOTE -
This bit defaults to zero for self-generated SPRMS.
6.11.2.5 U2 Bit
This bit carries performance information in the DS1 signal re-
ceived from the customer back to the network. This bit will be a
logic 1 if a condition is detected in the signal which would nor-
mally result in conversion of any bit in a PRM from 0 to 1. Each
U2 bit carries information for the same period as the 1-second
message in which it is embedded with such offset as is provided
by the transmission delay between the point of generation of the
PRM and the point of insertion of the SPRM. As a result of mod-
ifying a customer-generated PRM, a new Frame Check
Sequence (FCS) for the SPRM will be calculated and inserted
by the 3115-80.
6.11.3 SPRM/NPRM Mode
The SPRM/NPRM mode consists of both SPRM and NPRM
Performance Report Messages sent toward the network at 1-sec-
ond intervals. Detailed descriptions of SPRMs and NPRMs can
be found in Paragraphs 6.11 through 6.11.2.5.
Figure 9. 3115-80 Front Panel
B90-311580
126270
NIU-PM
C
P
E
M
O
N
TP1
TP2
F
A
C
M
O
N
PWR
LB
FLOS
CLOS
ESF
MAN
LB
B8ZS
7. HARDWARE OPTIONS & FEATURES
The 3115-80 contains features and options located on the front
and side (PCB) panels, as described in the paragraphs below.
- NOTE -
Set any/all manual option switches prior to installing the unit.
- WARNING -
Before making any connections, verify power is off (including
removing the fuse at the fuse and alarm panel) and that any
and all plug-in units are removed from the shelf. Do not
install plug-in units until all shelf wiring is complete.
7.1 Front Panel Features
The unit contains several LEDs for a quick visual indication to
the status of the circuit, two bantam-type monitor jacks for trans-
mission path testing, a DB-9 connector with a female RS-232
interface for craft terminal access, and test points for measuring
span current. A description of each is provided below.
7.1.1 Monitoring Bantam Jacks
The 3115-80 contains two bantam jacks which monitor the T1
signal. These jacks are labelled FAC MON and CPE MON, as
shown in Figure 9.
FAC MON Allows monitoring of the T1 signal being received
from the network
CPE MON Allows monitoring of the T1 signal being sent to
the network
7.1.2 RS-232 DB-9 Connector
The 3115-80 contains a front panel, 9-pin, female, RS-232 DB-9
hardware connector which allows access to stored performance

Section 311-580-20B 030-101527 Rev. B
12 0407IBRB
CAUTION
When disconnecting test equipment from the bantam jacks or the Craft Interface
port, apply pressure on the unit front panel to hold the unit in the assembly. Failure
to do so may cause the unit to be removed from service while disconnecting test
equipment.
Pin 3 - RxD (Receive Data-IN)
Pin 2 - TxD (Transmit Data-OUT)
Figure 10. Front Panel RS-232 (DB-9) Pin Assignments
Pin 5 - SGN (Signal Ground)
data for retrieval purposes, and allows maintenance, circuit
troubleshooting and set up procedures.
7.1.3 Test Points
The 3115-80 contains two test point jacks for measuring the span
current.
TP1 & TP2 Allows for measuring span current using a DC
voltmeter. TP1 will read positive with respect to
TP2. A voltmeter reading of 0.6VDC equates to
a 60mA span.
7.1.4 Status LEDs
The multi-function status LEDs on the front panel provide a
visual indication of various maintenance and alarm conditions.
The LED colors, states, and conditions are listed in Table 5.
LED
LED
Color
LED
State STATUS LED Description
PWR Green On Power is applied and present to the unit.
Off Power not applied.
LB
Yll
On Unit is in Loopback.
Yellow Flashing Unit is armed and ready to detect the addressable
LB code.
Blinking* Unit is in dual loopback.
Off Unit is not in any loopback condition.
FLOS Green On Signal is detected from the network.
Red On Signal from the network to the unit is lost.
CLOS Green On Signal is detected from the customer.
Red On Signal from the customer is lost.
