WiredRite SST- 4 Operating instructions

SST- 4
Installation
and Operation Guide
Simpler Is Better
WiredRite Systems, Inc.

Page 2 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
SAFETY SUMMARY
The following general safety precautions must be observed during all phases of operation, service, and
repair of this instrument. Failure to comply with these precautions or with specic warnings elsewhere
in this manual violates safety standards of design, manufacture, and intended use of the instrument.
Wired Rite Systems assumes no liability for the customer’s failure to comply with these requirements.
SST-4 installation must be performed by appropriate qualied personnel trained for the
installation of vehicle electrical equipment and controls for engine functions.
Vehicle safety interlocks installed in vehicles must never be bypassed.
Verify that the vehicle is disabled before performing installation or maintenance procedures
with the SST-4. The battery should be disconnected to ensure that the vehicle is disabled
during installation.
Whenever performing maintenance, use only factory specied parts and replacement parts.
Always use appropriate gauge wire for the expected current and power ratings.
DO NOT SUBSTITUTE PARTS OR MODIFY circuitry. Because of the danger of
introducing additional hazards, do not install substitute parts or perform any unauthorized
modication.
Equipment that appears damaged or defective should be made inoperative and secured
against unintended operation until they can be repaired by qualied service personnel.
1.
2.
3.
4.
5.
6.
7.
CONTENTS
SAFETY SUMMARY...............................................................................................................2
INTRODUCTION.....................................................................................................................3
OPERATIONAL FEATURES ...................................................................................................4
CONNECTIONS.......................................................................................................................5
INSTALLATION AND POWER-UP .......................................................................................6
PROGRAMMING ....................................................................................................................7
PROGRAMMING PROCEDURE............................................................................................8
TROUBLESHOOTING ............................................................................................................9
TEST MODE OPERATION:...................................................................................................11
APPENDIX I. WIRING DIAGRAMS ...................................................................................12
APPENDIX II. CONNECTION TABLES .............................................................................16
APPENDIX III. REPLACEABLE PARTS .............................................................................17
APPENDIX IV. TRUCK MANUFACTURER TECH SUPPORT .........................................17
APPENDIX V. AUTO STOP ON LOSS OF PRESSURE MODE..........................................18

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 3
INTRODUCTION
Thank you for purchasing the new SST-4 from Wired Rite Systems. This product has been designed for
the highest reliability while providing your critical remote START-STOP-THROTTLE functions. The
following items are included with the SST-4 shipment:
SST-4 circuit board with optional enclosure or mounting base.
Connector kits for wiring mating connectors to the six-pin connector and the two four-pin
connectors. Part numbers for the connectors are shown in the replaceable parts section at the
end of this manual.
Figure 1. SST-4 in enclosure with cover removed

Page 4 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
OPERATIONAL FEATURES
Ability to remotely operate engine controls, including Start/Stop, Throttle and E-Power.
Active and Inactive modes. Active mode when Master enable signal is provided to the SST-4.
Auto Stop On Loss Of Pressure Mode allows the monitoring of engine or PTO functions and
automatic fail-over to preset emergency power settings.
Inputs triggers include: MASTER, Start/Stop (SS), Auxiliary (AUX), Throttle (TH), Pressure
Sensor (PRESSURE) .
Triggers are provided by supplying either a positive signal (+12V) or ground signal.
Three replaceable on-board relays enable switching for Ignition, Start/Stop, and E-power.
Circuit breakers provide protection for Ignition, Start/Stop, and E-Power circuits.
Dual throttle relays allow for multiple throttle settings (engine speeds).
Emergency power (E-Power) source can be triggered independently.
Four character display showing faults, programming parameters and hour meter readout.
LED status indicators provide additional information, such as status of relay positions.
Programmable via 3-Pushbutton switches for choosing menu and entering/modifying
parameters. No computer is required for programming.
Timer delays can be set for the following: (Delay values are shown in Table 4)
E-Power Delay Timer
Throttle Delay Timer
Glow Plug Timer
Start Duration Timer (max cranking time of the vehicle’s starter).
Loss of engine oil/hydraulic uid pressure sensor delay
Maximum time for the E-Power circuit to be engaged can be set. Time values are shown in
Table 4.
Test mode allows bench testing of the inputs and outputs using built-in display.
On-board self-diagnostic tests display faults, and system “remembers” any faults that have
occurred, even if the faults no longer exist.
Connector kits are included for control and throttle connectors.
Pre-wired harnesses are available (optional).
•
•
•
•
•

