Western Airconditioning MU ECHOS A User manual

MU ECHOS
Water/water chiller and heat pump 6÷48
General
Water/Water chillers and heat pumps with hermetic scroll
compressor.
Configurations
HP: Reversible heat pump
A+: Energy efficiency class A+
LE: For connection to remote evaporator
LC: For connection to remote condenser
LN: Low sound level
Optional pump-/tank module
Quick facts
►Eco-friendly cooling
►High EER
►Limited space requirements
►Very low noise emissions
►Fully accessible
►Designed for radiating panels
►Split version available

2
MU ECHOS A
INDEX
Technical features 3
MU ECHOS - technical data 6
MU ECHOS - operating limits 8
MU ECHOS - electrical data 9
MU ECHOS - cooling capacity 10
MU ECHOS - heating capacity 12
MU ECHOS/LC - cooling capacity 14
MU ECHOS/LC/HP - heating capacity 16
MU ECHOS/LE - cooling capacity 18
MU ECHOS/LE/HP - heating capacity 20
MU ECHOS - noise levels 22
MU ECHOS/LN - noise levels 22
Dimensional drawing 23
Installations recommendations location 51

3
MU ECHOS A
TECHNICAL FEATURES
MU ECHOS
Water/water chiller and heat pump with scroll compressors
and plate heat exchangers.
STRUCTURE
The units are designed to be installed from inside. The struc-
ture is in steel sheet coated with epoxy-polyester powder
paint, with removable panels insulated with sound absorbing
material. The sizes 6, 8 and 11 are painted with RAL 7035
colour, suited for installation on the wall, the sizes from 16 to
48 are painted in RAL 7035 colour for installation on the floor.
COMPRESSOR
Rotary screw hermetically sealed scroll type compressors with
internal thermal protection, heater for the crankcase, suppor-
ted by rubber antivibration mounts to reduce the vibrations
transmission to the unit.Cooling circuitComprende: feed inlets,
dehydrating filter, thermostatic expansion valve, high and low
pressure switches. Units of sizes from 16 to 48 are also provi-
ded with safety valve and fluid sight glass.
EVAPORATOR
Brazed plate heat exchanger in stainless steel AISI 316 insulated
against condensate, temperature probe on the vane-operated
flow switch antifreeze protection (installed on sizes 6, 8 and 11
and supplied with the unit for the other sizes).
CONDENSER
Brazed plate condenser in stainless steel AISI 316 sized to
operate with well water (in/out 15/30 °C). The chiller units can
be fitted upon request with condenser sized to operate with
tower water (in/out 30/35°C).
ELECTRICAL PANEL
The panel consists of: main disconnect switch, automatic dis-
connect switch for the main and auxilliary power circuit pro-
tection, compressor remote disconnect switch, on/off digital
signal input contact, microprocessor for parameter setting
control of the following functions:
• Regulation of water temperature;
• Control of set-point self-regulation;
• Anti-freeze protection
• Compressor timing
• Alarm signalig
• Alarm reset
• Cumulative alarm contact for remote signaling;The control
display shows the following information:
• Ingoing and outgoing water temperature;
• Currently set temperature and differential
• Alarm description
• Operation hour counter;
CONTROL AND SAFETY DEVICES
The units are equipped with:
• Manual reset high pressure switch
• Controlled manual reset low pressure switch;
• High pressure safety valve (except for the 6, 8 and 11 sizes,
basic and /HP version);
• Water temperature probe on the user side, installed on the
heat exchanger inlet;
• Antifreeze probe on the user side heat exchanger outlet;
• Vane-operated mechanical flow switch fitted on sizes 6, 8
and 11 and supplied with the unit for the other sizes;
• Compressor overtemperature internal protection.
TESTING
All units are factory-tested and supplied complete with oil and
refrigerant (except for the LE, LE/HP, LC and LC/HP units).
VERSIONS
Check the table with the available configurations for any inter-
ferences between one option and the other.
The basic version constists of a cooled-water water chiller.
/HP:
reversible heat pump
Besides the components of the MU ECHOS, the cooling circuit
is equipped with 4-way inversion valve and a second thermo-
static expansion valve. The hydraulic circuit consists of a pres-
sure switch valve, a bypass solenoid valve and a second vane-
operated water flow switch. These components are already
installed on the 6, 8 and 11 sizes and for the other sizes they
are supplied with in the kit). The electrical panel has a digital
input contact for summer/winter switching.
/LE:
motocondensing unit
Motocondensing unit: The unit is designed to operate with an
air-cooled evaporator therefore it does not have a heat exchan-
ger on the user side or a thermostatic valve (can be supplied in
the kit upon requeast). The unit is loaded with nitrogen instead
of refrigerant
/LE /HP
reversible motocondensing unit
The unit is designed to operate with a remote air-cooled eva-
porator/condenser therefore it does not have a heat exchanger
on the user side or a thermostatic valve suited for chiller opera-
tion mode(can be supplied in the kit upon requeast). The unit
has a fluid receiver sized for the split unit supplied by Blue Box
and the thermostatic valve for the heat pump operation mode.
The unit is loaded with nitrogen instead of refrigerant
/LC
motoevaporating unit
The unit has no heat exchanger on the source side in order to
allow connection to a remote air-cooled condenser. The unit is
loaded with nitrogen instead of refrigerant
/LC /HP
reversible motoevaporating unit
The unit has no thermostatic valve for heat pump operation

4
MU ECHOS A
mode and no heat exchanger on the source side in order to
allow connection to a remote air-cooled condenser/evaporator.
The unit has a fluid receiver sized for the remote condenser
supplied by Blue Box.
The unit is loaded with nitrogen instead of refrigerant.
/LN
low-noise unit
The sizes 6, 8 and 11 with this outfit require the replacement
of the standard sound absorbing material with a multi-layer
acoustic insulation of high impedance.
The sizes from 16 to 48 require the installation of a sound-
proof cover on the compressor. This outfit can be combined
with all aforementioned versions of the unit
HYDRAULIC SYSTEM OPTIONS
The unit basic version has no circulation device or pump instal-
led (except for the 6, 8 and 11 sizes). All the outfits (except for
LE and LE/HP) can be equipped upon request with one of the
following hydraulic modules:
/ST 1P
Besides the standard components installed, the unit has a
circulation pump. This version is not suitable for the 6, 8 and
11 sizes .
/ST 1PS
Besides the standard components installed, the unit has an
inertial insulated storage tank and a circulation pump. The sizes
6, 8, 11 and from 16 to 48 of the HP version have the safety
valve and the expansion vessel fitted as standard.
This version is standard for the sizes 6, 8 and 11 while for the
other sizes it must be requested when ordering.
STANDARD EQUIPMENT
•Flowswitch(installedformodels6,8,11,equipedbutnot
installed on other models)
•Summer/Wintermodeselectionondigitalinput(tobespe-
cified with the order)
•RemoteOn/Offcontroldigitalinput
•Self-adaptablecontrollogic
ACCESSORIES
REFRIGERANT CIRCUIT ACCESSORIES
• Condensing cntrl. with pressure control valve for well water
(standard on HP version)
• Condensing control with pressure control valve for tower
water
• Fitting for tower water (in-out 30/35 °C)
• Pressure gauges
• Liquid line shut-off valve
• Liquid line solenoid valve
• Electronic expansion valve
• Brine Kit
HYDRAULIC CIRCUIT ACCESSORIES
•Automaticfillingkitwithpressuregauge(onlyfor1PSver-
sion)
• Expansion vessel (for ST 1PS version only; standard on ST
1PS/ HP version)
• Water safety valve (ST 1PS version only, standard on ST 1PS/
HP version)
•Upwardhydrauliccircuitconnections
ELECTRICAL ACCESSORIES
•Powersupply:400/3+N/50
•Setpointcompensatedaccordingtoexternalairtemperature
•Remotecontrolterminal
•Userinterface
•RS485serialinterface
•Singleoperationvoltage-freecontacts
•Electronicsoft-starter
VARIOUS ACCESSORIES
•Rubberantivibrationmounts
“BRINE KIT”ACCESSORY
It is applied if the evaporator output temperature is included
within +3°C and -8°C. It consists in a higher thermal insulation
of the exchanger and piping, a specific calibration of the low
pressure switches and of the anti-freeze alarm, and dimensio-
ning check of the mechanical thermostatic valve.
If it is not included in the set-up, the “Check condensation”
accessory must be added.
ELECTRONIC THERMOSTATIC VALVE
L’utilizzo di questo accessorio è particolarmente indicato sulle
unità che si trovano ad operare in condizioni di carico termico
molto variabile o di modalità di funzionamento variabili, come
nel caso della gestione congiunta di condizionamento e pro-
duzione di acqua ad alta temperatura. L’impiego della valvola
termostatica elettronica infatti permette di:
• massimizzare lo scambio termico all’evaporatore
• minimizzare i tempi di risposta alle variazioni del carico e di
condizioni operative
• ottimizzare la regolazione del surriscaldamento
• garantire la massima efficienza energetica
SELF-ADAPTABLE REGULATION LOGIC
This function allows the unit control to dynamically vary the
outlet water set point according to the stop and functional
cycles of the machine: in practice, by increasing and reducing
the water outlet temperature, the control avoids that compres-
sor start-ups are too close in time, decreasing the number of
peaks and protecting the unit components
REMOTE ON/OFF FROM DIGITAL INPUT
This function is standard on all units and consists in a remote
contact that allows to switch on and off the machine through a
signal that can be taken inside the building by a BMS (Building
Management System) system.

