Delta CMC-EIP01 User manual

CMC-EIP01
EtherNet/IP Communication Card for
VFD-C2000
Operation Manual
CMC-0206120-01


EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
Warning
3This operation manual provides information on specifications, installation, basic operation, setup
and deails of the communication protocol.
3AC motor drive is a delicate electrical and electronic product. For the safety of operator and the
mechanical equipment, please allow professional electrical mechanics to do the trial run and
adjust parameters for you. Should there be any questions, please consult your local Delta
distributors. Our professional staff will be happy to help you.
3Please read this operation manual thoroughly and follow the instructions in case damage on the
device or injury on the operation staff occur.
Table of Content
1Introduction to CMC-EIP01 ....................................................................................................................3
1.1 Features ..........................................................................................................................................3
1.2 Specifications ..................................................................................................................................3
2Product Profile and Outline ...................................................................................................................4
2.1 Dimension .......................................................................................................................................4
2.2 Parts................................................................................................................................................4
2.3 LED Indicator ..................................................................................................................................5
2.4 RJ-45 PIN Definition........................................................................................................................5
2.5 Error Codes.....................................................................................................................................5
2.6 Trouble-shooting .............................................................................................................................6
3Installation and Wiring............................................................................................................................7
3.1 How to Install...................................................................................................................................7
3.2 How to Disconnect ..........................................................................................................................7
3.3 How to Connect to Network ............................................................................................................8
4Internal Register......................................................................................................................................9
4.1 Basic Registers (BR) (BR MODBUS Address Base = 0x0000).......................................................9
4.2 Explanations on BR.........................................................................................................................9
4.3 Alarm Register (AL) ( AL MODBUS Address Base = 0x0200) ......................................................10
4.4 Input Buffer Register (IN) (IN MODBUS Address Base = 0x0500) ...............................................10
4.5 Output Buffer Register (OUT) (OUT MODBUS Address Base = 0x0600).....................................10
4.6 Monitor Word Register (MW MODBUS Address Base = 0x2200).................................................10
4.7 Explanations on MW ..................................................................................................................... 11
4.8 Definitions of Parameter Address for VFD-C2000 Communication Protocol ................................12
4.9 Definitions of Parameter Address for Keypad ÙVFD-C2000 Communication Protocol ..............13
5MODBUS Communication....................................................................................................................14
CMC-EIP01 Operation Manual 1

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
6EtherNet/IP Communication Protocol ................................................................................................ 14
6.1 EtherNet/IP Specifications Supported .......................................................................................... 14
6.2 EtherNet/IP Communication Parameter ....................................................................................... 15
6.3 Services and Objects Supported ..................................................................................................15
6.4 CIP Comman Status Code ........................................................................................................... 15
6.5 Error Code for Monitor Request ................................................................................................... 15
7Software Setting................................................................................................................................... 16
7.1 Setting up Communication and Searching for Modules in DCISoft .............................................. 17
7.2 Basic Settings............................................................................................................................... 22
7.3 Network Settings .......................................................................................................................... 24
7.4 Alarm Setting ................................................................................................................................ 26
7.5 IP Filter ......................................................................................................................................... 27
7.6 Parameter List .............................................................................................................................. 28
7.7 Monitor.......................................................................................................................................... 29
7.8 Security......................................................................................................................................... 30
7.9 Returning to Default Settings........................................................................................................ 31
8Application Examples.......................................................................................................................... 32
8.1 Write Frequency of VFD-C2000 by DVP-SV + DVPEN01-SL through Network (MODBUS TCP) 32
8.2 Monitor VFD-C2000 Parameters On-Line through DCISoft/Web ................................................. 33
8.3 Set up and Clear Password.......................................................................................................... 35
8.4 IP Filter Protection ........................................................................................................................ 38
8.5 E-Mail ........................................................................................................................................... 40
8.6 Keypad Operation (1) ................................................................................................................... 42
8.7 Keypad Operation (2) ................................................................................................................... 43
8.8 Keypad Operation (3) ................................................................................................................... 45
8.9 EtherNet/IP Application................................................................................................................. 47
Appendix A: EtherNet/IP Services and Objects....................................................................................... 48
A.1 Objects Supported........................................................................................................................ 48
A.2 Data Formates Supported ............................................................................................................ 48
A.3 Identity Object (Class Code: 0x01)............................................................................................... 48
A.4 Message Router Object (Class Code: 0x02) ................................................................................ 49
A.5 Assembly Object (Class Code: 0x04)........................................................................................... 49
A.6 Connection Manager Object (Class Code: 0x06) ......................................................................... 49
A.7 BR Object (Class Code: 0x64) ..................................................................................................... 50
A.8 AL Object (Class Code: 0x65) ...................................................................................................... 50
A.9 MW Object (Class Code: 0x66) ....................................................................................................50
A.10 TCP/IP Interface Object (Class Code: 0xF5)................................................................................ 51
A.11 Ethernet Link Object (Class Code: 0xF6) ..................................................................................... 52
CMC-EIP01 Operation Manual
2