ESF Green On Unit has detected ESF framing from the network.
Off Unit is detecting SF/unframed signals from the
network.
B8ZS Green On Unit is configured for B8ZS line coding.
Off Unit is configured for AMI line coding.
*The on/off cycle of a flashing LED is faster than a blinking LED.
Table 5. Front Panel LED Conditions and States
7.1.5 Push Button Switch, MAN LB
The NIU loopback state can be controlled by pressing the front-
panel MAN LB push button. Depression of the MAN LB push
button will cycle through the loopback states.
SPAN LOC
Top Edge of PCB
Edge Connector (56-pin) of PCB
Figure 11. NIU Powering Option Location
Middle of Side-panel’s
Printed Circuit Board
Gray/shaded rectangle is
the pin jumper.
P201
When first depressed, the LB LED will go off and remain
off during the first 3 seconds that the MAN LB is depressed.
If released during this 3 second period, all existing loopback
conditions will be deactivated.
If depressed for 3 to 5 seconds, the LB LED will be on solid
(Green). If released in this interval, the Network Loopback
will be activated.
If depressed for greater than 5 seconds, the LB LED will be-
gin flashing (Green). If released after 5 seconds, the Dual
Loopback will be activated.
7.2 PCB Power Options (Side Panel)
The unit has a powering option capability (pin headers on the
PCB, making connection via a push-on pin jumper) to configure
the unit for the proper powering operation. A jumper is pro-
vided to allow the installer to select either Span or Local
powering. If Span power is desired, mount the jumper over the
left two rows of pins on header P201. If Local power is desired,
mount the jumper over the right two columns of pins on header
P201. The location of this option is shown in Figure 11.
8. INSTALLATION
Installation consists of inspecting the equipment for damages,
following proper safety precautions, mounting the unit in the
proper slot of the mounting assembly, and verifying the presence
of power and signalling as indicated by the status LEDs. The fol-
lowing paragraphs provide detailed instructions for performing
these procedures.
8.1 Following Safety Precautions
Before installing the NIU, observe the following safety notes.
- INSPECTION NOTE -
Visually inspect the unit for damages prior to installation: if dam-
aged in transit, immediately report the damage to the transporta-
tion company and to Westell (see Part 11 for telephone number).
CAUTION - STATIC-SENSITIVE
This product contains static-sensitive components! Follow
proper electrostatic discharge procedures to maintain
personal and equipment safety. Do not store units near
magnetic, electromagnetic or electrostatic fields. Always
store or ship units in the original static-protective packaging
from Westell. Use anti-static mats when working on units.

Section 311-580-20B
030-101527 Rev. B
13
0407IBRB
CAUTION
Risk of electric shock. Voltages up to 140 VDC (with reference to
ground) may be present on telecommunications circuits.
- PRECAUTIONARY STATEMENT -
- Never install telephone wiring during a lightning storm.
- Never install telephone jacks in wet locations unless the jack is
specifically designed for wet locations.
- Never touch uninsulated telephone wires or terminals unless
the phone line has been disconnected at the network interface.
- Use caution when installing or modifying telephone lines.
- This equipment is intended to be used behind devices that
provide primary lightning protection.
- This installation should conform to Local Codes and NEC
requirements.
- This equipment is to be installed in a restricted access location.
- CAUTION -
Never apply power until all installer connections are made.
8.2 Mounting the Module
The 3115-80 is a 200 MECHANICS-type plug-in module that
mounts in a 200- or 400-mechanics-type mounting assembly (or
equivalent mounting which matches the pin-out plan of the
module). Before installing the module, set any options in the de-
sired position(s). Align the module with the mounting or
assembly card guides above and below the unit and insert as far
as it will go into the slot connector.
Function Designation Pin Number
FAC IN T 7
R 13
CPE OUT CT1 5
CR1 15
CPE IN CT 55
CR 49
FAC OUT T1 41
R1 47
LOCAL POWER -Local Power 35
Ground 17
Frame Ground FRM GND 27
Table 6. 3115-80 Pin Designations
8.3 Making Installer Connections
No installer connections are required other than inserting the
module into the card-edge connector in the shelf or assembly.
