Sound
Sound power level Lwa dB(A) 43 47 50
Sound pressure level in 1 m 1) Lpa dB(A) 28 32 35
Field of application
Heat source temperature min/max °C -6 to +20
Heat flow temperature at > B0 min/max °C +25 to +65
Heat flow temperature at B-6 min/max °C +25 to +60
Vaporiser, brine side (at B0/W35)
Volume flow minimum / nominal / standard m³/h 1.88/2.15/2.51 2.45/2.80/3.27 3.13/3.58/4.18
Pressure drop via heat pump kPa 8/11/14 12/15/20 17/21/29
Free compression 2) kPa 100/95/91 92/86/80 81/72/59
Medium water/ethylene glycol % 75/25 75/25 75/25
Built-in brine pump A 16-1 KW A 16-1 KW A 16-1 KW
Condenser, heater side (at B0/W35)
Volume flow minimum / nominal / standard m³/h 0.91/1.30/1.81 1.18/1.69/2.36 1.53/2.18/3.06
Pressure drop via heat pump kPa 4/7/13 5/10/18 7/14/27
Free compression 2) kPa 77/73/61 75/66/52 70/57/36
Medium water % 100 100 100
Built-in heating pump A 15-1 A 15-1 A 15-1
Dimensions/connections/miscellaneous
Dimensions D x W x H mm 700 x 530 x 1260
Total weight kg 170 170 190
Heating circuit connection AG Inch 5/4" 5/4" 5/4"
Brine circuit connection AG Inch 5/4" 5/4" 5/4"
Cooling agent/filling quantity -- / kg R-410A/2.1 R-410A/2.8 R-410A/3.1
Refrigeration oil filling quantity l 1.2 1.2 1.0
Expansion vessel heater 3) V l SD 50.3 SD 50.3 SD 80.3
set upstream pressure, heating circuit p bar 1.0 1.0 1.0
Expansion vessel, brine circuit V l SD 25.3 SD 25.3 SD 35.3
set upstream pressure, brine circuit p bar 0.5 0.5 0.5
Safety valve (brine/heating) p bar 3.0 3.0 3.0
Switching point, brine pressure controller p bar 0.4 0.4 0.4
Heat pump type FUSIO W 11 FUSIO W 14 FUSIO W 18
Model All in One All in One All in One
Controller Optiplus integrated integrated integrated
WPZ-test number SW-307-12-06
FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller
Standard performance data (as per EN 14511) W 35 W 50 W 35 W 50 W 35 W 50
Heat output at B0 kW 10.6 9.9 13.8 12.9 17.8 16.7
COP at B0 - 4.7 3.1 4.7 3.1 4.5 3.1
El. power consumption at B0 kW 2.2 3.2 2.9 4.1 3.9 5.4
Cooling output at B0 kW 8.3 6.7 10.9 8.8 13.9 11.3
1) Free field value
2) Free compression is specified for highest level
3) Expansion vessel heater is enclosed from fusio w 11
4) FUSIO W 5 and FUSIO W 6 without soft starter