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
1 Introduction to CMC-EIP01
Thank you for choosing Delta CMC-EIP01 communication card. To ensure correct installation and operation
of the product, please read this operation manual carefully before using it.
CMC-EIP01 is an EtherNet/IP communication card, supporting EtherNet/IP protocol and one MODBUS TCP
protocol connection and able to conduct remote setup and monitoring through DCISoft or Web. It also
supports remote monitoring by using SCADA (Supervisory Control And Data Acquisition) software or human
machine interface. Sending e-mail, IP filter, on-line monitoring and webpage functions are also provided by
CMC-EIP01. In addition, by auto MDI/MDI-X function, no jumper cable is required when using the network
cable.
1.1 Features
zAuto-detects transmission speed 10/100 Mbps
zAuto MDI/MDI-X
zSupports MODBUS TCP slave communication protocol (1 connection)
zE-mail alarm
zWeb browser setup and on-line monitoring
zSupports EtherNet/IP explicit message Class 3
1.2 Specifications
Specification
Connector RJ-45 with Auto MDI/MDIX
Number of ports 1 Port
Interface Ethernet
Cable Category 5e shielding 100M
Speed 10/100 Mbps Auto-Detect
ICMP, IP, TCP, UDP, DHCP, SMTP, HTTP, MODBUS TCP, EtherNet/IP, Delta
Configuration
Protocol
Environment
Noise immunity
ESD (IEC 61800-5-1, IEC 61000-4-2)
EFT (IEC 61800-5-1, IEC 61000-4-4)
Surge Teat (IEC 61800-5-1, IEC 61000-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 61000-4-6)
Operation -10°C ~ 50°C (temperature), 90% (humidity)
Storage -25°C ~ 70°C (temperature), 95% (humidity)
Vibration/shock
immunity
International standard: IEC 61800-5-1, IEC 60068-2-6/IEC 61800-5-1, IEC
60068-2-27
Standards
Electrical Specification
Power supply
voltage 5 VDC
Power
consumption 0.8 W
Insulation voltage 500 VDC
Weight 25g
CMC-EIP01 Operation Manual 3

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
2 Product Profile and Outline
2.1 Dimension
Unit: mm [inch]
2.2 Parts
c Screw fixing hole g RJ-45 connection port
d Positioning hole h POWER indicator
e AC motor drive connection port i Fool-proof groove
f LINK indicator
CMC-EIP01 Operation Manual
4

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
2.3 LED Indicator
LED Status Indication How to correct
On Power supply in normal
status --
POWER Green
Off No power supply Check the power supply.
On Network connection in
normal status --
Flashes Network in operation --
LINK Green
Off Network not connected Check if the network cable is
connected.
2.4 RJ-45 PIN Definition
RJ-45 sketcch PIN Signal Definition
1 Tx+ Positive pole for data transmission
2 Tx- Negative pole for data transmission
3 Rx+ Positive pole for data receiving
4 -- N/C
5 -- N/C
6 Rx- Negative pole for data receiving
7 -- N/C
8 -- N/C
2.5 Error Codes
ID Code Definition
75 ECFF Incorrect default setting
76 ECiF Serious internal error
80 ECEF Ethernet connection error
81 ECto Communication timeout between CMC-EIP01 and VFD-C2000
Checksum error in the communication between CMC-EIP01 and
VFD-C2000
82 ECCS
83 ECrF Reset CMC-EIP01 to default setting
85 ECo1 Exceeds max. number of communications in EtherNet/IP
86 ECiP IP error
87 EC3F Mail alarm
CMC-EIP01 Operation Manual 5

