manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Wind Crest
  6. •
  7. Ventilation Hood
  8. •
  9. Wind Crest WPX Series User manual

Wind Crest WPX Series User manual

1 of 9 Rev A
PLEASE READ ENTIRE INSTRUCTION BEFORE PROCEEDING.
INSTALLATIONS MUST COMPLY WITH ALL LOCAL CODES.
IMPORTANT: Save these Instructions for the Local Electrical Inspector's use.
INSTALLER: Please leave these Installation Instructions with this unit for owner.
OWNER: Please retain these Instructions for future reference
IMPORTANT SAFETYINSTRUCTIONS
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS,
HOODS SHOULD BE INSTALLED WITH VENTILATORS APPROVED FOR USE WITH THE HOOD.
SEE TABLE –1 ON THIS PAGE FOR APPROVED VENTILATORS.
WARNING - TO REDUCE THE
RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO
PERSONS, OBSERVE THE
FOLLOWING:
A. Installation work and Electrical
Wiring Must Be Done By Qualified
Person(s) In Accordance With All
Applicable Codes & Standards.
Including Fire-Rated Construction.
“WARNING” To Reduce The Risk Of
Fire, Use Only Metal Duct Work.
B. Sufficient air is needed for proper
combustion and exhausting of gases
through the flue (chimney) of fuel
burning equipment to prevent
backdrafting. Follow the heating
equipment manufactures guideline and
safetystandard such as those published
by the National Fire Protection
Association (NFPA) and the American
Societyfor Heating, Refrigeration and
Air Conditioning Engineers (ASHRAE),
and the local code authorities.
C. When cutting or drilling into wall or
ceiling, do not damage electrical wiring
and other hidden utilities.
D. Before Servicing or Cleaning Unit,
Switch Power off At Service Panel And
Lock Service Disconnecting Means to
Prevent Power From Being Switched On
Accidentally. When The Service
Disconnecting Means Cannot be Locked,
securely Fasten A Prominent Warning
Device, Such As A Tag, To The Service
Panel
CAUTION - TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR, BE SURE TO
DUCT AIR OUTSIDE FOR DUCTED FANS –DO NOT VENT EXHAUST AIR INTO SPACE WITHIN
WALLS OR CEILING OR INTO ATTICS, CRAWL SPACES OR GARAGES.
Read this instruction completely before starting installation. Planning the complete installation before starting any work
is highly recommended. This includes all aspects of the installation including hood location, ducting, electrical requirements,
and adequacy of mounting surfaces.
DUCTING: Use a minimum 8" round duct for VEN060I installations. Use a minimum 10" round duct for VEN120I,
VEN100E and VEN150E installations. See Page –2 for Transition (Purchased Separately) Recommendations.
INSTALLATION INSTRUCTIONS
HOOD MODELS –WPX
TABLE - 1
Use model VEN060I or VEN120I
for internal ventilator. Use
VEN100E or VEN150E for remote
ventilator
This hood series has been designed to be used with the ventilators shown in
Table –1 (Exception: The VEN120I cannot be used on 30-inch wide
Hoods). Before cutting into cabinets, it is necessary to confirm that the
correct ventilator is being used. Your dealer should have reviewed your needs
prior to your purchase. Be sure you have the correct ventilation system.
CAUTION: To Reduce The Risk Of Fire And Electrical Shock, Install This
Rangehood Only With Blowers Manufactured By Wind Crest.
P.O. Box 18645 Anaheim, Ca 92817 (877) 387-6721
2 of 9 Rev A
.
NOTE: Unit must be vented
to outside of the building.
BEFORE STARTING INSTALLATION, YOU MUST IDENTIFY THE VENTILATOR MODEL BEING USED
AND IF A TOP OR REAR EXHAUST IS TO BE USED.
NOTE: VEN120I cannot be used in rear exhaust applications or on Models with Heat-