The unit makes electrical connections to external equipment
when installed and properly seated in the 56-pin card-edge con-
nector in the mounting assembly. The pin-outs used by the NIU
are listed in Table 6.
- CAUTION -
Use care when installing and removing modules - do not force
into place. If a module resists insertion, remove it and check
for obstructions in/near the connectors and mounting slots,
then carefully re-align and gently re-insert the module.
NIU’s
DB-9
Connector
Baud rate: 9600
Number of data bits: 8
# of start/stop bits: 1
Parity: none
Local Echo: No/Off
Warning Bell: On
Mode: VT100
Auto Line Wrap: No/Off
Standard
RS-232
Cable
(used with
PC with
VT100
emulator).
Terminal
Settings:
Figure 12. Preparing for Provisioning Via DB-9 Port
200 MECHANICS or
400-type mounting
assembly
9. SET-UP AND OPERATION
9.1 Craft Terminal Setup and Operation
9.1.1 The front-panel craft interface port allows the craft to
configure the unit for a particular application, view the stored T1
performance statistics, as well as graphically view circuit status
and perform various test routines. Each menu provides an asso-
ciated HELP screen that explains the function and use of the
menu. HELP screens are accessed by pressing (?).
9.1.2 The craft interface port is a DB-9 connector with an
electrical RS-232 female interface in a DCE configuration. The
craft device can be a terminal operating in the VT-100 protocol
or a PC running a VT-100 terminal emulator program. If a
VT-100 terminal is used a null-modem" cable may be required
between the terminal and the NIU. If a PC with VT-100 emula-
tor program is used, a standard RS-232 cable can be used. The
RS-232 port should be set up for 9600 baud, no parity, and one
stop bit (NP,1S). The electrical connections to the craft port are
shown in Figure 10.
9.2 Menus and Screens
9.2.1 MAIN Menu Screen
Once the terminal or PC is connected to the craft interface port,
the MAIN menu should appear. The MAIN menu provides the
NIU model number, CLEI code, Technical Service contact tele-
phone number, as well as navigation buttons to other screens.
The Model Number and CLEI Code are set at the factory and
cannot be changed. The MAIN menu is illustrated in Figure 14.
To return to the MAIN menu screen from any other screen enter
<Esc>.
9.2.2 PROVISIONING Menu Screen
The PROVISIONING screen (Figure 15) is used to configure
the unit’s options. To reach this screen from the MAIN menu,
type <O>. The NIU is set from the factory to a standard config-
uration. All options in the menu can be set and queried
remotely. For each option, the display shows the CURRENT"
configuration as well as a NEW" field that shows what the op-

Section 311-580-20B 030-101527 Rev. B
14 0407IBRB
Figure 13. A Directory Tree/Path of Software Menus Accessed Via the Craft Interface & VT100 Terminal
Main
Menu
Alarm
Thresholds
Provisioning Circuit Status
(& Loopbacks)
Performance
Statistics Set Clock
Main Menu Screen
on VT100 Terminal
Level 2 -
Level 1 -
Event/Alarm
Log Reports NotePad
Event/Alarm
Log Report
Provisioning
Report
Short PM
Report
Long PM
Report
Delete Record
15 MinuteCurrent Hourly Daily
Add Record
See Figure 14 through Figure 25
for sample menu screens.
Help
Change Circuit ID
Change Options
Test Mode
Provisioning
Submenus
Figure 14. Main Menu Screen
Westell B90-311580 CLEI: T1S1ABTAAA
MAIN MENU
PROACT
T1 PERFORMANCE MONITORING NIU
WESTELL TECHNOLOGIES, INC.
AURORA, IL.
1-800-323-6883
SELECTIONS
O) PROVISIONING
P) PERFORMANCE STATISTICS
S) CIRCUIT STATUS
L) EVENT/ALARM LOG
C) SET CLOCK
T) ALARM THRESHOLDS
R) REPORTS
N) NOTEPAD
?) HELP
Enter letter of selection
tion can be changed to. Use <tab> or the arrow keys to advance
to an option field. Use the <space> bar to change the available
options under the NEW" field.