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 5
CONNECTIONS
Detailed wiring diagrams and notes are found in Appendix I. Please refer to that section for
information and suggestions for your specic requirements. This manual assumes that the installation
was completed using these suggestions.
Figure 2 shows the SST-4 board layout, highlighting key components.
Figure 3 shows the terminal connections for the wiring to the SST-4.
Wiring diagrams. Wiring diagrams for common congurations of the SST-4 board are shown in
Appendix I. Wiring diagrams.
Connection tables. Tables showing the function of each connection to the SST-4 are shown in
Appendix II. Connection Tables.
Figure 2. SST-4 simplified board layout showing key components.
1 2 3 4 5 6 7
TB1
6
3
J1
4
1
4 34 3
1
T1
2
T2
2 1
J1 INPUTS TBI T1 T2
PIN FUNCTION TSP FUNCTION PIN FUNCTION PIN FUNCTION
1 PRESSURE 1 GROUND 1 RLY1 NORM.CLOSED 1 RLY2 NORM.CLOSED
2 AUX TRIG 2 START OUT 2 RLY1 NORM.OPEN 2 RLY2 NORM.OPEN
3 MASTER 3 MAIN POWER (VBAT ) 3 RLY1 NORM.CLOSED 3 RLY2 NORM.CLOSED
4 THROTTLE 4 AUX IN 4 RLY1 NORM.OPEN 4 RLY2 NORM.OPEN
5 START/STOP 5 AUX OUT
6 GROUND 6 IGNITION IN
7 IGNITION OUT
Figure 3. SST-4 Terminal connections.

Page 6 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
INSTALLATION AND POWER-UP
After all of the connections have been made, and the unit has been mounted securely, the
SST-4 is ready to be powered up. The following procedure describes the power up and
initial checkout.
With the ignition switch in the ON position, turn on the “Master” switch to power up the
SST-4. On initial power up the SST-4 will perform a self-diagnostic test to verify that all of
the functions are operating correctly. If a ashing “SP” is reported, the master switch was
turned on with the ignition switch in the off position. Turn on the iginition switch, and then
hold down the UP and DOWN buttons simultaneously for 5 seconds to clear the fault.
If no faults are detected, the SST-4 will go into “Run mode” and the hour meter readout will
be visible on the display (refer to Table 1).
If a fault is detected on power up, a code will be ashing on the display indicating in which
circuit the fault has occurred. For assistance in troubleshooting, please refer to the trouble
shooting section.
After all of the faults have been cleared and the SST-4 is operating in normal mode, apply
signals to test the proper function of the SST-4. Table 1 outlines the different display
codes and the operations which they indicate. Apply signals as available to ensure proper
operation of each function.When checking signals, verify the status of various signals on
the board by using the green display indicators, shown in and detailed in Table 2.
1.
2.
3.
4.
5.
Display Flashing Description
Yes Board power only, Master switch is off.
No
Run mode (hour meter display) Note: If hour meter is
counting, the decimal ashes. If not counting, decimal
does not ash.
No Stop mode
No Start signal active, glow plugs on
No Start signal active, starter on
No Throttle Plunger input active
No Emergency Power input active
Table 1. Display during normal operations
LED # Description On Indicates
D2 Start/Stop or Throttle
Input An input trigger is applied to Start/Stop or Throttle
D3 Throttle Relay #1 Relay is enabled
D4 Throttle Relay #2 Relay is enabled
D5 Start Relay Relay is enabled, power at START OUT on TB1.
D6 AUX Relay (E-Pump) Relay is enabled, power at AUX OUT on TB1.
D7 Ignition Relay is enabled, power at IGN OUT on TB1.
Table 2. SST-4 Green LED indicators.