Lamps.
Prepare cabinet and/or wall for mounting either top (Fig -
3) or rear (Fig - 6) exhaust. Use furring strips to level
cabinet mounting surface with any cabinet trims.
For knock out removal see Fig- B
Remove See
Ventilator Model Knock out # Transition # Fig
VEN060I Top Exhaust 2 10100.00 1,3
VEN120I Top Exhaust 2 & 3 11257.00 2,3
VEN100 & VEN150 2 & 3 11257.00 3
External, Top Exhaust
VEN060I Rear Exhaust 1 11254.00 4,5,6
Break the metal webs by placing a screwdriver at one
corner of the plate and hitting screwdriver sharply with a
hammer. After breaking a second web the plate can be
flexed to break other webs.
Wear eye protection when using tools.
Caution: When knock outs are removed
the edges will be sharp!!!!!!!!! Sharp Edges
should be Filed or Covered with Metal
Tape.
Attach and secure the transition to the hood with #6x3/8
sheet metal screws and tape all joints prior to installing the
hood. Attach hood to cabinet using #10 wood screws. If
duct cover is used refer to Instructions on Page –6. Holes
are located in the back panel and top panel of the hood for
mounting. Use a minimum of four #10x3/4 wood screws
to mount the hood. Longer screws are required if wall
board or other nonstructural surfaces are used between the
hood and main mounting surface which should be a
minimum of 3/4”thick. When using rear holes for
additional mounting use appropriate anchors if not
engaging the wood structure.
HINT: If you find vibration noise is present because of
cabinet structure use additional screws, in holes available,
to make the mounting more ridged.
Connect 120 volt, 60 Hz power through the conduit hole
in top of hood, connecting to pigtail in hood junction box,
white to white, black to black and connect green ground
wire to the power supply ground wire per local codes. See
Fig –A.
The recommended height from countertop or cooking
surface to the bottom edge of the hood is 30 to 36 inches.
Hood is recommended for use over domestic gas or
electric appliances. Not recommended for use over solid
fuel fired appliances.
After installing the hood, install the internal blower
(Top Exhaust See Fig 1 & 2; Rear Exhaust See Fig -
4) unit by positioning the blower onto bracket-A,
notched blower bracket will center blower. Rotate
into position against hood and secure Bracket –B to
Hood with #8 sheet metal screws. If the remote
ventilator is used see related instructions and Fig - 3.
The VEN100E/150E ventilator will require revision
of some wiring in the hood receptacle box - See
VEN100E/150E instructions.
NOTE: VEN150E requires a dedicated 20 AMP
Power Supply. All other ventilators require a
dedicated 15 AMP Power Supply
CAUTION: The hood is of sufficient weight that two
installers are recommended to prevent injury or damage to
the hood in handling.
Turn the power on at the service entrance and check the
operation of the controls.
NOTE: be sure that all dampers are operating properly
and are free to open.
BACKDRAFT DAMPER
: It is recommended that a backdraft damper
(#10288.00 for 8” round ducts, #10289.00 for 10” round ducts) be used in all
installations. In cold weather installations it is necessary to use a backdraft
damper to minimize backflow of cold air into room. A non-metallic thermal
break should also be used to minimize conduction of outside temperatures
through the ductwork. The thermal break should be located as close as possible
to where the ducting enters the heated portion of the house.
SAFTY WARNING:
Turn off power circuit at
the service entrance and
lockout panel before
wiring the range hood.
3 of 9 Rev A