5
MU ECHOS A
SUMMER/WINTER SELECTION FROM DIGITAL
INPUT
This function is standard on all heat pumps. When the unit is
switched on, a functioning mode must be set, which can be
either the heat pump or the chiller one. Through this remote
contact, the functioning mode can be modified even inside
the building and without a direct access to the microprocessor
control.
FILLING SYSTEM WITH MANOMETER
This accessory allows the automatic load of the hydraulic sys-
tem, the adjustment of the correct working pressure, which
can always be verified by using the manometer, and enables
the continuous maintenance of such pressure, reintegrating
the missing water if necessary.
RS-485 INTERFACE
The growing diffusion of both domotic and BMS (Building
Management System) systems led to the integration of all the
system components under an only supervision. To respond to
this request, the unit can be equipped with a serial board that
allows the correct machine integration in the “building-sys-
tem”, by using MODBUS or CAREL communication protocols..
REMOTE CONTROL USER TERMINAL
Intended for a professional user, it consists in a faithful re-
production of the control panel, from where the unit can be
completely set and all its parameters visualised on the display.
Insertion of passwords, which enable different access levels,
are required to access the parameters.
The type of terminal depends on the control installed on the
unit
USER INTERFACE µAD
By using a simple and intuitive interface, this device allows to
carry out the following main functions:
• Switching on and off the unit
• The unit function mode switch-over from heat pump to
chiller and vice versa
• Enabling the sleep function
• The weekly timer thermostat function with automatic ON/
OFF management of the unit
• Displaying unit functioning conditions
SOFT-STARTER
Blue Box units adopt all the required functioning set-ups and
logics to minimise peak currents. The Soft-Starter accessory
allows a further 40% reduction of normal current peaks,
through an electronic control of the electric motor start-up.
COMPENSATION OF THE SET-POINT according to the external
air temperature
The unit microprocessor control can compensate the set point
in a dynamic way, on variation of the external air temperature.
The compensation can be positive or negative: with positive
compensation, on increase of the air temperature the functio-
ning set also increases. With negative compensation on in-
crease of the air temperature the set decreases. Compensation
can be made either on the summer set point or on the winter
set point (heat pumps).
By default, both summer and winter negative compensation is
set, but this configuration can be modified from the micropro-
cessor keyboard. Unless otherwise specified, default values are
indicated in the graphics below.
SUMMER COMPENSATION - POSITIVE
12 / 7°C
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
12 / 7°C
35 / 40°C
SET POINT 1
SET POINT 2
SET POINT 2
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
30 / 40°C
SET POINT 2
0°C
T1 T2
15°C
40 / 45°C
5°C
40 / 45°C
SET POINT 2
SET POINT 1
0°C
T1 T2
15°C
5°C
External air temperature
SUMMER COMPENSATION - NEGATIVE
12 / 7°C
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
12 / 7°C
35 / 40°C
SET POINT 1
SET POINT 2
SET POINT 2
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
30 / 40°C
SET POINT 2
0°C
T1 T2
15°C
40 / 45°C
5°C
40 / 45°C
SET POINT 2
SET POINT 1
0°C
T1 T2
15°C
5°C
External air temperature
WINTER COMPENSATION - POSITIVE
12 / 7°C
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
12 / 7°C
35 / 40°C
SET POINT 1
SET POINT 2
SET POINT 2
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
30 / 40°C
SET POINT 2
0°C
T1 T2
15°C
40 / 45°C
5°C
40 / 45°C
SET POINT 2
SET POINT 1
0°C
T1 T2
15°C
5°C
External air temperature
WINTER COMPENSATION - NEGATIVE
12 / 7°C
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
12 / 7°C
35 / 40°C
SET POINT 1
SET POINT 2
SET POINT 2
SET POINT 1
25°C
T1 T2
35°C
17 / 12°C
5°C
30 / 40°C
SET POINT 2
0°C
T1 T2
15°C
40 / 45°C
5°C
40 / 45°C
SET POINT 2
SET POINT 1
0°C
T1 T2
15°C
5°C
External air temperature