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 7
PROGRAMMING
Parameter Value Description
“A”
Plunger Mode
1 Single plunger (Start/Stop only)
2* Dual plunger (Start/Stop/Throttle)
“b”
Throttle Mode (Only if A is set to 2)
1* Throttle relays latch ON and OFF (maintained)
2 Throttle relays are momentary (on-demand)
3 T1 latches ON, T2 momentary, STOP turns both OFF
4 T1 & T2 latch ON, T2 OFF, STOP turns both OFF
5† Timed operation (see “E”)
6 T1 latches ON, T1 OFF & T2 latches ON, T1 & T2 OFF
7 T1 momentary ON, T2 momentary ON, repeat
8 No throttle mode
9† As soon as MASTER Power is applied:
T1 latches ON, T2 momentary, STOP turns both OFF
A†
As soon as MASTER Power is applied:
T1 latches ON, T2 latches ON/OFF with Throttle input signal,
STOP turns both OFF
“C”
AUX (Emergency Power) Mode
1* AUX (Emergency Power) from the J1 Pin 4 input (THROTTLE)
2 AUX (Emergency Power) from the J1 Pin 5 input (START/STOP)
3 RESERVED
4 AUX (Emergency Power) from J1 Pin 2 (AUX TRIG)
5 Auto Stop on Loss of Pressure Mode (see appendix V)
“D”
AUX (Emergency Power Time) 0-9, 3* Time delay for Emergency Power relay actuation,
“E”
Throttle Mode Timer 0-9, 0* Time delay for throttle timed operation,
“F”
Glow Plug Timer 0-9, 0* Delay time for starter activation
“H”
Start Duration Timer 0-9, 5* Maximum time for starter cranking
“J”
Emergency Power Duration Time 0-d, 8* Maximum time for Emergency Power operation
“L”
Diagnostic display On/Off
0* Diagnostic Display Off
1 Diagnostic Display On
“o”
Auto Stop Pressure Delay Timer 3-d, 7* Pressure Sender delay time out when in Auto Stop Mode
“P”
Pressure Switch Descriptor
0* Normally open and ground signal indicates pressure present.
1 Normally closed and ground signal indicates NO pressure.
2 Normally open and positive signal indicates pressure present.
3 Normally closed and positive signal indicates NO pressure,
Table 3. Programmable parameters and settings. *Denotes Factory Setting. † See timer notes Appendix VI
Value Delay Time Value Delay Time Value Delay Time
0 No delay / timeout 5 10 seconds A 1 minute
1 1 second 6 15 seconds b 2 minutes
2 2 seconds 7 20 seconds C 3 minutes
3 3 seconds 8 30 seconds d 4 minutes
4 5 seconds 9 45 seconds
Table 4. Programmable Delay Timer Values