10"
13-1/2"
5"
7-3/8"
13-1/2"
9-1/4"
11-1/2"
4-1/4"
14"
4-1/4"
9-1/4"
14"
10100.00 11254.00
11257.00 10377.00
KNOCK OUTS
COVER
HOOD TOP
HOOD WIRING
MOUNTING
ACCESS
SCREW
REMOVE APPROPRIATE KNOCK OUTS AND CONNECT WIRING
ACCORDING TO HOOD AND BLOWER INSTALLATION INSTRUCTIONS.
CAUTION: ALWAYS INSTALL RECEPTACLE BOX COVER.
RECEPTACLE BOX COVER
COVER IS PACKED WITH FILTERS
Fig - A
NOTE: Transitions Are Not Included With VEN060I, VEN100E and VEN150E - Must Be Purchased
Separately.
Transition dimensions may very. Before assembling transitions to hood, fit them into the prepared cabinet opening to be sure the openings are large
enough to accommodate the transition. Enlarge the hole if required
Attach the transition (See DUCTING, pg 1), obtained separately from your local hardware or available through your dealer, and install the hood as
described previously in this instruction.
1
2
1
23
Fig - B
4 of 9 Rev A
FIG-1
TRANSITION #10100.00 OR #11257.00
THE 8" EXHAUST WITH TRANSITION # 10100.00,
WILL BE ON THE CENTER LINE OF HOOD WIDTH
AND ON CENTER LINE OF 12" DIMENSION
OR 10" EXHAUST WITH TRANSITION # 11257.00
ROTATE
INTO
POSITION
POSITION
INTO
ROTATE
B
A
VEN060I
VEN120I (SHOWN)
HOOD MODELS WPX
TOP EXHAUST
A
VEN060I
INTO
POSITION
ROTATE
B
AIR FLOW
USE # 10100.00
TRANSITION
TO 8" DUCT
USE # 10377.00
TRANSITION
FOR REAR
WALL
EXHAUST
(10" DUCT)
VEN060I ONLY
AIR FLOW
USE # 11257.00
TRANSITION
TO 10" DUCT
REMOVE KNOCK OUT # 2
REMOVE KNOCK OUT # 2 & 3
FIG-2
VEN100 & 150E
B
A
WITH 2 SCREWS
& SECURE
WITH 2 SCREWS
& SECURE
& SECURE
WITH 2 SCREWS
SECURE TRANSITION TO HOOD USING #6X 3/8"
SHEET METAL SCREWS, TAPE ALL JOINT & SEAMS
15"
24"
ALL HOODS
2"
12"
15"
FIG - 3
TOP EXHAUST
W/ROOF OR WALL CAP
TO EXHAUST
8" OR 10" DUCT
5 of 9 Rev A
FIG-4
HOOD MODELS WPX
REAR EXHAUST
REMOVE KNOCK OUT # 1
SECURE TRANSITION TO HOOD USING #6 X 3/8"
SHEET METAL SCREWS, TAPE ALL JOINT & SEAMS
FIG - 6
USE # 11254.00
TRANSITION
TO 10" DUCT
OR WALL CAP
ROUTE TO OUTSIDE
W/WALL CAP - # 11259.00
SECURE TRANSITION TO HOOD USING #6X 3/8"
SHEET METAL SCREWS. TAPE ALL JOINTS AND
SEAMS.
FIG-5
14 4
1
8
1
7
6"
C
LHOOD
A
CUT HOLE IN DRYWALL
TO ACCEPT TRANSITION
# 11254.00
A= CENTER OF ROUND DUCT
USING # 11254.00 TRANSITION
1
4
10 51
8
6 of 9 Rev A
DUCT COVER INSTALLATION INSTRUCTION FOR WPX MODELS
PLEASE READ DUCT COVER AND HOOD INSTRUCTION
COMPLETELY BEFORE PROCEEDING WITH INSTALLATION
PARTS: One 15” Duct Cover Section
One 19” Duct Cover Section
One Duct Cover Bracket
Two #8 x 1-1/2” Screws (Mount duct cover bracket to ceiling)
Four #8 x 3-1/2” Screws Secure duct cover section 1 and 2)
Four #8 x 1/2“ Screw Mount duct cover to hood)
Your WPX model hood includes a duct cover, which can be used as an alternate installation method to enclose the
ventilation duct. The hood can also be mounted under a cabinet.
HOOD UNDER CABINET
INSTALLATION INSTALLATION
HOOD WITH DUCT COVER
Two typical installation options shown above
When used, the duct cover is designed to accommodate typical ceiling heights of 8-ft to 10-ft.
USING DUCT COVER
SECTION - 1 & 2 ONLYSECTION - 2 ONLY
USING DUCT COVERUSING DUCT COVER
SECTION - 1 ONLY
15"
15" 19" 32" MAX
19" MIN
CEILING
CEILING
CEILING
CAUTION: To prevent damaging the duct cover, DO NOT remove the protective covering until you are
ready to assemble the cover to the hood.
7 of 9 Rev A
1) Decide on hood location, position above cooking surface and type of air discharge to be used (See Hood
Installation Instruction). When using the Duct Cover(s) plan on spacing from the top of the hood to the