6
MU ECHOS A
6 8 11 16 19 22 24 28 32 35 42 48
(1) kW 8,4 11,5 14,6 22,5 26,1 30,4 32,9 37, 3 45,7 49,4 58,4 65,4
(1) kW 1,4 1,7 2,2 3,4 4,1 4,9 5,4 6,3 7,1 7,8 9,0 10,0
(1) 6,12 6,59 6,57 6,59 6,30 6,26 6,12 5,93 6,43 6,32 6,49 6,53
AAAAAAAAAAAA
(1),(8) kW 8,4 11,4 14,6 22,2 25,7 29,9 32,5 36,8 45,1 48,7 57,7 64,7
(1),(8) 5,24 5,75 5,78 5,33 5,18 5,20 5,16 5,04 5,41 5,37 5,55 5,62
AAAAAAABAAAA
(2) kW 5,9 8,3 10,4 15,6 18,1 21,0 23,5 26,7 32,5 35,2 41,8 46,6
(2) kW 1,4 1,8 2,3 3,4 4,1 4,8 5,3 6,2 7,0 7,7 8,7 9,9
(2) 4,24 4,61 4,52 4,58 4,40 4,38 4,44 4,31 4,65 4,57 4,80 4,71
4,83 5,31 5,16 5,10 4,95 4,91 4,91 4,80 5,14 5,07 5,31 5,18
DCCCCCCCCCB B
(2),(8) kW 5,9 8,3 10,4 15,4 17,9 20,8 23,3 26,5 32,2 34,9 41,4 46,2
(2),(8) 3,90 4,27 4,21 4,09 3,96 3,96 4,03 3,93 4,22 4,17 4,39 4,33
(8) 4,32 4,77 4,64 4,30 4,17 4,14 4,14 4,05 4,30 4,25 4,46 4,36
DCDDDDDDDDCC
(3) kW 6,4 8,8 11,0 16,5 19,2 22,5 24,8 28,0 34,5 36,9 43,9 48,8
(3) kW 1,3 1,6 2,0 3,1 3,7 4,3 4,8 5,6 6,2 7,0 7,8 8,9
(3) 4,89 5,51 5,52 5,34 5,19 5,22 5,16 4,99 5,56 5,26 5,63 5,48
(4) kW 7,1 9,8 12,0 17, 8 21,5 24,9 27,6 32,2 36,5 39,8 47,3 53,2
(4) kW 1,4 1,9 2,3 3,5 4,2 4,9 5,4 6,3 7,0 7,8 8,7 9,8
(4) 5,10 5,14 5,22 5,09 5,12 5,08 5,11 5,11 5,21 5,10 5,44 5,43
AAAAAAAAAAAA
(4),(8) kW 7, 2 9,8 12,0 18,0 21,7 25,2 27,9 32,5 36,9 40,2 47,7 53,6
(4),(8) 4,92 4,99 5,08 4,57 4,62 4,62 4,67 4,69 4,75 4,68 4,98 5,01
AAAAAAAAAAAA
(5) kW 6,9 9,5 11,7 16,8 20,3 23,5 26,6 31,1 35,2 38,4 45,0 50,6
(5) kW 1,8 2,5 3,0 4,4 5,3 6,1 6,7 7, 8 8,7 9,6 10,6 12,1
(5) 3,87 3,80 3,90 3,86 3,85 3,83 4,00 4,00 4,06 3,98 4,23 4,20
CDCCDDCCCCB B
(5),(8) kW 7,0 9,5 11,8 17,0 20,5 23,7 26,9 31,4 35,5 38,7 45,3 51,0
(5),(8) 3,78 3,73 3,83 3,60 3,60 3,61 3,76 3,77 3,81 3,76 3,98 3,98
DDDDDDDDDDCC
n° / n° 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1
%0-100 0-100 0-100 0 -100 0 -100 0 -100 0 -100 0 -100 0-100 0-100 0-100 0-100
(1) l/h 1.451 1.972 2.518 3.874 4.488 5.224 5.663 6.413 7. 8 6 4 8.490 10.048 11. 245
(1) kPa 16 11 12 117 121 115 110 111 124 118 115 106
(1) l/h 563 757 967 1.488 1.733 2.019 2.196 2.498 3.029 3.278 3.866 4.323
(1) kPa 22 21 17 19 25 21 19 14 26 31 25 32
kPa 46 45 42 78 69 100 92 82 87 119 114 85
l 35 35 35 50 50 50 100 100 100 100 100 100
(6) dB(A) 61 61 62 62 62 69 69 71 71 71 72 74
(7) dB(A) 47 47 48 48 48 55 55 57 57 57 58 60
(6) dB(A) 59 59 60 60 60 67 67 69 69 69 70 72
(7) dB(A) 45 45 46 46 46 53 53 55 55 55 56 58
(1)User side ingoing-outgoing water temperature 23/18°C; source side ingoing water
temperature 30/35°C
(2)User side ingoing-outgoing water temperature 12/7°C; source side ingoing water
temperature 30/35°C
(3)User side ingoing-outgoing water temperature 12/7°C; source side ingoing water
temperature 15/30°C
(4)User side ingoing-outgoing water temperature 30/35°C; source side ingoing-outgoing
water temperature 10/x°C
(5)User side ingoing-outgoing water temperature 40/45°C; source side ingoing-outgoing
water temperature 10/x°C
(6)Noise power levels calculated according to ISO 3744
(7)Noise pressure levels measured at 1 meter from the unit in free field, with a directivity
factor Q=4
(8)Values according to EN 14511-3:2011
This datasheet gives the characteristic data of the basic and standard versions of the
series; for details refer to the specific documentation
MU ECHOS - TECHNICAL DATA
UNIT SIZE
Cooling (Gross values)
Nominal cooling capacity (W 30°C/W 18°C)
Total power input for cooling
EER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity (W 30°C/W 18°C)
EER
Efficiency class
Cooling (Gross values)
Nominal cooling capacity (W 30°C/W 7°C)
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity (W 30°C/W 7°C)
EER
ESEER
Efficiency class
Cooling (Gross values)
Nominal cooling capacity (W 15°C/W 7°C)
Total power input for cooling
EER
Heating (Gross values)
Nominal heating capacity (W 10°C/W 35°C)
Total power input for heating
COP
Efficiency class
Heating (EN 14511 values)
Nominal heating capacity (W 10°C/W 35°C)
COP
Efficiency class
Heating (Gross values)
Nominal heating capacity (W 10°C/W 45°C)
Total power input for heating
COP
Efficiency class
Heating (EN 14511 values)
Nominal heating capacity (W 10°C/W 45°C)
COP
Efficiency class
Compressors
Quantity/Refrigerant circuits
Capacity steps
Evaporator
Water flow rate
Pressure drop
Conderser
Water flow rate
Pressure drop
Hydraulic module
Available pump pressure
Storage tank capacity
Sound level
Sound power value (standard unit)
Sound pressure value (standard unit)
Sound power value (SLN version)
Sound pressure value (SLN version)

7
MU ECHOS A
6 8 11 16 19 22 24 28 32 35 42 48
Lmm -507 861 862
Dmm -537 543 537
Hmm -671 671 1.020
W(1) kg ---102 106 112 164 168 200 203 204 252
6 8 11 16 19 22 24 28 32 35 42 48
Lmm 456 925 861 862
Dmm 398 537 543 537
Hmm 1.000 1.221 1.220 2.050
W(1) kg 158 164 169 226 231 238 344 348 371 378 378 426
6 8 11 16 19 22 24 28 32 35 42 48
LL (2) mm 100 300 300 300
LR (2) mm 100 300 300 300
DF (2) mm 500 500 500 500
DR (2) mm 0300 300 300
DR
D
DF
L
R
L
L
L
LR
L
L
L
H
DR
D
DF
H
MU ECHOS - TECHNICAL DATA
Basic version and ST1P
Length
Depth
Height
Operating weight
Version ST1PS
Length
Depth
Height
Operating weight
Clearance areas
Left side
Right side
Front side
Rear side
(1)The weight is only indicative and may vary depending on the unit outfit
(2)The clearance areas are indicated considering that the unit is controlled from the front side.

8
MU ECHOS A
20
25
30
35
40
45
50
55
60
-10 -5 0 5 10 15 20
Temperatura di uscita acqua utenza [°C]
Temperatura di uscita acqua sorgente [°C]
Solo riscaldamento
20
25
30
35
40
45
50
55
60
-25 -20 -15 -10 -5 0 5 10 15
Temperatura di uscita acqua utenza [°C]
Temperatura di evaporazione [°C]
Solo riscaldamento
20
25
30
35
40
45
50
55
60
65
-10 -5 0 5 10 15 20
Temperatura di condensazione [°C]
Temperatura di uscita acqua sorgente [°C]
Solo riscaldamento
-10
-5
0
5
10
15
20
25
20 25 30 35 40 45 50 55
Temperatura di uscita acqua utenza [°C]
Temperatura di uscita acqua sorgente [°C]
Solo raffreddamento
-10
-5
0
5
10
15
20
25
25 30 35 40 45 50 55 60 65
Temperatura di uscita acqua utenza [°C]
Temperatura di condensazione [°C]
Solo raffreddamento
-25
-20
-15
-10
-5
0
5
10
15
20 25 30 35 40 45 50 55
Temperatura di evaporazione [°C]
Temperatura di uscita acqua sorgente [°C]
Solo raffreddamento
MU ECHOS - OPERATING LIMITS
The heat exchanger temperature rise must be within 4°C e 7°C
: within this range the unit can operate only with glycol solution on evaporator side
CH VERSION AND HP
/LC VERSION AND LC /HP
/LE VERSION AND LE /HP
User outgoing water temperature [°C]
User outgoing water temperature [°C]
User outgoing water temperature [°C]
User outgoing water temperature [°C]
Evaporation temperature [°C]
Evaporation temperature [°C]
Condensation temperature [°C]
Condensation temperature [°C]
Source water outlet temperature [°C]
Source water outlet temperature [°C] Source water outlet temperature [°C]
Source water outlet temperature [°C]
COOLING
COOLING
COOLING
HEATING
HEATING
HEATING

9
MU ECHOS A
6 8 11 16 19 22 24 28 32 35 42 48
(1) kW ---6,1 7,5 8,8 9,2 10,7 12,6 13,8 15,6 17,6
(1),(2) A - - - 9,8 12 14,2 15,9 18,1 20,6 22,3 25,29 30,6
(3) A - - - 56 69 75 101 101 101 102 158 195
A - - - (34) (41) (45) (61) (61) (61) (61) (95) (117)
6 8 11 16 19 22 24 28 32 35 42 48
(1) kW 3,76 4,76 5,76 8,3 9,7 11,6 12 13,5 15,4 16,2 18 20
(1),(2) A13,1 17,4 22,4 10,1 12,3 14,65 16,35 18,55 21,05 23,2 26,19 31,5
(3) A58 82 97 56 69 75 101 101 101 103 159 196
A(35) (49) (58) (34) (42) (45) (61) (61) (61) (62) (95) (118)
6 8 11 16 19 22 24 28 32 35 42 48
V/ph/Hz 230/1~/50 400/3N~/50
(4) V/ph/Hz 400/3N~/50 -
MU ECHOS - ELECTRICAL DATA
Basic version
Maximum absorbed power
Maximum absorbed current
Maximum input current
Version ST1P o ST1PS
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Standard power supply
Optional power supply
The indicated data is valid for unit with standard power supply
(1)Electrical power that must be supplied by the mains to power the unit.
(2)Internal breakers tripping current. This value is never exceeded and must be used to size the line and its protections (refer to the electric diagram supplied with the unit).
(3)The maximum peak of the current is calculated considering the compressor start and the maximum power absorbed by all the other devices.
The value between parentheses refers to the units equipped with soft-starter (optional).
(4)To be asked for when ordering
The values and images inside the document are indicative and can be modified by the manufacturer without prior notification.
For further information refer to the specific documentation. The reproduction of this material, even partial, is prohibited.