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
2.6 Trouble-shooting
Abnormality Cause How to correct
Check if the AC motor drive is powered and the
power supply is in normal status.
AC motor drive not powered
POWER LED
off CMC-EIP01 not connected to
AC motor drive
Make sure CMC-EIP01 is tightly connected to
AC motor drive.
CMC-EIP01 not connected to
network
Make sure the network cable is correctly
connected to the network.
LINK LED off Poor contact to RJ-45
connector
Make sure RJ-45 connector is connected to
Ethernet port.
CMC-EIP01 not connected to
the network
Make sure CMC-EIP01 is connected to the
network.
No
communication
Card found PC and CMC-EIP01 in
different networks and
blocked by firewall.
Search by IP or set up relevant settings by the
keypad on AC motor drive.
CMC-EIP01 not connected to
network
Make sure CMC-EIP01 is connected to the
network.
Incorrect communication
setting in DCISoft
Make sure the communication setting in DCISoft
is set to Ethernet.
Fail to open
CMC-EIP01
setup page PC and CMC-EIP01 in
different networks and
blocked by firewall
Conduct the setup by the keypad on AC motor
drive.
Able to open
CMC-EIP01
setup page but
fail to utilize
webpage
monitoring
Incorrect network setting in
CMC-EIP01
Check if the network setting for CMC-EIP01 is
correct. For the Intranet setting in your company,
please consult your IT staff. For the Internet
setting in your home, please refer to the network
setting instruction provided by your ISP.
Incorrect network setting in
CMC-EIP01
Check if the network setting for CMC-EIP01 is
correct.
Fail to send
e-mail
Incorrect mail server setting Please confirm the IP address for SMTP Server.
CMC-EIP01 Operation Manual
6

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
3 Installation and Wiring
In this section, we illustrate how to connect CMC-EIP01 to VFD-C2000 and the network.
3.1 How to Install
How to connect CMC-EIP01 to VFD-C2000 series AC motor drive:
zSwitch off the power supply of VFD-C2000.
zOpen the front cover of VFD-C2000.
zPlace the insulation spacer into the positioning pin at Slot 1 (see [Figure 1]) and aim the two holes on
the PCB at the positioning pin. Press the pin to clip the holes with the PCB (see [Figure 2]).
zScrew up at torque 6~8 kg-cm (5.21~6.94 in-lbs) after the PCB is clipped with the holes (see [Figure
3]).
Slot 1Slot 2
Slot 3
[Figure 1] [Figure 2] [Figure 3]
3.2 How to Disconnect
How to disconnect CMC-EIP01 from VFD-C2000:
zSwitch off the power of VFD-C2000.
zOpen the front cover of VFD-C2000.
zRemove the two screws (see [Figure 1]).
zTwist open the card clip and insert the slot type screwdriver to the hollow to prize the PCB off the card
clip (see [Figure 2]).
zTwist open the other card clip to remove the PCB (see [Figure 3]).
[Figure 1] [Figure 2] [Figure 3]
CMC-EIP01 Operation Manual 7

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
3.3 How to Connect to Network
Connect CMC-EIP01 to the Ethernet hub by CAT-5e pair twisted wire. Since CMC-EIP01 has auto
MDI/MDIX function, so CAT-5e does not require jumper cable.
Network structure of PC and CMC-EIP01:
Note:
When operating VFD-C2000 through CMC-EIP01 on the network, set the controller of VFD-C2000 to
CMC-EIP01 first.
Parameter settings:
Parameter Set value Function
00-20 8 Set the source of frequency command to “CMC-EIP01”
00-21 5 Set the source of control to “CMC-EIP01”
09-30 0 Communication decode way
CMC-EIP01 Operation Manual
8

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
4 Internal Register
4.1 Basic Registers (BR) (BR MODBUS Address Base = 0x0000)
BR# Attribute Content Definition
#0 R Model name System defined and read only.
Model code of CMC-EIP01: H’0204
#1 R Firmware version In hex form, displaying the current firmware version
#2 R
Release date of the
version In hex form
#6 R VFD-C2000 station No. 1~254
#11 R
MODBUS communication
timeout Default: 50 (ms)
#13 R/W
Network keep alive time
(TCP/IP) Default: 30 (s)
4.2 Explanations on BR
BR#0: Model Name
Explanations:
Model code of CMC-EIP01 = H’0204
BR#1: Firmware Version
Explanations:
Displaying the firmware version of CMC-EIP01 in hex form, e.g. H’0100 indicates version V1.00.
BR#2: Release Date of the Version
Explanations:
Displaying the release date of the version in hex form, e.g. H’0101 indicates January 1.
BR#6: VFD-C2000 Station No.
Explanations:
Station No. of VFD-C2000 drive. Range: 1 ~ 254
BR#11: MODBUS Communication Timeout
Explanations:
For setting up the communication timeout (ms) in MODBUS TCP mode. Default: 50ms.
BR#13: Network Keep Alive Time (TCP/IP)
Explanations:
For setting the network keep alive time (s). Range: 10 ~ 65,535; Default: 30s. If the connection idle time
exceeds the keep alive time, CMC-EIP01 will disconnect the idling connection.
CMC-EIP01 Operation Manual 9