ceiling 1/8” larger than the duct cover length being used. This allows assembly of the duct cover after
installation of the hood, electric connections and ducting. The small gap, at top of duct, remaining after
installation will not be noticeable in most applications. If necessary a small quarter-round can be used to
this gap at the ceiling interface.
SPACING TO
BE 1/8"
LARGER THAN
DUCT COVER
BEING USED
2) When using the duct cover and hood, locate hood centerline on wall and mount the Duct Cover Bracket to
ceiling centered on the hood centerline, use #8 x 1-1/2” screws to mount bracket. Mount the bracket to the
ceiling with edge “A” against the hood-mounting wall. Wood framing should be located, behind wallboard,
in the area of the ceiling. If not, use anchors to fasten bracket to ceiling.
C
L HOOD
BRACKET
DUCT COVER
TO
SECURE
CEILING
#8 SCREWS
SECURE W/2
WALL
CEILING
A
The Duct Cover Bracket is used to ensure the Duct Cover is retained against the wall, for appearance purposes,
when the longer length of cover is used.
8 of 9 Rev A
3) Mount the hood and install wiring and ducting per Hood Installation Instruction.
4) When using Duct Cover sections 1 & 2, set in length of duct needed and secure sections together using four #8 x 3/8”
screws. Flanges on Duct Cover Section should be positioned facing toward same end of Duct Cover assembly. HINT:
Predrive screws into holes, remove screws, remove protective cover from Duct Cover Sections, assemble Duct Cover
sections and set length (Use extreme caution to avoid scratching Duct Cover Sections), reinstall screws and
tighten. This will ease assembly of screws and prevent scratching of Duct Cover.
REMINDER: Length of Duct Covers should be 1/8” smaller than spacing of hood top to ceiling.
DESIRED
DUCT COVER
HEIGHT
SCREW, BOTH
SIDES WITH
#8 X3/8 SCREWS
15" SECTION
19" SECTION
15" SECTION
FLANGE
19" SECTION
FLANGE
5) Predrive #8x1/2” screws into bottom flange of duct cover. Remove screws and aside for use when mounting duct
cover to hood.
6) Install the duct cover onto the hood, flanges facing down, and spread the sides of the Duct Cover slightly and position
the cover over the Duct Cover Bracket.
7) Fasten Duct Cover to hood using screws from step-5. This should be done before installing internal blower unit.
8) Install internal blower unit or remote blower unit as required.
KNOCK OUTS
COVER
HOODTOP
HOOD WIRING
MOUNTING
ACCESS
SCREW
REMOVE APPROPRIATE KNOCK OUTS ANDCONNECT WIRING
ACCORDINGTO HOOD AND BLOWER INSTALLATION INSTRUCTIONS.
CAUTION: ALWAYS INSTALL RECEPTACLE BOX COVER.
RECEPTACLE BOX COVER
COVER IS PACKED WITH FILTERS
9 of 9 Rev A
1
2
3
44
3
2
1
LIGHT
LEFT RIGHT
LIGHT
12 B # 1
18 B # 6
18 R # 22
18 BL #23
18 B # 24
18 W # 9
18 B # 8
18 W # 10
18 B # 7
18 W 18 B
18 BL 18 R
18 W # 5
18 W # 25
18 B # 12
18 W # 13
18 G # 11
18 BL # 3
18 B # 2
18 R # 4
BLOWER
MOTOR
ROTARY
3-SPD
SWITCH
BOX
RECEPTACLE
RECEPTACLE
PLUG
POWER SUPPLY
N G L1
WIRING DIAGRAM-INTERNAL BLOWER & LIGHTING
A
B
1
2
3
SWITCH
LIGHT
III
I
I
I
1 2 3
4 5 6
18 W # 5
1
22
1
1
2
3
44
3
2
1
RIGHT
HEAT
LIGHT
HEAT
LIGHT
LEFT
LIGHT
LEFT RIGHT
LIGHT
12 B # 1
18 R # 22
18 BL #23
18 B # 24
18 B # 14 18 B # 15
18 W # 21 18 B # 16 18 B # 18
18 B # 19
18 B # 17
18 W # 20
18 W # 10
18 W 18 B
18 BL 18 R
18 W # 25
18 B # 12
18 W # 13
18 G # 11
18 BL # 3
18 B # 2
18 R # 4
BLOWER
MOTOR
18 W # 26
HEAT
LIGHT
SWITCH
LEFT
SWITCH
HEAT
LIGHT
RIGHT
BOX
RECEPTACLE
RECEPTACLE
PLUG
POWER SUPPLY
N G L1
WIRING DIAGRAM-INTERNAL BLOWER, LIGHTING & HEAT LAMPS
18 W # 5
SWITCH
18 W # 5
I
I
1
LIGHT
4
32
I
65
II
I
18 B # 6
B
A
18 B # 8
SWITCH
3-SPD
ROTARY
2
3
1
18 W # 9 18 B # 7