10
MU ECHOS A
To
[°C] 30 35 40 45 50
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
6
45,8 1,3 5,5 1,5 5,1 1,7 4,8 1,9 4,4 2,1
76,4 1,3 6,0 1,5 5,7 1,7 5,3 1,9 4,9 2,1
86,6 1,3 6,2 1,5 5,9 1,7 5,5 1,9 5,1 2,1
96,8 1,3 6,5 1,5 6,1 1,7 5,7 1,9 5,3 2,1
10 7,0 1,3 6,7 1,5 6,3 1,7 5,9 1,9 5,5 2,1
8
48,0 1,6 7, 7 1,9 7, 2 2,1 6,8 2,4 6,4 2,8
78,8 1,6 8,4 1,8 8,0 2,1 7, 5 2,4 7,0 2,7
89,1 1,6 8,7 1,8 8,2 2,1 7, 7 2,4 7, 2 2,7
99,4 1,6 8,9 1,8 8,5 2,1 8,0 2,4 7, 4 2,7
10 9,7 1,6 9,2 1,8 8,7 2,1 8,2 2,4 7, 7 2,7
11
410,0 2,0 9,6 2,3 9,1 2,6 8,6 3,0 8,1 3,4
711, 0 2,0 10,5 2,3 10,0 2,6 9,5 3,0 8,9 3,4
811, 4 2,0 10,9 2,3 10,3 2,6 9,8 3,0 9,2 3,4
911, 8 2,0 11, 2 2,3 10,7 2,6 10,1 3,0 9,5 3,4
10 12,1 2,0 11, 6 2,3 11, 0 2,6 10,4 2,9 9,8 3,4
16
415,0 3,1 14,0 3,4 13,0 3,8 12,1 4,2 11, 2 4,7
716,5 3,1 15,4 3,4 14,4 3,8 13, 5 4,2 12,5 4,7
817,1 3,1 16,0 3,4 14,9 3,8 13,9 4,2 13,0 4,7
917, 6 3,1 16,5 3,4 15,5 3,8 14,4 4,2 13,4 4,7
10 18,2 3,1 17,1 3,4 16,0 3,8 14,9 4,2 13,9 4,7
19
417, 4 3,7 16,2 4,1 15,0 4,6 13,9 5,1 12,9 5,7
719,2 3,7 17,9 4,1 16,7 4,6 15,5 5,1 14,4 5,7
819,8 3,7 18,5 4,1 17, 3 4,6 16,1 5,1 14,9 5,7
920,5 3,7 19,2 4,1 17,9 4,6 16,6 5,1 15,4 5,8
10 21,2 3,7 19, 8 4,1 18,5 4,6 17, 2 5,1 16,0 5,8
22
420,3 4,3 18,9 4,7 17, 6 5,3 16,3 5,9 15,1 6,7
722,5 4,3 20,9 4,8 19,5 5,3 18,1 5,9 16,8 6,7
823,2 4,3 21,6 4,8 20,2 5,3 18,8 5,9 17,4 6,7
924,0 4,3 22,4 4,8 20,9 5,3 19,4 6,0 18,0 6,7
10 24,8 4,3 23,1 4,8 21,6 5,3 20,1 6,0 18,7 6,7
MU ECHOS - COOLING CAPACITY
Model
CONDENSER OUTGOING WATER TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

11
MU ECHOS A
To
[°C] 30 35 40 45 50
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
24
422,6 4,8 21,4 5,3 20,3 5,9 19,3 6,5 18,2 7, 3
724,8 4,8 23,5 5,3 22,3 5,9 21,2 6,6 20,0 7, 3
825,6 4,8 24,3 5,3 23,0 5,9 21,8 6,6 20,6 7,4
926,4 4,8 25,0 5,3 23,8 5,9 22,5 6,6 21,3 7,4
10 27, 2 4,8 25,8 5,3 24,5 5,9 23,2 6,6 21,9 7, 4
28
425,5 5,6 24,2 6,2 23,0 6,9 21,8 7, 6 20,7 8,5
728,0 5,6 26,6 6,2 25,3 6,9 23,9 7,7 22,6 8,5
828,8 5,6 27, 4 6,2 26,0 6,9 24,7 7,7 23,3 8,6
929,7 5,6 28,3 6,2 26,8 6,9 25,4 7, 7 24,1 8,6
10 30,7 5,6 29,1 6,2 27,7 6,9 26,2 7, 7 24,8 8,6
32
431,3 6,3 29,7 6,9 28,2 7, 6 26,7 8,5 25,2 9,4
734,5 6,2 32,7 6,9 31,0 7, 6 29,3 8,5 27,7 9,5
835,6 6,2 33,7 6,9 32,0 7, 6 30,3 8,5 28,6 9,5
936,7 6,2 34,8 6,9 33,0 7, 6 31,2 8,5 29,5 9,5
10 37, 8 6,2 35,9 6,9 34,0 7,7 32,2 8,5 30,4 9,5
35
433,6 7,1 31,8 7, 8 30,2 8,6 28,6 9,6 27,1 10,6
736,9 7,0 35,0 7, 8 33,2 8,6 31,4 9,6 29,7 10,7
838,0 7, 0 36,1 7, 8 34,2 8,6 32,4 9,6 30,6 10,7
939,2 7, 0 37, 2 7, 8 35,3 8,7 33,4 9,7 31,6 10,8
10 40,4 7,0 38,4 7, 8 36,4 8,7 34,5 9,7 32,6 10,8
42
439,9 7, 7 38,1 8,5 36,1 9,4 34,0 10,4 31,6 11, 6
743,9 7, 8 42,0 8,6 39,8 9,5 37, 5 10,5 35,0 11, 6
845,3 7, 8 43,3 8,6 41,1 9,5 38,8 10,5 36,2 11,7
946,7 7,9 44,7 8,7 42,5 9,5 40,0 10,5 37,4 11,7
10 48,2 7,9 46,1 8,7 43,8 9,6 41,3 10,6 38,6 11,7
48
444,3 8,9 42,1 9,8 39,8 10,9 37, 3 12,0 34,8 13,4
748,8 8,9 46,5 9,8 44,0 10,9 41, 3 12,1 38,6 13,4
850,3 8,9 47,9 9,9 45,4 10,9 42,8 12,1 39,9 13,4
952,0 8,9 49,5 9,9 46,9 10,9 44,2 12,1 41,3 13,4
10 53,6 8,9 51,1 9,9 48,4 10,9 45,6 12,1 42,7 13,4
MU ECHOS - COOLING CAPACITY
Model
CONDENSER OUTGOING WATER TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