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
4.3 Alarm Register (AL) ( AL MODBUS Address Base = 0x0200)
AL# bit in each AL Attribute Function Explanation
bit 15 R Function enabling flag bit 15 = 1 ÆFunction enabled
bit 15 = 0 ÆFunction disabled
bit 4 ~ bit14 R Reserved
bit 2~ bit 3 R Type of triggered event
bit 3 bit 2
Reserved 0 0
Trigger e-mail 0 1
Reserved 1 0
Reserved 1 1
bit 1 R Status of trigger bit 1 = 0 ÆNot yet triggered
bit 1 = 1 ÆAlready triggered
#0~#15
bit 0 R Type of trigger bit 0 = 0 ÆTriggered by software
bit 0 = 1 ÆTriggered by hardware
4.4 Input Buffer Register (IN) (IN MODBUS Address Base = 0x0500)
IN# Attribute Content Explanation Default Latched
#0~#15 R/W
Buffer register for
input data EtherNet/IP input data 0 No
Symbol:
R – Read only; R/W – Can be read and written
Explanations:
The input buffer register sends the input data to the Ethernet. These IN correspond to addresses 0x2100 ~
0x210F in VFD-C2000 and total 32 words.
4.5 Output Buffer Register (OUT) (OUT MODBUS Address Base = 0x0600)
OUT# Attribute Content Explanation Default Latched
#0~#2 R/W
Buffer register for
output data EtherNet/IP output data 0 No
Symbol:
R – Read only; R/W – Can be read and written
Explanations:
The output buffer register sends the output data to VFD-C2000. These OUT correspond to addresses
0x2000 ~ 0x2002 in VFD-C2000 and total 6 words.
4.6 Monitor Word Register (MW MODBUS Address Base = 0x2200)
MW# Attribute Content Explanation
#0 R Monitor function bit 15 = 1 ÆCache mode enabled
bit 15 = 0 ÆCache mode disabled
The low byte in odd MW records the station No. of
device to be monitored, and high byte records the
number of data to be monitored. Every MW holds
one monitored register. The even MW records the
address of register.
#1~#32 R/W
Station No. and device
address to be monitored
Every MW records one value monitored in a
register.
#201~#300 R Value monitored
#301~#307 R Status monitored Every MW records the status of 16 registers.
1: Normal; 0: Abnormal
CMC-EIP01 Operation Manual
10

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
4.7 Explanations on MW
MW#0: Monitor Function
Explanations:
Default: H’8010
MW#1~MW#32: Station No. and Device Address to be Monitored
Explanations:
The low byte in odd MW records the station No. of device to be monitored, and high byte records the
number of data to be monitored. Every MW holds one monitored register. The even MW records the address
of register.
MW#201~MW#300: Value Monitored
Explanations:
Every MW records one value monitored in a register.
MW201 MW202 MW203 … MW300
Device 1 Device 2 … Device 100
MW#301~MW#307: Status Monitored
Explanations:
Every MW records the status of 16 registers. 1: Normal; 0: Abnormal
B15 … B1 B0
MW301 Device 16 … Device 2 Device 1
B15 … B1 B0
MW302 Device 32 … Device 18 Device 17
.
.
.
.
.
.
.
.
.
.
B15 … B1 B0
MW307 Device 32 … Device 18 Device 17
CMC-EIP01 Operation Manual 11