Other Wind Crest Ventilation Hood manuals

Wind Crest PCG36S User manual

Wind Crest

Wind Crest PCG36S User manual

Wind Crest WCL Classic Series User manual

Wind Crest

Wind Crest WCL Classic Series User manual

Wind Crest UIX3019S Installation guide

Wind Crest

Wind Crest UIX3019S Installation guide

Wind Crest WCG300S Installation guide

Wind Crest

Wind Crest WCG300S Installation guide

Wind Crest WSL Series User manual

Wind Crest

Wind Crest WSL Series User manual

Wind Crest WSL Series User manual

Wind Crest

Wind Crest WSL Series User manual

Wind Crest WER Series User manual

Wind Crest

Wind Crest WER Series User manual

Wind Crest WST300SBG Installation guide

Wind Crest

Wind Crest WST300SBG Installation guide

Wind Crest VEN150E User manual

Wind Crest

Wind Crest VEN150E User manual

Wind Crest PFA36SCG Installation guide

Wind Crest

Wind Crest PFA36SCG Installation guide

Wind Crest UIX3622S Installation guide

Wind Crest

Wind Crest UIX3622S Installation guide

Wind Crest PER Series User manual

Wind Crest

Wind Crest PER Series User manual

Wind Crest WCB302S Use Installation guide

Wind Crest

Wind Crest WCB302S Use Installation guide

Wind Crest VEN100E User manual

Wind Crest

Wind Crest VEN100E User manual

Wind Crest VEN060I User manual

Wind Crest

Wind Crest VEN060I User manual

Wind Crest PPN Series User manual

Wind Crest

Wind Crest PPN Series User manual

Wind Crest UL2936S User manual

Wind Crest

Wind Crest UL2936S User manual

Wind Crest WCL User manual

Wind Crest

Wind Crest WCL User manual

Wind Crest EUROPA WER Series User manual

Wind Crest

Wind Crest EUROPA WER Series User manual

Wind Crest WPN User manual

Wind Crest

Wind Crest WPN User manual

Wind Crest WST360SBG User manual

Wind Crest

Wind Crest WST360SBG User manual

Popular Ventilation Hood manuals by other brands

Zanussi TH 6033 Instructions for use and care

Zanussi

Zanussi TH 6033 Instructions for use and care

inventum AKI6015ZWA user manual

inventum

inventum AKI6015ZWA user manual

Grundig GDKP2464BBSC user manual

Grundig

Grundig GDKP2464BBSC user manual

Zephyr Pisa ZPI-E30AG290 Use, care and installation guide

Zephyr

Zephyr Pisa ZPI-E30AG290 Use, care and installation guide

Electrolux EFG 535 user manual

Electrolux

Electrolux EFG 535 user manual

Electrolux RH30WC55GSA parts catalog

Electrolux

Electrolux RH30WC55GSA parts catalog

Klarstein 10031680 manual

Klarstein

Klarstein 10031680 manual

Amana UXT3030AY Product dimensions

Amana

Amana UXT3030AY Product dimensions

Whirlpool RH2324XJQ3 parts list

Whirlpool

Whirlpool RH2324XJQ3 parts list

Delta Heat DHVH36 installation instructions

Delta Heat

Delta Heat DHVH36 installation instructions

NEFF D99L20N0 instruction manual

NEFF

NEFF D99L20N0 instruction manual

Zanussi ZHC 920 operating instructions

Zanussi

Zanussi ZHC 920 operating instructions

Wolf CTWH30 installation instructions

Wolf

Wolf CTWH30 installation instructions

Glem GHB972IX instruction manual

Glem

Glem GHB972IX instruction manual

Electrolux EFC6422 user manual

Electrolux

Electrolux EFC6422 user manual

NuTone Premier POWER MODULE NSPM390 Series instructions

NuTone

NuTone Premier POWER MODULE NSPM390 Series instructions

Pelgrim PSK925RVS Instructions for use

Pelgrim

Pelgrim PSK925RVS Instructions for use

Ancona aero island iv User instructions

Ancona

Ancona aero island iv User instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.