9.2.2.1 Saving The Changed Options
After configuring the options, press <S> to save the new set-
tings. Note: If you enter <Esc> without saving, the system will give
a message asking if you want to save the new settings.
- WARNING -
Always save changes before disconnecting to activate the changes. If
the craft terminal is disconnected without saving the changes, the
changes will be lost (unit does not save changes automatically).
9.2.3 PERFORMANCE STATISTICS Menu Screens
The Performance Statistics screens are used to view the stored
T1 performance statistics. To reach this screen from the MAIN
menu, type <P>. The example screen below (Figure 16), shows
various performance parameters for both the NET-to-CPE (A
to Z) and CPE-to-NET (Z to A) directions as well as a status reg-
ister describing abnormal circuit conditions during the period.
By using the selection keys at the bottom of the screen, all His-
torical time registers can be examined. Type the appropriate
command to view the 15-minute, Hourly, and Daily screens or
the <N> for Next and <P> for Previous page commands. The
parameters on these screens are automatically updated at 5-sec-
ond intervals. To return to the MAIN menu from this screen,
press the <Esc> key.

Section 311-580-20B
030-101527 Rev. B
15
0407IBRB
Figure 15. Provisioning Menu Screen
PROVISIONING MENU
Option Current New
>Monitored Line Coding: B8ZS AMI
Monitored Framing: ESF
CPE LOS Response: AIS-CI
RAI-CI Option: ENABLED
Real Time PM mode NPRM/SPRM
CPE-to-FAC Regen: REGEN ON
CPE-to-FAC LBO: DISABLED
FAC-to-CPE Regen: REGEN OFF
FAC-to-CPE LBO: DISABLED
Loopback Timeout: 120 MINUTE
Loopback Mode NORMAL
Circuit ID: <UNASSIGNED>
SELECTIONS
S) Save D) Set to default settings
Use <tab> to select option, <space> to change, or Esc to return to main menu
Westell B90-311580 CLEI: T1S1ABTAAA
Field/Option Parameter Default* Description
Monitored Line Coding AMI Configures unit for AMI line coding.
g
(Note 1) B8ZS Configures unit for B8ZS line coding.
Monitored Framing SF Monitors SF parameters for PM.
g
ESF Monitors ESF parameters for PM.
CPE LOS Response None No response to customer LOS.
p
LB Enters loopback toward Network upon detecting a Customer LOS.
Idle Send Idle toward Network upon detecting a customer LOS.
AIS Send AIS toward Network upon detecting a Customer LOS.
AIS-CI Send AIS-CI toward Network upon detecting a Customer LOS.
RAI-CI Option Enabled Converts customer RAI to RAI-CI if also receiving a valid network signal.
p
Disabled RAI from CPE is always passed unchanged.
Real-Time Mode None Disables real-time reporting.
NPRM Configures the unit to send NPRM messages.
SPRM Configures the unit to send SPRM messages.
SPRM/NPRM Configures the unit to send both SPRM and NPRM messages.
CPE-to-FAC REGEN Regen Off No regeneration in the CPE-to-FAC (Z-A, XMT) path.
Regen On Regeneration in the CPE-to-FAC path.
CPE-to-FAC LBO Disabled Select this option to disable the CPE-to-FAC LBO.
7.5 dB Select this option to select 7.5 dB of LBO.
15 dB Select this option to select 15 dB of LBO.
22.5 dB Select this option select 22.5 dB of LBO.
AB15 dB Select this option if the Auto Binder level of the cable is 15 dB.
AB22.5 dB Select this option if the Auto Binder level of the cable is 22.5 dB.
FAC-to-CPE REGEN Regen Off No regeneration in the FAC-to-CPE (A-Z, RCV) path.
Regen On Regeneration in the FAC-to-CPE path (0 dB DSX hand-off).
FAC-to-CPE LBO Disabled Select this option to disable the FAC-to-CPE LBO.