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
4.8 Definitions of Parameter Address for VFD-C2000 Communication Protocol
Parameter content Address Definition
Parameter set in
VFD-C2000 GGnnH GG is the parameter group; nn is the parameter number.
Ex: Parameter 04-01 is indicated by 0401H.
Commands to
VFD-C2000 2000H bit0 ~ 3 0: No function
1: Stop
2: Run
3: Enable JOG
bit4 ~ 5 00B: No function
01B: Forward command
10B: Reverse command
11B: Change direction command
bit6 ~ 7 00B: 1st acceleration/deceleration section
01B: 2nd acceleration/deceleration section
10B: 3rd acceleration/deceleration section
11B: 4th acceleration/deceleration section
bit8 ~ 11 0000B: Main speed
0001B: 1st speed section
0010B: 2nd speed section
0011B: 3rd speed section
0100B: 4th speed section
0101B: 5th speed section
0110B: 6th speed section
0111B: 7th speed section
1000B: 8th speed section
1001B: 9th speed section
1010B: 10th speed section
1011B: 11th speed section
1100B: 12th speed section
1101B: 13th speed section
1110B: 14th speed section
1111B: 15th speed section
bit12 1: Enable bit6 ~ 11
bit13 ~ 14 00B: No function
01B: The command is operated by keypad.
10B: The command is operated by parameter setting
(00-21)
11B: Change the operational source of the command
bit15 Reserved
2001H Frequency command
2002H bit0 1: E.F. = ON
bit1 1: Reset command
CMC-EIP01 Operation Manual
12

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
Parameter content Address Definition
Commands to
VFD-C2000 2002H bit2 1: External interruption (B.B) = ON
bit3~5 Reserved
Monitor VFD-C2000
status 2100H Error code: Refer to parameter 06-17 ~ 06-22
2119H bit0 1: Forward running command
bit1 1: Running status
bit2 1: JOG command
bit3 1: Reverse command
bit4 1: Reversing status
bit8 1: Main frequency comes from communication interface
bit9
1: Maini frequency comes from analog/external terminal
signal input
bit10 1: The command is operated by communication
interface
bit11 1: Lock the parameter
bit12 1: Enable parameter copy function in keypad
bit13~15 Reserved
2102H Frequency command (F)
2103H Output frequency (H)
2104H Output current (AXXX.X)
2105H DC bus voltage (UXXX.X)
2106H Output voltage (EXXX.X)
2107H Current execution speed of the multi-section command
2109H Counting value
2116H Multi-function display (parameter 00-04)
211BH Max. frequency
2200H Feedback signal %
2201H Reserved
2203H AVI percentage
2204H ACI percentage
2205H AUI percentage
2206H Temperatuer of IGBT
2207H Temperature of capacitor
2208H Status of digital input
2209H Status of digital output
4.9 Definitions of Parameter Address for Keypad ÙVFD-C2000 Communication Protocol
Address No. on keypad Definition
- 09-00 VFD-C2000 Communication Address
2501H 09-61 CMC-EIP01 Firmwrare Version
2502H 09-62 CMC-EIP01 Product Code
2505H 09-63 CMC-EIP01 Fault
CMC-EIP01 Operation Manual 13

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
Address No. on keypad Definition
2520H 09-75
IP Configuration
0 – Static
1 – DHCP
2521H 09-76 IP Address 1
2522H 09-77 IP Address 2
2523H 09-78 IP Address 3
2524H 09-79 IP Address 4
2525H 09-80 Net Mask 1
2526H 09-81 Net Mask 2
2527H 09-82 Net Mask 3
2528H 09-83 Net Mask 4
2529H 09-84 Gateway 1
252AH 09-85 Gateway 2
252BH 09-86 Gateway 3
252CH 09-87 Gateway 4
252DH 09-88 Password Low (0~255)
252EH 09-89 Passwrod High (0~255)
252FH 09-90 Return to Factory Setting
2530H 09-91
CMC-EIP01 Setting
bit 0: Enable IP Filter
bit 1: Internet parameter enable
bit 2: Login password enable
2531H 09-92
CMC-EIP01 Status
bit 0: Password enable
5 MODBUS Communication
Function codes supported:
Code Definition
0x03 Read register in VFD-C2000
0x06 Write single register in VFD-C2000
0x10 Write multiple registers in VFD-C2000
6 EtherNet/IP Communication Protocol
6.1 EtherNet/IP Specifications Supported
zTrigger type: Cyclic
zTransport class: 1
zApplication behavior: Exclusive owner
Parameter OÆT TÆO
Data size Fixed Fixed
Connection type Multicast, Point to Point Multicast, Point to Point
CMC-EIP01 Operation Manual
14