12
MU ECHOS A
To
[°C] 30/35 35/40 40/45 45/50
Pf Pe Pf Pe Pf Pe Pf Pe
6
55,4 1,4 5,1 1,6 4,9 1,8 4,6 2,0
65,5 1,4 5,3 1,6 5,0 1,8 4,7 2,0
75,7 1,4 5,5 1,6 5,2 1,8 4,9 2,0
85,9 1,4 5,6 1,6 5,3 1,8 5,0 2,0
96,1 1,4 5,8 1,6 5,5 1,8 5,2 2,0
10 6,3 1,4 6,0 1,6 5,7 1,8 5,3 2,1
8
57,4 1,9 7, 0 2,2 6,7 2,5 6,2 2,9
67, 6 1,9 7, 3 2,2 6,8 2,5 6,4 2,9
77,9 1,9 7, 5 2,2 7,1 2,5 6,6 2,9
88,1 1,9 7, 7 2,2 7, 3 2,5 6,8 2,8
98,4 1,9 7,9 2,2 7, 5 2,5 7, 0 2,8
10 8,6 1,9 8,2 2,2 7, 7 2,5 7, 2 2,8
11
59,1 2,3 8,7 2,7 8,3 3,0 7, 8 3,5
69,4 2,3 9,0 2,6 8,5 3,0 8,1 3,5
79,7 2,3 9,2 2,6 8,8 3,0 8,3 3,4
810,0 2,3 9,5 2,6 9,1 3,0 8,6 3,4
910,3 2,3 9,8 2,6 9,3 3,0 8,8 3,4
10 10,6 2,3 10,1 2,6 9,6 3,0 9,1 3,4
16
513,4 3,5 12,5 3,9 11,7 4,3 10,9 4,9
613, 8 3,5 12,9 3,9 12,1 4,3 11, 3 4,9
714,2 3,5 13, 3 3,9 12,5 4,4 11,7 4,9
814,7 3,5 13,8 3,9 12,9 4,4 12,1 4,9
915,2 3,5 14, 3 3,9 13,4 4,4 12, 5 4,9
10 15,7 3,5 14,8 3,9 13, 8 4,4 12,9 4,9
19
516,2 4,2 15,1 4,7 14,1 5,3 13,2 5,9
616,7 4,2 15,6 4,7 14,6 5,3 13,6 5,9
717, 3 4,2 16,1 4,7 15,1 5,3 14,1 5,9
817, 8 4,2 16,7 4,7 15,6 5,3 14,6 5,9
918,4 4,2 17, 2 4,7 16,1 5,3 15,1 5,9
10 19,0 4,2 17, 8 4,7 16,7 5,3 15,6 5,9
22
518,8 4,9 17, 5 5,5 16,4 6,1 15,2 6,9
619,4 4,9 18,1 5,5 16,9 6,1 15,8 6,9
720,0 4,9 18,7 5,5 17, 5 6,1 16,3 6,9
820,6 4,9 19, 3 5,5 18,1 6,2 16,9 6,9
921,4 4,9 20,0 5,5 18,7 6,2 17,4 6,9
10 22,0 4,9 20,6 5,5 19,3 6,2 18,1 6,9
MU ECHOS - HEATING CAPACITY
Model
CONDENSER INGOING/OUTGOING WATER TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

13
MU ECHOS A
To
[°C] 30/35 35/40 40/45 45/50
Pf Pe Pf Pe Pf Pe Pf Pe
24
520,9 5,4 19,9 6,0 19,0 6,6 18,1 7,4
621,5 5,4 20,5 6,0 19,5 6,7 18,6 7, 4
722,2 5,4 21,1 6,0 20,1 6,7 19,1 7, 4
822,8 5,4 21,8 6,0 20,7 6,7 19,7 7, 4
923,6 5,4 22,4 6,0 21,3 6,7 20,3 7, 5
10 24,3 5,4 23,1 6,0 22,0 6,7 20,9 7, 5
28
524,5 6,3 23,4 7,0 22,3 7, 8 21,2 8,6
625,2 6,3 24,0 7, 0 22,9 7, 8 21,8 8,6
726,0 6,3 24,7 7,0 23,6 7, 8 22,4 8,7
826,7 6,3 25,5 7, 0 24,3 7, 8 23,1 8,7
927, 6 6,3 26,3 7, 0 25,0 7, 8 23,8 8,7
10 28,4 6,3 27, 0 7, 0 25,8 7, 8 24,5 8,7
32
527,9 7, 0 26,5 7, 8 25,2 8,6 23,9 9,6
628,7 7, 0 2 7, 3 7, 8 26,0 8,6 24,7 9,6
729,6 7, 0 28,1 7, 8 26,8 8,7 25,4 9,6
830,5 7, 0 29,0 7, 8 27, 6 8,7 26,2 9,7
931,4 7, 0 29,9 7, 8 28,4 8,7 27, 0 9,7
10 32,4 7, 0 30,8 7, 8 29,3 8,7 2 7, 8 9,7
35
530,3 7, 8 28,8 8,7 27, 4 9,6 26,0 10,7
631,2 7, 8 29,7 8,7 28,2 9,6 26,7 10,7
732,2 7, 8 30,6 8,7 29,0 9,6 27, 6 10,7
833,2 7, 8 31,5 8,7 30,0 9,7 28,4 10,8
934,2 7, 8 32,5 8,7 30,9 9,7 29,3 10,8
10 35,2 7, 8 33,5 8,7 31,8 9,7 30,2 10,8
42
536,5 8,7 34,6 9,6 32,5 10,6 30,3 11, 8
637, 6 8,7 35,7 9,6 33,6 10,6 31,4 11, 8
738,8 8,7 36,8 9,6 34,7 10,7 32,4 11,9
840,0 8,7 38,0 9,6 35,9 10,7 33,5 11,9
941,3 8,8 39,2 9,7 37,0 10,7 34,6 11,9
10 42,6 8,8 40,5 9,7 38,2 10,7 35,7 11,9
48
540,9 9,8 38,8 10,9 36,5 12,0 34,0 13,4
642,2 9,8 40,0 10,9 37,7 12,0 35,2 13,4
743,6 9,8 41, 3 10,9 38,9 12,1 36,4 13,4
845,0 9,8 42,7 10,9 40,3 12,1 37,7 13,4
946,5 9,8 44,1 10,9 41,6 12,1 38,9 13,4
10 48,0 9,8 45,5 10,9 43,0 12,1 40,2 13,4
MU ECHOS - HEATING CAPACITY
Model
CONDENSER INGOING/OUTGOING WATER TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

14
MU ECHOS A
To
[°C] 35 40 45 50 55 58
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
6
55,8 1,3 5,5 1,4 5,2 1,6 4,9 1,8 4,6 2,1 4,4 2,2
66,0 1,3 5,7 1,4 5,4 1,6 5,1 1,8 4,7 2,1 4,5 2,2
76,2 1,3 5,9 1,4 5,6 1,6 5,2 1,8 4,9 2,1 4,7 2,3
86,4 1,3 6,1 1,4 5,8 1,6 5,4 1,8 5,0 2,1 4,8 2,3
96,6 1,3 6,3 1,4 6,0 1,6 5,6 1,8 5,2 2,1 5,0 2,3
10 6,9 1,3 6,5 1,4 6,2 1,6 5,8 1,8 5,4 2,1 5,1 2,3
8
57, 5 1,8 7,1 2,0 6,7 2,3 6,3 2,6 5,9 3,0 5,6 3,3
67,7 1,7 7, 4 2,0 6,9 2,3 6,5 2,6 6,1 3,0 5,8 3,3
78,0 1,7 7, 6 2,0 7, 2 2,3 6,7 2,6 6,3 3,0 6,0 3,3
88,2 1,7 7, 8 2,0 7,4 2,3 6,9 2,6 6,5 3,0 6,2 3,2
98,5 1,7 8,1 2,0 7, 6 2,3 7, 2 2,6 6,7 3,0 6,3 3,2
10 8,8 1,7 8,3 2,0 7,9 2,2 7, 4 2,6 6,9 3,0 6,5 3,2
11
510,1 2,2 9,6 2,5 9,1 2,9 8,6 3,3 8,0 3,8 7,7 4,1
610,5 2,2 10,0 2,5 9,4 2,9 8,9 3,3 8,3 3,7 7,9 4,1
710,8 2,2 10,3 2,5 9,7 2,8 9,2 3,3 8,6 3,7 8,2 4,0
811, 2 2,2 10,6 2,5 10,1 2,8 9,5 3,2 8,8 3,7 8,4 4,0
911, 5 2,2 11,0 2,5 10,4 2,8 9,8 3,2 9,1 3,7 8,7 4,0
10 11,9 2,2 11, 4 2,5 10,7 2,8 10,1 3,2 9,4 3,7 9,0 4,0
16
515,3 3,1 14,2 3,5 13, 2 3,9 12,3 4,3 11, 4 4,9 10,8 5,2
615,8 3,1 14,7 3,5 13,7 3,9 12,7 4,3 11, 8 4,8 11, 3 5,2
716,4 3,1 15, 3 3,5 14,2 3,9 13, 2 4,3 12, 3 4,8 11,7 5,2
817, 0 3,1 15,8 3,4 14,7 3,9 13,7 4,3 12,7 4,8 12,1 5,2
917, 6 3,1 16,4 3,4 15,3 3,8 14,2 4,3 13, 2 4,8 12,6 5,2
10 18,2 3,1 17, 0 3,4 15,8 3,8 14,7 4,3 13,7 4,8 13,1 5,2
19
518,2 3,7 16,9 4,1 15,6 4,6 14,4 5,2 13,3 5,9 12,7 6,3
618,8 3,7 17, 5 4,1 16,2 4,6 15,0 5,2 13,8 5,9 13, 2 6,3
719,5 3,7 18,1 4,1 16,8 4,6 15,5 5,2 14,4 5,9 13,7 6,3
820,2 3,7 18,8 4,1 17, 4 4,6 16,1 5,2 14,9 5,9 14,2 6,3
920,9 3,7 19,4 4,1 18,1 4,6 16,7 5,2 15,5 5,8 14,7 6,3
10 21,6 3,7 20,1 4,1 18,7 4,6 17, 4 5,2 16,1 5,8 15, 3 6,3
22
521,0 4,4 19,5 4,8 18,0 5,4 16,7 6,1 15,4 6,9 14,6 7,4
621,7 4,3 20,2 4,8 18,7 5,4 17, 3 6,1 16,0 6,9 15, 2 7, 4
722,5 4,3 20,9 4,8 19,4 5,4 18,0 6,1 16,6 6,9 15,8 7, 4
823,3 4,3 21,7 4,8 20,1 5,4 18,6 6,1 17, 2 6,9 16,4 7, 4
924,1 4,3 22,4 4,8 20,9 5,4 19,3 6,1 17, 9 6,9 17, 0 7,4
10 25,0 4,3 23,2 4,8 21,6 5,4 20,0 6,1 18,5 6,9 17,7 7, 4
MU ECHOS/LC - COOLING CAPACITY
Model
CONDENSATION MEDIUM TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