7.5 dB Select this option to select 7.5 dB of LBO.
15 dB Select this option to select 15 dB of LBO.
Loopback Time-out Disabled Loopback will not time-out.
p
20 Minute Loopback will automatically time-out 20 minutes after initial activation.
60 Minute Loopback will automatically time-out 60 minutes after initial activation.
120 Minute Loopback will automatically time-out 120 minutes after initial activation.
24 Hour Loopback will automatically time-out 1440 minutes after initial activation.
Loopback Mode Normal Unit loops up to normal inband/Data Link loopback codes.
p
Addressed Unit loops up to unique 16-bit addressed loopback code.
Circuit ID <user defined> This field can be up to 20 alphanumeric characters (user defined).
Table 7. Options and Parameters

Section 311-580-20B 030-101527 Rev. B
16 0407IBRB
Figure 16. 15-Minute PM Status Screen (Typical)
Westell B90-311580 CLEI: T1S1ABTAAA
02/28/2003 09:02:48
15 MINUTE PM STATISTICS
(CURRENT)
FAC-to-CPE CPE to FAC Date: 02/28/2003
Time: 08:00:00
CV-L 0 0
ES-L 0 0
SES-L 0 99
LOSS-L
CV-P 0 0
ES-P 0 0
SES-P 0 99
UAS-P
PDV-SEC 102 2
B8ZS_SEC 0 0
MSEC 102 102
STAT .2..5.78 .2..5678
SELECTIONS
Q) 15 Minute H) Hourly D) Daily N) Next P) Previous
U) Disable auto updating C) Clear stored data
Enter selection or <Esc> to go back to main menu
Stat Register Key
−−−−−−−−−−−−−−−−−−
1 Loopback
2 Data Incomplete
3 Loss of Signal
4 Unused
5 Power Loss
6 AIS
7 Yellow Alarm
8 Out of Frame
9.2.3.1 Updates
To stop the automatic updating, type <U>. To resume automat-
ic updating, type <U> again.
9.2.3.2 Clearing Status Registers
To clear all stored historical data, type <C>. The system will
give a confirmation message prompting if all data is to be
cleared. Type <Y> for Yes or <N> for No.
- WARNING -
The clear command <C> affects all performance monitoring
screens. The clear command will clear all data screens regardless of
the activating time interval screen.
9.2.4 CIRCUIT STATUS Menu Screen
9.2.4.1 The Circuit Status screen is used to view the circuit sta-
tus of the NIU, as well as perform various test routines such as
loopback. To reach this screen from the MAIN menu, type <S>.
The Circuit Status screen, shown in Figure 17, provides a graphi-
cal representation of the NIU and its ports to the T1 facility and
customer interface.
9.2.4.2 For each port, the screen shows:
1. Level (LVL) of the signal in dB. Possible field values are:
0 0dB level detected
-1 -1dB level detected
-2 -2dB level detected up to
-30 -30dB level detected
LOW Too low to measure
2. Framing (FRMG) that is present at the port. Possible val-
ues in this field are:
SF SF framing present
ESF ESF framing present
UNF unframed
UNK unknown
3. Signal (SIG) status at the port. Possible values here are:
OK Normal signal condition
LOS Loss Of Signal
AIS Alarm Indication Signal (all ones)
RAI Remote Alarm Indication (yellow alarm)
Idle Customer Disconnect Indication signal
RAI-CI Remote Alarm Indication - Customer Interface
AIS-CI Alarm Indication Signal - Customer Interface
9.2.4.3 The Circuit Status screen also shows a graphical repre-
sentation of the internal transmission paths of the NIU, with the
specific regeneration or LBO parameters that have been provi-
sioned. When different parameters are provisioned, remotely or
via the provisioning menu, they will be reflected here.
9.2.4.4 Facility Loopback. By using the <Ctrl><F>keys si-
multaneously, the NIU can be placed into a loopback toward the
Facility (see Figure 18).
