
2-RECEIVING
After receiving, clean the unit from all the packing components. If the units looks damaged or not completed,
don’t go on with the installation. Check in the label that the units received is the same of the ordered code.
Claims must be submitted by writing within 8 days from receiving.
3-INSTALLATION INSTRUCTIONS
The units are designed to be installed under-ceiling. Dimensions of the grille and of the unit are right to be
installed in continuous ceiling or in 600x600mm modular block ceiling. Special dimensions can be requested
to the manufacturer in case of different modular block ceiling dimensions.
3.1-Positioning
The unit is designed to supply air with Coanda effect (according to this effect, air flow is horizontal, and very
closed to the ceiling). For this reason, the position of the unit and of the room furnishing (lamps,..) must be
studied not to stop the air flow.
The position of the unit must be evaluated considering also the threw distance of the unit (refer to technical
manual).
Respect the minimum distance needed for maintenance, (see dimensional drawings).
3.2-Fixing the unit to the true ceiling
First of all, be sure that the true ceiling and the components used are able to carry the weight of the units.
Fix the units to the true ceiling using the 20x10 holes in the right and left flanks. Units sizes 18 has also holes
20x10 in the plenum. For more information regarding the fixing holes, see dimensional drawings.
We suggest to install the units using M8 treaded bar and to block it using nuts and washers. Even if the fans
have very low vibrations, we suggest to use rubber anti-vibrations.