15
MU ECHOS A
To
[°C] 35 40 45 50 55 58
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
24
523,4 4,9 22,2 5,4 21,0 6,0 19,9 6,7 18,8 7, 5 18,1 8,0
624,2 4,8 22,9 5,4 21,7 6,0 20,5 6,7 19,4 7, 5 18,7 8,0
725,0 4,8 23,7 5,4 22,4 6,0 21,2 6,7 20,0 7, 5 19,3 8,0
825,8 4,8 24,5 5,4 23,2 6,0 21,9 6,7 20,6 7, 5 19,9 8,0
926,7 4,8 25,3 5,4 23,9 6,0 22,6 6,7 21,3 7, 5 20,5 8,0
10 27, 5 4,8 26,1 5,3 24,7 6,0 23,3 6,7 22,0 7, 5 21,2 8,0
28
526,5 5,7 25,2 6,3 23,8 7, 0 22,5 7, 8 21,3 8,7 20,6 9,3
627,4 5,6 26,0 6,3 24,6 7, 0 23,3 7, 8 22,0 8,7 21,2 9,3
728,3 5,6 26,8 6,2 25,4 7, 0 24,0 7, 8 22,7 8,7 21,9 9,3
829,2 5,6 27,7 6,2 26,2 7, 0 24,8 7, 8 23,4 8,7 22,6 9,3
930,2 5,6 28,6 6,2 27,1 7, 0 25,6 7, 8 24,2 8,7 23,3 9,3
10 31,1 5,6 29,5 6,2 27,9 7, 0 26,4 7, 8 24,9 8,7 24,0 9,3
32
532,0 6,5 30,3 7, 2 28,7 8,0 27,1 9,0 25,6 10,0 24,7 10,7
633,1 6,5 31,3 7, 2 29,6 8,0 28,0 9,0 26,4 10,0 25,5 10,7
734,2 6,4 32,4 7, 2 30,6 8,0 28,9 9,0 27, 3 10,0 26,3 10,7
835,3 6,4 33,4 7, 2 31,6 8,0 29,9 9,0 28,1 10,0 27,1 10,7
936,5 6,4 34,5 7, 2 32,7 8,0 30,8 9,0 29,0 10,0 28,0 10,7
10 37, 6 6,4 35,6 7, 2 33,7 8,0 31,8 9,0 30,0 10,0 28,9 10,7
35
534,9 7,1 33,0 7,9 31,3 8,8 29,5 9,9 27,9 11, 0 26,9 11, 8
636,1 7,1 34,1 7,9 32,3 8,8 30,5 9,9 28,8 11, 0 27, 7 11, 8
737, 3 7,1 35,3 7, 9 33,4 8,8 31,5 9,9 29,7 11, 0 28,6 11, 8
838,5 7,1 36,4 7,9 34,5 8,8 32,5 9,9 30,7 11,1 29,6 11, 8
939,7 7,1 3 7, 6 7,9 35,6 8,8 33,6 9,9 31,6 11,1 30,5 11, 8
10 41,0 7,1 38,8 7,9 36,7 8,8 34,7 9,9 32,7 11,1 31,5 11, 8
42
541,4 8,1 39,4 8,9 37,1 9,9 34,7 11, 0 32,1 12, 3 30,4 13,1
642,8 8,1 40,8 8,9 38,4 9,9 35,9 11, 0 33,2 12, 3 31,5 13,1
744,2 8,1 42,1 9,0 39,7 9,9 37, 2 11, 0 34,4 12, 3 32,6 13,1
845,7 8,1 43,5 9,0 41,1 9,9 38,5 11, 0 35,6 12,3 33,8 13,1
947, 2 8,1 44,9 9,0 42,4 9,9 39,7 11,0 36,8 12,3 34,9 13,2
10 48,7 8,2 46,4 9,0 43,8 10,0 41,1 11, 0 38,1 12,3 36,1 13,2
48
547, 0 9,1 44,5 10,1 41,9 11, 3 39,2 12,5 36,2 14,0 34,4 14,9
648,7 9,1 46,1 10,1 43,4 11, 3 40,6 12, 5 37, 6 14,0 35,7 14,9
750,2 9,1 47,7 10,1 44,9 11, 2 42,0 12,5 38,9 13,9 37, 0 14,9
851,9 9,1 49,3 10,1 46,5 11, 2 43,5 12, 5 40,4 13,9 38,4 14,9
953,6 9,1 50,9 10,1 48,1 11, 2 45,0 12, 5 41,8 13,9 39,7 14,9
10 55,4 9,1 52,6 10,1 49,7 11, 2 46,6 12,5 43,3 13,9 41,2 14,9
MU ECHOS/LC - COOLING CAPACITY
Model
CONDENSATION MEDIUM TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