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
6.2 EtherNet/IP Communication Parameter
zInput buffer register: In Assembly Instance = 101, Width = 16 bits, Size = 16
zOutput buffer register: Out Assembly Instance = 100, Width = 16 bits, Size = 3
zConfiguration: Instance = 102, Width = 8 bits, Size = 0
6.3 Services and Objects Supported
See Appendix A.
6.4 CIP Comman Status Code
Status
code Status Definition
0x 00 Success Requested service is successfully executed.
0x 01 Connection failure Connected service fails.
Node in the program cannot identify the definition or syntax of a
path segment. When this error takes place, the execution of
program will be terminated.
0x 04 Path segment error
The path is related to object type, but the node in the program
does not cover or cannot identify the type or structure of the
object. When this error takes place, the execution of program
will be terminated.
0x 05 Path destination unknown
0x 08 Service not supported The object does not support required service or has not yet
defined the service.
0x 0E Attribute not settable Receives request of modifying unchangeable attribute
0x 13 Not enough data Receives insufficient data and therefore cannot execute
command
0x 14 Attribute not supported Does not support requested attribute
The received data exceeds what the command execution
requires.
0x 15 Too much data
The requested parameter is invalid, indicating that the
parameter does not fit the definition of the requirement, or the
requirement has been defined in “Application Object
Specification”.
0x 20 Invalid parameter
The size of the path transmistting requested service cannot
afford the request to the object or cover too much route data.
0x 26 Path size invalid
6.5 Error Code for Monitor Request
Status
code
Extended status
code Definition
0x00 -The execution of service is successful.
0x01 0x0100
The connection is in progress or the connection is re-openned.
The code will be sent back when the source is trying to establish a
connection to the target but the target has already been connected.
0x01 0x0103
Does not support the combination of this transmission type and trigger.
The target does not support the defined combination of transmission type
and trigger. The router will not teminate the connection, only the target end
has to send back this extended status code.
0x01 0x0106
Clash of control right
A connection takes the control, blocking the establishment of other
connections. When this device occupies the connection in this way, only
one connection will be allowed to control this device.
0x01 0x0107 Cannot find the corresponding target to connect
0x01 0x0108
Invalid network connection parameter
When the application program in the target does not support the defined
connection type, connection level, or there are too many users, the
extended status code will be sent back. Only the node on target has to send
back the extended status code.
CMC-EIP01 Operation Manual 15

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
Status Extended status Definition
code code
0x01 0x0109
Invalid setting of the size of the on-line data exchange zone
This device does not support the setting of the current data exchange
zone.The setting can be too big or too small.
0x01 0x0111 RPI setting not supported
0x01 0x0113
The number of connections exceeds the maximum.
No further connections are able to connect to this device.
0x01 0x0114
The company ID does not match product code.
The product code or company ID marked in the electronic key logic section
does not match the record in the target device.
0x01 0x0115
Inconsistent product type
The product type marked in the electronic key logic section does not match
the record in the target device.
0x01 0x0116
Inconsistent version
The primary and secondary revised versions marked in the electronic key
logic section do not match the record in the target device.
0x01 0x0315
Invalid section exists in the path.
The type or value of a section in the path is invalid. When the device cannot
interpret the path, it will respond with this extended status code.
Cause of this error: Unidentifiable path type, unexpected section type or
other problems existing in the path.
7 Software Setting
This section gives instructions on how to set up the parameters of CMC-EIP01 by using Delta’s
Communication Software, DCISoft, and explanations on each setup page. Before you open the setup pages,
you have to select “Ethernet” as the communication type. Next, you can search by “Search” or “IP search”
function. CMC-EIP01 is set up by UDP port 20006; therefore, be aware of relevant settings of the firewall.
The PC is connected to VFD-C2000 with CMC-EIP01 through cable or hub:
CMC-EIP01 Operation Manual
16

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
7.1 Setting up Communication and Searching for Modules in DCISoft
Communication Setting
1. Open DCISoft on the PC and select “Tools” => “Communication Setting”.
2. Select “Ethernet” for the communication setting.
CMC-EIP01 Operation Manual 17

EtherNet/IP Communication Card for VFD-C2000: CMC-EIP01
Search
1. Click the “Search” icon in DCISoft to search for all Delta’s Ethernet products on the
network by search function. The modules found are displayed in the left-hand side column,
and the device list of all modules is displayed on the right-hand side column.
2. Click the module you need in the left-hand side column to display the device list of the
module in the right-hand side column. Double click the device on the right-hand side
column to enter the setup page of the device.
CMC-EIP01 Operation Manual
18
Table of contents
Other Delta Network Card manuals
Popular Network Card manuals by other brands

Huawei
Huawei CR-NETB Specifications

ZyXEL Communications
ZyXEL Communications G-162 release note

Cisco
Cisco ONS 15454 Series Software feature and configuration guide

Palm
Palm CompactFlash 10/100 Quick installation guide

Compaq
Compaq Wireless LAN 100 specification

IP-Link
IP-Link iLAN-100 installation guide