Page 8 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
PROGRAMMING PROCEDURE
The following procedure describes how to view and change settings for SST-4 operation. These
procedures require the user to access the pushbuttons on the SST-4 circuit board: “MENU”, “UP”, and
“DOWN”.
Press the “MENU” button on the SST-4 board. The display will show the board’s current
operating conguration, starting with “A2”, that is, the system is set for dual plunger mode.
Press “MENU” again, and the next parameter is displayed. Repeat pressing “MENU” to
view all the settings, until the system returns to “A2”.
If changes are desired, press “MENU” until the target parameter is displayed. Use the “UP”
and “DOWN” keys to change the parameter to the desired value. The available choices are
those shown in Table 5.
To save changes, press and hold the “MENU” key for 5 seconds. The display ashes “SA”
to conrm that the conguration change has been saved.
If the conguration has been changed mistakenly, restore the SST-4 to its previous conguration by
holding the “MENU” and “DOWN” keys for three seconds. This will reload the last saved settings.
You can page through the congurations and see that it is as expected, then the settings must be saved,
by holding the “MENU” key for 5 seconds. The display will ash “SA” for conrmation of the save.
The SST-4 is preloaded with a factory default conguration. The default settings are displayed on
Table 3 with an asterisk (*). To recall these setting hold the “MENU” and “UP” keys down together
for 3 seconds. You can page through the congurations and see that it is as expected, then the settings
must be saved, by pressing and holding the “MENU” key for 5 seconds. The display will ash “SA” as
conrmation of the save. The table below shows a summary of the pushbutton controls.
It is important to note that changes are not saved automatically, but must be written to memory by
holding down the “MENU” key for 5 seconds. This includes any of the recall functions described
above. The values that were recalled are not made active until the user has saved them.
1.
2.
3.
4.
Function summary Function description Procedure
Choose parameter Choose which parameter will be
modied.
Press “MENU” until the desired parameter is
displayed.
Choose value Choose the value of the selected
parameter.
Press “UP” and “DOWN” until the desired
parameter value is displayed.
Save changes Save the changes made to one or more
parameter values.
Press and hold “MENU” for 5 seconds. “SA” is
ashed to conrm save.
Recall previous Recall previously saved conguration and
cancel last save command.
Press and hold both “MENU” and “DOWN” for
three seconds. “SA” is ashed to conrm save.
Recall factory Recall factory settings for all parameters. Press and hold both “MENU” and “UP” for
three seconds. “SA” is ashed to conrm save.
Table 5. Menu/Up/Down Pushbutton functions

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 9
TROUBLESHOOTING
If a problem is encountered, the following procedure can be used to troubleshoot the system, and
identify and x some of the more common problems. If the problem is not easily identied, please
contact Wired Rite for assistance at 1-800-538-7483. Before beginning the troubleshooting, please
check these ve items:
System Lock-up. The processor on the SST-4 board can go into a locked-up situation if
the power is toggled on and off at a rapid rate. If this occurs the processor must be reset by
disconnecting the power to the board for several seconds and then reconnecting it.
Ground. The ground wire of the SST-4 must NOT be connected to the chassis, but routed
directly to the negative side of the battery.
On-board LED indicators. An additional troubleshooting resource is the on-board LED
indicators. These functions are described in Table 2. SST-4 Green LED indicators.
Diagnostic Display. If an error is detected by the SST-4, and parameter “L” is set to 1, the
display will ash to identify the problem circuit. Refer to Table 6 for locating the cause of
the fault.
Storing and clearing faults. If a fault occurs, the SST-4’s on board diagnostics will
record in which circuit the fault occurred and save the fault into memory. To clear all of
the recorded faults, press and hold the “UP” and “DOWN” buttons on the board for three
seconds or remove board power. This will erase the volatile memory and place the system
back in the “Run mode”
Troubleshooting Procedure
Begin with all inputs to the board OFF. Remove the enclosure lid if present to allow visual
inspection of the 4-character display and the relay status indicators.
Supply power to the SST-4 board. The 4-character displays should be active, for example
with two blinking decimal points. Check for board power on TB1 pin 3 (GND is available
on TB1 pin 1.) If there is no power, check the circuit breaker.
Turn the ignition ON. This should illuminate the relay indicators D5 (Starter Relay), D6
(Aux Relay), and D7 (Ignition Relay). If one or more indicators are not illuminated, then
that circuit may not be receiving power from the ignition splice. Check the associated
wiring path to ensure that the circuit is enabled. You may need to manually reset the
manual circuit breakers near each relay by pressing the yellow tab. NOTE: The Aux Relay
manual circuit breaker can be placed in two positions, depending on whether the system
incorporates a separate E-power battery. If there is a separate E-power battery, then the
circuit breaker should be connected between J5 and J6; otherwise it should be connected
between J6 and J7.
Turn ON the SST-4 MASTER switch. This is sometimes labeled “MACHINE” or “PTO” or
“AERIAL ENABLE” to indicate non-truck functions. This should activate the hour meter
on the 4-character display. If not, check that the signal from the SST-4 MASTER signal is
being applied to J1 Pin 3.
Apply START signal from the aerial switch. Indicator D2 should be illuminated. If not,
verify that the START signal is being applied to J1 Pin 5. Remove the START signal.
Apply THROTTLE signal from the aerial switch. Indicator D2 should be illuminated. If not
verify that the THROTTLE signal is being applied to J1 Pin 4. Remove the THROTTLE
signal.
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
6.