16
MU ECHOS A
To
[°C] 25/30 30/35 35/40 40/45 45/50
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
6
-15 4,6 1,2 4,6 1,4 4,6 1,5 ****
-10 5,4 1,2 5,4 1,4 5,3 1,6 5,3 1,8 * *
-5 6,3 1,2 6,2 1,4 6,1 1,6 6,1 1,8 6,0 2,0
07, 3 1,2 7, 2 1,4 7,1 1,6 6,9 1,8 6,8 2,0
58,5 1,3 8,3 1,4 8,1 1,6 7,9 1,8 7,7 2,1
8
-15 6,3 1,8 6,3 2,0 6,3 2,3 * * * *
-10 7, 4 1,7 7, 3 2,0 7, 3 2,3 7, 3 2,6 * *
-5 8,5 1,7 8,4 1,9 8,3 2,2 8,2 2,6 8,2 2,9
09,8 1,7 9,6 1,9 9,4 2,2 9,3 2,5 9,2 2,9
511, 2 1,6 10,9 1,9 10,7 2,2 10,4 2,5 10,2 2,8
11
-15 8,0 2,1 8,0 2,4 8,1 2,8 * * * *
-10 9,3 2,1 9,2 2,4 9,2 2,7 9,3 3,2 * *
-5 10,8 2,1 10,6 2,3 10,5 2,7 10,5 3,1 10,5 3,5
012,5 2,0 12,3 2,3 12,1 2,6 11,9 3,0 11, 8 3,4
514,5 2,0 14,1 2,3 13,8 2,6 13,5 2,9 13, 2 3,4
16
-15 11, 7 3,1 11, 4 3,4 11,1 3,8 11, 0 4,3 11, 0 4,8
-10 13,4 3,1 13,0 3,5 12,6 3,8 12,4 4,3 12,3 4,8
-5 15,5 3,1 14,9 3,5 14,4 3,9 14,0 4,3 13, 8 4,8
017,9 3,2 17, 2 3,5 16,6 3,9 16,1 4,3 15,7 4,9
520,8 3,2 19,9 3,5 19,2 3,9 18,5 4,4 18,0 4,9
19
-15 14,2 3,7 13,8 4,1 13,5 4,6 13,4 5,2 13,4 5,9
-10 16,3 3,7 15,7 4,1 15,3 4,6 15,0 5,2 14,9 5,9
-5 18,7 3,7 18,0 4,2 17,4 4,7 17, 0 5,2 16,8 5,9
021,7 3,8 20,8 4,2 20,0 4,7 19,4 5,3 19,0 5,9
525,2 3,8 24,1 4,2 23,1 4,7 22,3 5,3 21,7 5,9
22
-15 16,4 4,3 15,8 4,8 15,5 5,4 15,4 6,1 15,4 6,8
-10 18,8 4,3 18,1 4,8 17, 6 5,4 17, 3 6,1 17, 2 6,9
-5 21,6 4,4 20,7 4,9 20,1 5,4 19,6 6,1 19,3 6,9
025,0 4,4 23,9 4,9 23,1 5,5 22,4 6,1 21,9 6,9
529,0 4,4 27, 7 4,9 26,6 5,5 25,7 6,2 25,0 6,9
MU ECHOS/LC/HP - HEATING CAPACITY
Model
CONDENSER INGOING/OUTGOING WATER TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

17
MU ECHOS A
To
[°C] 25/30 30/35 35/40 40/45 45/50
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
24
-15 19,5 5,7 19,0 5,9 18,6 6,2 18,4 6,6 18,3 7,1
-10 21,6 5,3 21,1 5,7 20,7 6,1 20,5 6,6 20,4 7, 2
-5 24,3 5,1 23,7 5,5 23,2 6,0 22,9 6,6 22,7 7, 3
027, 6 4,9 26,8 5,4 26,3 6,0 25,8 6,7 25,5 7, 4
531,6 4,9 30,7 5,4 29,9 6,0 29,3 6,7 28,8 7, 5
28
-15 22,9 6,6 22,3 6,9 21,8 7, 2 21,6 7,7 21,5 8,2
-10 25,3 6,2 24,7 6,6 24,2 7,1 24,0 7,7 23,9 8,4
-5 28,4 5,9 27,7 6,4 27, 2 7, 0 26,8 7,7 26,7 8,5
032,3 5,7 31,4 6,3 30,8 7, 0 30,3 7, 8 29,9 8,6
537, 0 5,7 35,9 6,3 35,0 7, 0 34,3 7, 8 33,7 8,7
32
-15 25,7 7, 5 25,0 7, 8 24,5 8,2 24,1 8,7 24,0 9,3
-10 28,4 7, 0 27,7 7, 4 27,1 8,0 26,8 8,6 26,6 9,4
-5 31,9 6,6 31,1 7, 2 30,5 7, 8 30,0 8,6 29,8 9,5
036,3 6,4 35,3 7, 0 34,5 7, 8 33,9 8,6 33,5 9,6
541,7 6,3 40,5 7, 0 39,4 7, 8 38,5 8,7 37, 8 9,7
35
-15 28,0 8,3 27, 2 8,6 26,6 9,1 26,3 9,6 26,1 10,3
-10 30,9 7,7 30,1 8,2 29,5 8,8 29,2 9,6 29,0 10,4
-5 34,7 7, 3 33,8 8,0 33,2 8,7 32,7 9,6 32,4 10,6
039,5 7,1 38,4 7, 8 3 7, 6 8,7 36,9 9,6 36,4 10,7
545,3 7, 0 44,0 7, 8 42,8 8,7 41,9 9,7 41,1 10,8
42
-15 29,6 7, 5 29,2 8,3 28,8 9,3 28,5 10,4 * *
-10 34,6 7, 6 33,9 8,4 33,3 9,4 32,7 10,4 32,1 11, 7
-5 40,3 7,7 39,4 8,5 38,5 9,4 37, 5 10,5 36,6 11,7
046,8 7,9 45,6 8,7 44,4 9,6 43,1 10,6 41,9 11, 8
554,2 8,0 52,7 8,8 51,2 9,7 49,5 10,7 47,9 11,9
48
-15 33,6 8,8 33,0 9,8 32,4 10,9 32,0 12,2 * *
-10 39,2 8,8 38,3 9,8 3 7, 5 10,9 36,7 12,1 36,1 13,5
-5 45,6 8,8 44,5 9,8 43,4 10,8 42,3 12,0 41,3 13,4
053,1 8,8 51,6 9,8 50,2 10,9 48,7 12,0 47, 3 13,4
561,5 8,9 59,7 9,8 57,9 10,9 56,1 12,1 54,2 13,4
MU ECHOS/LC/HP - HEATING CAPACITY
Model
CONDENSER INGOING/OUTGOING WATER TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)

18
MU ECHOS A
Tev
[°C] 30 35 40 45 50
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
6
05,8 1,3 5,4 1,5 5,1 1,7 4,7 1,9 4,3 2,1
2,5 6,3 1,3 6,0 1,5 5,6 1,7 5,2 1,9 4,8 2,1
56,9 1,3 6,5 1,5 6,1 1,7 5,7 1,9 5,3 2,1
77,4 1,3 7, 0 1,5 6,6 1,7 6,1 1,9 5,7 2,1
10 8,2 1,3 7, 8 1,5 7, 3 1,7 6,8 1,9 6,3 2,1
8
08,1 1,6 7,7 1,9 7, 2 2,1 6,8 2,4 6,3 2,8
2,5 8,8 1,6 8,4 1,8 7,9 2,1 7,4 2,4 6,8 2,7
59,6 1,6 9,1 1,8 8,5 2,1 8,0 2,4 7, 4 2,7
710,2 1,6 9,7 1,8 9,1 2,1 8,5 2,4 7,9 2,7
10 11, 2 1,6 10,6 1,8 10,0 2,1 9,4 2,3 8,7 2,7
11
010,3 2,0 9,8 2,3 9,2 2,6 8,7 3,0 8,1 3,4
2,5 11, 2 2,0 10,7 2,3 10,1 2,6 9,5 3,0 8,8 3,4
512,3 2,0 11, 6 2,3 11, 0 2,6 10,3 2,9 9,6 3,4
713,1 2,0 12,5 2,3 11, 8 2,6 11, 0 2,9 10,3 3,3
10 14,6 2,0 13,8 2,2 13,0 2,5 12,2 2,9 11, 4 3,3
16
014,8 3,1 13,7 3,4 12,7 3,8 11, 7 4,2 10,8 4,7
2,5 16,2 3,1 15,0 3,4 13,9 3,8 12,9 4,2 11,9 4,7
517, 7 3,1 16,5 3,4 15,3 3,8 14,2 4,2 13,1 4,7
719,0 3,1 17, 7 3,4 16,5 3,8 15,3 4,3 14,1 4,7
10 21,2 3,1 19,7 3,5 18,4 3,8 17,1 4,3 15,9 4,8
19
017, 3 3,7 15,9 4,1 14,7 4,5 13,5 5,1 12,4 5,7
2,5 18,9 3,7 17, 5 4,1 16,1 4,6 14,9 5,1 13,7 5,7
520,6 3,7 19,1 4,1 17,7 4,6 16,3 5,1 15,0 5,7
722,1 3,7 20,6 4,1 19,1 4,6 17, 6 5,1 16,2 5,8
10 24,6 3,8 22,9 4,2 21,3 4,6 19,7 5,2 18,2 5,8
22
020,2 4,3 18,6 4,7 17,1 5,3 15,8 5,9 14,5 6,6
2,5 22,1 4,3 20,4 4,8 18,8 5,3 17, 4 5,9 15,9 6,7
524,1 4,3 22,3 4,8 20,7 5,3 19,1 6,0 17, 6 6,7
725,9 4,3 24,0 4,8 22,3 5,3 20,6 6,0 19,0 6,7
10 28,8 4,4 26,8 4,8 24,9 5,4 23,0 6,0 21,3 6,7
MU ECHOS/LE - COOLING CAPACITY
Model
CONDENSER OUTGOING WATER TEMPERATURE [°C]
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Tev: evaporation temperature [°C]