9.2.4.5 CPE Loopback. By using the <Ctrl><C> keys simul-
taneously, the NIU can be placed into a loopback toward the
CPE only. The graphical representation on the Status Screen
will change appropriately to show the CPE loopback and AIS be-
ing transmitted toward the facility.
9.2.4.6 Dual Loopback. Dual loopback is achieved by using
both <Ctrl><F> and <Ctrl><C> (see Figure 19). The
graphical representation will change appropriately to show the

Section 311-580-20B
030-101527 Rev. B
17
0407IBRB
Westell B90-311580 CIRCUIT STATUS CLEI: T1S1ABTAAA
LVL: -13.0dBdsx LVL: -13.8dBdsx
FRMG: SF 3115-80 FRMG: SF
SIG: OK SIG: OK
TO FAC TO CPE
7.5dB LBO
LVL: -12dBdsx LVL: -4.0dBdsx
FRMG: SF FRMG: SF
SIG: OK Normal Operation SIG: OK
SELECTIONS
^F) Operate FAC Loopback
^C) Operate CPE Loopback
T) Test Mode Provisioning
^T) Enable Test Mode
Enter selection or <Esc> to go back to main menu
Figure 17. Typical Circuit Status Screen - Normal Operation
Figure 18. Typical Circuit Status Screen - Facility Loopback
X
X
Westell B90-311580 CIRCUIT STATUS CLEI: T1S1ABTAAA
LVL: -13.0dBdsx 3115-80 LVL: 0.0dBdsx
FRMG: SF FRMG: UNF/UNK
SIG: OK SIG: AIS
TO FAC AIS TO CPE
0dB LBO
LVL: -0.5dBdsx LVL: -4.0dBdsx
FRMG: SF Facility Loopback FRMG:
SIG: OK SIG:
SELECTIONS
^C) operate CPE loopback
^D) deactivate loopback
Enter selection or <Esc> to go back to main menu
loopback state as well as the configuration of transmission pa-
rameters and options in the loopback path. Figure 20 shows the
NIU in a single loopback mode when FAC-to-CPE Regenera-
tion is Enabled.
9.2.4.7 Using the <Ctrl><D> keys simultaneously will cause
the NIU to deactivate loopback and return the circuit to normal
operation.
9.2.5 TEST MODE PROVISIONING Menu Screen
The TEST MODE PROVISIONING screen (Figure 21) is used
to configure the unit’s options for the test mode. To reach this
screen from the MAIN menu, type <S> to get into the STATUS
Screen and then type <T>. For each option, the display shows
the CURRENT" configuration as well as a NEW" field that
shows what the option can be changed to. Use <tab> or the ar-
row keys to advance to an option field. Use the <space> bar to
change the available options under the NEW" field.
9.2.5.1 Saving The Changed Options
After configuring the options, press <S> to save the new set-
tings. Note: If you enter <Esc> without saving, the system will give
a message asking if you want to save the new settings.
- WARNING -
If the craft terminal is disconnected without saving the changes, the
changes will be lost (unit does not save changes automatically).