Page 10 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
Apply signal to activate the Start, Stop, and E-power functions as dened in the
programming settings. Verify that the 4-character display shows “St”, “SP”, and “EP” as
expected. If not, check programming settings (see Programming section). Set parameter
“L” to 1 and if the display is ashing “St”, “SP”, or “EP”, then there has been a fault in that
circuit. Check the manual circuit breakers and reset if necessary by pressing the yellow tab
on the circuit breaker.
Apply signal to activate the Throttle functions as dened in the programming settings.
Verify that the Throttle Relay Indicators D3 and D4 are activated. If not, check
programming settings (see Programming section).
Troubleshooting Quick Reference
The following table shows common problems and possible solutions when operating the SST-4. If the
problem is not easily identied, please contact Wired Rite for assistance at 1-800-538-7483.
7.
8.
Flashing Display Description
Fault detected in Stop circuit
Fault detected in Start circuit
Fault detected in Emergency Power circuit
Table 6. Fault Display
Problem Possible solution
Nothing is displayed on 4-character display. Check board power available at TB1 pin 3. If power is applied
and board is unresponsive, try resetting processor by removing
system power for at least three seconds. Then reapply power.
Relay Indicators D5, D6, D7 off with Ignition on. Check Ignition Splice. Check manual circuit breakers. Check
position of Aux Relay circuit breaker. With separate E-power
battery, circuit breaker should be between J5 and J6. Otherwise
it should be between J6 and J7.
No HOUR METER is displayed on 4-character display. Check board power and SST-4 Master input at J1 Pin 3.
HOUR METER is not counting (decimal not ashing) Check SST-4 Master input at J1 Pin 3. Check Programming
Parameter “o” for Hour Meter Input mode (Master or Spare).
Start/Stop or Throttle inputs do not activate D2 indicator. Check signal path for trigger signals Start/Stop (J1 Pin 5) and
Throttle (J1 Pin 4).
Displayed state of “St”, “SP” or “EP” are not as expected Check Programming Parameters C and D and timer durations.
Throttle Relay not triggering and Relay Indicators D3
and D4 are not illuminated.
Check signal path for Throttle signals into T1 and T2. Check
Programming Parameters A, B, and E.

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 11
TEST MODE OPERATION:
Test Mode is used to verify the wiring and operation of the system.
CAUTION: when in Test Mode, the vehicle or Emergency Pump may start unexpectedly.
Whenever possible, Test Mode should be used for bench testing. If used when installed, two
mechanics should be present, and extra care is strongly advised.
To enter Test Mode, press and hold all three buttons: “MENU”, “UP”, and “DOWN” for ve seconds
until all of the segments ash in the middle two 7-segment displays.
To verify each of the items shown in the table below, perform the user action, and verify the resulting
display.
Verification Of Relay
Functions User Action Resulting Display
Ignition relay & T1
Throttle relay
With ignition ON press MENU button on SST-4 board
(WARNING: Vehicle may start)
Starter relay & T2 Throttle
relay
With ignition ON press Up button on SST-4 board
(WARNING: Vehicle may start)
Emergency Pump relay With ignition ON press Down button on SST-4 board
(WARNING: E-Pump may start)
Verification Of Installation Wiring User Action Resulting Display
Board Power (TB1, Position 3) Apply power to board
Ignition Power (TB1, Position 6) Turn ignition key ON
Power from Master switch (J1, Pin 3) Turn ON Master switch
Remote E-Power input (J1, Pin 2) Activate remote E-power switch
Remote Start/Stop input (J1, Pin 5) Activate remote Start/Stop switch
Remote Throttle input (J1, Pin 4) Activate remote Throttle switch