19
MU ECHOS A
Tev
[°C] 30 35 40 45 50
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
24
022,3 4,8 21,1 5,3 19,9 5,9 18,8 6,5 17, 7 7, 3
2,5 24,3 4,8 22,9 5,3 21,6 5,9 20,4 6,6 19,2 7, 3
526,4 4,8 24,9 5,3 23,5 5,9 22,2 6,6 20,8 7, 4
728,2 4,8 26,6 5,3 25,1 6,0 23,7 6,6 22,2 7,4
10 31,1 4,8 29,4 5,4 27,7 6,0 26,1 6,7 24,5 7, 5
28
025,6 5,6 24,2 6,2 22,9 6,9 21,6 7, 6 20,3 8,4
2,5 27,9 5,6 26,3 6,2 24,9 6,9 23,4 7, 6 22,1 8,5
530,3 5,6 28,6 6,2 27, 0 6,9 25,4 7, 7 23,9 8,6
732,4 5,6 30,6 6,2 28,8 6,9 27, 2 7, 7 25,5 8,6
10 35,7 5,6 33,7 6,3 31,8 7, 0 30,0 7, 8 28,1 8,7
32
030,6 6,3 28,9 6,9 27, 2 7, 6 25,7 8,5 24,2 9,4
2,5 33,3 6,2 31,4 6,9 29,6 7, 6 27, 9 8,5 26,3 9,5
536,2 6,2 34,1 6,9 32,2 7, 6 30,4 8,5 28,6 9,5
738,7 6,2 36,5 6,9 34,4 7,7 32,4 8,6 30,5 9,5
10 42,7 6,2 40,3 6,9 38,0 7, 7 35,8 8,6 33,7 9,6
35
032,9 7,1 31,0 7, 8 29,3 8,6 27, 6 9,6 26,0 10,6
2,5 35,7 7, 0 33,7 7, 8 31,8 8,6 30,0 9,6 28,3 10,7
538,8 7,0 36,7 7, 8 34,6 8,6 32,6 9,6 30,7 10,7
741,5 7, 0 39,2 7, 8 3 7,0 8,7 34,8 9,7 32,7 10,8
10 45,8 7, 0 43,3 7, 8 40,8 8,7 38,4 9,7 36,1 10,9
42
039,4 7, 7 37, 5 8,5 35,3 9,4 33,0 10,4 30,5 11, 5
2,5 43,0 7, 8 40,9 8,6 38,6 9,5 36,1 10,5 33,4 11, 6
546,8 7,9 44,5 8,7 42,1 9,5 39,4 10,5 36,5 11,7
750,0 7, 9 47, 6 8,7 45,0 9,6 42,2 10,6 39,2 11,7
10 55,1 8,0 52,5 8,8 49,7 9,7 46,6 10,7 43,3 11, 8
48
044,3 8,9 41,9 9,8 39,4 10,9 36,7 12,0 33,9 13,4
2,5 48,4 8,9 45,8 9,8 43,1 10,9 40,3 12,1 37, 3 13,4
552,7 8,9 50,0 9,9 47,1 10,9 4 4,1 12,1 40,8 13,4
756,4 9,0 53,5 9,9 50,5 11, 0 47, 3 12,1 43,9 13,4
10 62,2 9,0 59,1 10,0 55,8 11, 0 52,3 12, 2 48,7 13,5
MU ECHOS/LE - COOLING CAPACITY
Model
CONDENSER OUTGOING WATER TEMPERATURE [°C]
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Tev: evaporation temperature [°C]

20
MU ECHOS A
To
[°C] 35 40 45 50 55 60
Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe Pf Pe
6
67,0 1,3 6,9 1,4 6,9 1,6 6,8 1,8 6,8 2,1 * *
77,2 1,3 7,1 1,4 7,0 1,6 7,0 1,8 6,9 2,1 6,9 2,4
87,4 1,3 7,3 1,4 7,2 1,6 7,1 1,8 7,1 2,1 7,0 2,4
97,6 1,3 7,5 1,4 7,4 1,6 7,3 1,8 7,2 2,1 7,1 2,4
10 7,8 1,3 7,7 1,4 7,6 1,6 7,5 1,8 7,4 2,1 7,3 2,4
8
69,7 1,7 9,5 2,0 9,4 2,3 9,3 2,6 9,3 3,0 9,2 3,4
79,9 1,7 9,7 2,0 9,6 2,3 9,5 2,6 9,4 3,0 9,4 3,4
810,1 1,7 10,0 2,0 9,8 2,3 9,7 2,6 9,6 3,0 9,6 3,4
910,4 1,7 10,2 2,0 10,1 2,3 9,9 2,6 9,8 3,0 9,7 3,4
10 10,6 1,7 10,5 2,0 10,3 2,2 10,1 2,6 10,0 3,0 9,9 3,4
11
611,7 2,2 11,6 2,5 11,6 2,9 11,5 3,3 11,5 3,8 * *
712,0 2,2 11,9 2,5 11,8 2,9 11,8 3,3 11,7 3,8 11,7 4,3
812,3 2,2 12,2 2,5 12,1 2,9 12,0 3,3 11,9 3,8 11,9 4,3
912,6 2,2 12,5 2,5 12,4 2,9 12,3 3,3 12,2 3,7 12,1 4,3
10 13,0 2,2 12,8 2,5 12,6 2,8 12,5 3,3 12,4 3,7 12,4 4,2
16
618,0 3,1 17,3 3,5 16,8 3,9 16,4 4,3 16,1 4,9 15,9 5,4
718,5 3,1 17,8 3,5 17,3 3,9 16,8 4,3 16,5 4,9 16,3 5,4
819,0 3,1 18,3 3,5 17,7 3,9 17,3 4,3 17,0 4,8 16,7 5,4
919,5 3,1 18,8 3,5 18,2 3,9 17,7 4,3 17,4 4,8 17,1 5,4
10 20,0 3,1 19,3 3,5 18,7 3,9 18,2 4,3 17,8 4,8 17,5 5,4
19
621,8 3,7 21,0 4,1 20,4 4,6 19,9 5,2 19,5 5,9 19,4 6,6
722,4 3,7 21,6 4,1 20,9 4,6 20,4 5,2 20,0 5,9 19,8 6,6
823,0 3,7 22,2 4,1 21,5 4,6 20,9 5,2 20,5 5,9 20,3 6,6
923,6 3,7 22,8 4,1 22,1 4,6 21,5 5,2 21,0 5,9 20,7 6,6
10 24,3 3,7 23,4 4,1 22,7 4,6 22,0 5,2 21,6 5,9 21,2 6,6
22
625,2 4,4 24,3 4,9 23,6 5,4 23,0 6,1 22,7 6,9 22,4 7,8
725,9 4,4 25,0 4,8 24,2 5,4 23,6 6,1 23,2 6,9 22,9 7,8
826,6 4,4 25,7 4,8 24,9 5,4 24,2 6,1 23,8 6,9 23,5 7,8
927,4 4,3 26,4 4,8 25,5 5,4 24,9 6,1 24,4 6,9 24,0 7,8
10 28,1 4,3 27,1 4,8 26,2 5,4 25,5 6,1 25,0 6,9 24,6 7,7
MU ECHOS/LE/HP - HEATING CAPACITY
Model
CONDENSATION MEDIUM TEMPERATURE [°C]
Pf: total cooling capacity provided
Pa: compressor power
To: water outlet temperature from the heat exchanger users (delta T=5K)
Table of contents
Popular Accessories manuals by other brands

Ventura
Ventura Prenox FREESTANDER 2009 Erection Instructions

turck
turck FCS-G1/4A4-NAEX/D100 manual

Trivita
Trivita Essential Oils Diffuser Instructions & Care

aquilar
aquilar AquiTron AT-OPSEN installation instructions

Greenheck
Greenheck FD Series Installation instruction supplement

Elkay
Elkay EFOA Installation, care & use manual