Section 311-580-20B 030-101527 Rev. B
18 0407IBRB
Figure 19. Typical Circuit Status Screen - Dual Loopback
Westell B90-311580 CIRCUIT STATUS CLEI: T1S1ABTAAA
LVL: -13.0dBdsx 3115-80 LVL: 0.0dBdsx
FRMG: SF FRMG:
SIG: OK SIG:
TO FAC TO CPE
0dB LBO
LVL: -0.5dBdsx LVL: 0.0dBdsx
FRMG: SF Dual Loopback FRMG:
SIG: OK SIG:
SELECTIONS
^D) deactivate loopback
Enter selection or <Esc> to go back to main menu
Figure 20. Typical Circuit Status Screen - Facility Loopback with CPE-to-FAC REGEN Enabled
Westell B90-311580 CIRCUIT STATUS CLEI: T1S1ABTAAA
LVL: -0.5dBdsx LVL: 0.0dBdsx
FRMG: SF 3115-80 FRMG: UNF/UNK
SIG: OK SIG: AIS
TO FAC AIS TO CPE
REGEN
LVL: -0.5dBdsx Facility Loopback LVL: -8.0dBdsx
FRMG: SF FRMG:
SIG: OK SIG:
SELECTIONS
^C) operate CPE loopback
^D) deactivate loopback
Enter selection or <Esc> to go back to main menu
X
X
Figure 21. Test Mode Provisioning Menu Screen
Westell B90-311580 CLEI: T1S1ABTAAA
TEST MODE PROVISIONING MENU
Option Current New
>Test Pattern: 1:7 1:1
Framing for Pattern SF
Test Pattern to CPE ENABLED
Test Pattern to NET: DISABLED
User Pattern: 10111110
SELECTIONS
S) Save D) Set to default settings
Use <tab> to select option, <space> to change, or Esc to return to main menu

Section 311-580-20B
030-101527 Rev. B
19
0407IBRB
Figure 22. Event/Alarm Log Screen (Typical - Sample Only)
Westell B90-311580 CLEI: T1S1ABTAAA
EVENT/ALARM LOG Events 1 - 15 of 100
No. Date Time Event
1 2/28/00 13 : 00 : 00 MANUAL LOOP DOWN
2 2/28/00 12 : 50 : 00 MANUAL LOOP UP
3 2/28/00 12 : 60 : 15 REMOTE LOOP DOWN
4 2/28/00 12 : 05 : 00 REMOTE LOOP UP
5 2/28/00 12 : 02 : 30 MANUAL LOOP UP
6 2/28/00 12 : 02 : 00 CHANGED CPE REGEN OPTION
7 2/28/00 12 : 01 : 20 MANUAL LOOP DOWN
8 2/28/00 12 : 00 : 30 CHANGED FAC REGEN OPTION
9 2/28/00 11 : 02 : 50 CHANGED FAC REGEN OPTION
10 2/28/00 11 : 02 : 00 MANUAL LOOP UP
11 2/28/00 11 : 00 : 00 AIS FROM CPE CLEARED
12 2/28/00 10 : 02 : 15 AIS FROM CPE
13 2/28/00 10 : 02 : 00 LOS FROM CPE CLEARED
14 2/28/00 10 : 00 : 05 LOS FROM CPE
15 2/28/00 10 : 00 : 00 POWER UP
SELECTIONS
N) Next page P) Previous page C) Clear log ?) Help
Enter selection or <Esc> to go back to main menu
Field Parameter Default
TEST PATTERN 1:1
1:7
ALL ONES
USER (4-16 BITS)
FRAMING FOR PATTERN UNFRAMED
SF
ESF
TEST PATTERN TO CPE ENABLED
DISABLED
TEST PATTERN TO NET ENABLED
DISABLED
Table 8. 3115-80 Test Mode Parameters
9.2.5.2 The test mode is activated while in the STATUS screen
by using the <Ctrl><T> keys simultaneously. Additional ap-
plications of <Ctrl><T> will toggle the state of the test mode.
9.2.6 Event/Alarm Log Screen
9.2.6.1 The Event/Alarm Log screen is used to view various
events that occurred on the span during the monitoring period.
The log provides time-stamped entries for the most important
types of events such as alarm signal detection, loopback, PM
Registers cleared, Event/Alarm Log cleared, Clock setting, loss
of signal, power outages, and more. The Event/Alarm Log will
retain the 100 most recent events in non-volatile memory. The
Event/Alarm Log can be viewed locally via the craft interface
port. An example of a typical Event/Alarm Log screen is shown
in Figure 22. The Event/Alarm Log can also be retrieved re-
motely via TL1 commands.
9.2.6.2 To gain access to the Event/Alarm Log screen, type
<L> while in the Main Menu. The Event/Alarm Log appears.
To advance through the log, type <N> (next page), or <P>
(previous page), or <Esc>(to return to the MAIN Menu).
9.2.6.3 To clear all stored data in the Event/Alarm Log, type
<C>. The system will give a confirmation message prompting
if all data is to be cleared. Type <Y> for Yes or <N> for No.
9.2.7 SET CLOCK Menu Screen
9.2.7.1 The SET CLOCK screen, Figure 23, is used to set the
unit’s internal clock. To reach this screen from the MAIN menu,
type <C>. The unit is shipped from the factory with its clock set
to Central Standard Time.
9.2.7.2 To set the date or time, use the <tab> to select the
field, then type the new parameter in the highlighted box. To
save the changes, press <Enter>.
9.2.7.3 To return to the MAIN menu from this screen, press
the <Esc> key. The clock can be remotely set via TL1 com-
mands, using the SET-DAT command.
9.2.8 ALARM THRESHOLDS Screen
The ALARM THRESHOLDS screen allows the user to set vari-
ous performance monitoring thresholds for the different
parameters, illustrated above in Figure 24. An event will be re-
corded in the Event/Alarm log when any parameter threshold is
exceeded. A threshold setting of 0" will disable it.
9.2.9 REPORTS screen
The CRAFT port provides a means for downloading various re-
ports to a PC running HyperTerminal software. The menu
option for performing this function will be labeled RE-
PORTS", and will appear as part of the MAIN menu. Once
selected, the REPORTS" screen, Figure 25, will allow the user
to select from one of four options, labeled as follows:
1. Information Report - Provides all provisioning (including
Alarm Threshold) information about the unit.

Section 311-580-20B 030-101527 Rev. B
20 0407IBRB
Figure 23. Set Clock Menu Screen (Typical)
Westell B90-311580 CLEI: T1S1ABTAAA
SET CLOCK
Current Time
08/28/2003 11:50:23
New Time
08/25/2003 09:50:00
Use <tab> to select field, <return> to save, or <Esc> to return to main menu
Figure 24. ALARM THRESHOLDS Screen
Westell B90-311580 CLEI: T1S1ABTAAA
ALARM THRESHOLDS
PARAMETER 15-MINUTE 1−DAY
>
ES-L 25 250
SES-L 4 40
ESP-P 25 250
SESP-P 4 40
UASP-P 10 10
SELECTIONS
S) SAVE D) SET DEFAULT THRESHOLDS X) DISABLE All THRESHOLDS
NOTE: Setting a threshold to a value of 0 will disable it
Enter selection or ESC to go back to previous menu
2. Event Log Report - Provides all provisioning information
and a complete listing of all stored Event/Alarm Log
events.
3. Short PM Report - Provides all provisioning information,
and detailed PM information for the current 15-minute,
current hour and current day.
4. Long PM Report - Provides all provisioning information,
and a complete listing of all PM information stored in the
unit.
Reports Screen Download Procedure
1. Select Transfer," Capture Text" from the Hyper Terminal
drop down menu.
2. Enter a file name then select Start."
3. Select a report number 1," 2," 3," or 4" to capture data
from the SEND DATA TO LOG FILE" menu.
4. After download is complete, select Transfer," Capture
Text," and Stop" from HyperTerminal.
9.2.10 NOTE PAD Screen
The Note Pad screen provides a means for Craft personnel to log
notes about the circuit. See Figure 26. Each entry is date and
time stamped for future reference. Up to 15 notes can be en-
tered, with each note limited to 50 characters. Add, delete, and
edit selections allow the user to manage entries.
9.3 Remote Provisioning and Query via TL1
The NIU is capable of being provisioned and queried via TL1
commands. These TL1 commands and responses are trans-
ported via the Facility Data Link and do not require that the unit
be put in loopback. The TL1 instruction sequence is outlined in
Appendix C of this document.
9.3.1 Remote Provisioning via 16-Bit Commands
To initiate a remote provisioning session, the NIU is first put into
loopback. While in loopback, the test person sends the appropri-
ate provisioning code to the NIU. Each code consists of a 16-bit
pattern and can be unframed, SF or ESF framed. All codes must
be sent to the unit for minimum of five seconds. In order to see
a bit-error response from the unit, the code must be present for
a minimum of 10 seconds. The unit will respond to the code with
This manual suits for next models
1
Table of contents
Other Westell Network Card manuals