Page 12 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
APPENDIX I. WIRING DIAGRAMS
The SST-4 can be wired in various ways for a variety of engine control applications. This section
includes wiring diagram for three common congurations:
Aux E-Power Battery. Emergency Power is provided from an Auxiliary Battery.
Programming state would include “C4”.
No Aux E-Power Battery. Emergency Power is provided from normal battery (there is no
Auxiliary Battery) and E-power control is from Start/Stop or Throttle signals. Programming
state would include “C1” or “C2”.
No Aux E-Power Battery, simplied. Fully ignition supplied. Emergency Power is provided
from normal battery (there is no Auxiliary Battery) and E-power control is from Start/Stop
or Throttle signals. Programming state would include “C1” or “C2”.
1.
2.
3.
1 2 3 4 5 6 7
TB1
6
3
J1
4
1
4 34 3
1
T1
2
T2
2 1
J1 INPUTS TBI T1 T2
PIN FUNCTION TSP FUNCTION PIN FUNCTION PIN FUNCTION
1 PRESSURE 1 GROUND 1 RLY1 NORM.CLOSED 1 RLY2 NORM.CLOSED
2 AUX TRIG 2 START OUT 2 RLY1 NORM.OPEN 2 RLY2 NORM.OPEN
3 MASTER 3 MAIN POWER (VBAT) 3 RLY1 NORM.CLOSED 3 RLY2 NORM.CLOSED
4 THROTTLE 4 AUX IN 4 RLY1 NORM.OPEN 4 RLY2 NORM.OPEN
5 START/STOP 5 AUX OUT
6 GROUND 6 IGNITION IN
7 IGNITION OUT
The Auxiliary (AUX), Throttle (TH), and Start/Stop (SS) are input triggers that are provided by
supplying either a positive signal (+12V) or ground signal.
Emergency Power operation: If using a separate E-Power Battery, the circuit breaker for the AUX
relay on the SST-4 must be connected between the J6 and J5 female push-on connectors. If a
separate E-Power battery is NOT being used, the circuit breaker must be connected between the J6
and J7 connectors. See Figure 2 for connection locations.
1.
2.
Connection Notes

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 13
RED/WHT (J1 PIN-3)
80 AMP
BREAKER
+
WRS PART# CBW 1081
BATTERY +12 VOLTS
EXISTING
EXISTING
STARTER
SOLENOID
INSTALLER MUST CUT
EXISTING IGNITION
WIRE HERE
EXISTING
REFER TO ENGINE ECM
DOCUMENTATION FOR
WIRING INSTRUCTIONS
CIRCUIT
BREAKER
IGNITION
ELECTRONIC
CONTROL
MODULE
STARTER
BATTERY
ACC
START
ON
WHT/BLU (J1 PIN-5)
WHT/YEL (J1 PIN-4)
WHT/GRN (J1 PIN-2)
20A20A20A
STARTER
AUX.
E-PUMP IGNITION
D2
D3 D4
MENU UP DOWN
J1 T1 T2
TB1
1 7
AUXILIARY
BATTERY
WHT- GND
ORG/BLK- STARTER
RED-VBAT
RED/GRN-AUX BAT
PUR/GRN-AUX OUT
ORG-IGN IN
ORG/RED-IGN OUT
D5 D6 D7
IGNITIONAUX.STARTER
THROTTLE
AIR CYLINDER
START/STOP
AIR CYLINDER
E-POWER
AIR CYLINDER
PRESSURE SWITCHES
VEHICLE
BATTERY
MASTER
SWITCH
EMERGENCY
HYDRAULIC PUMP
SOLINOID
Wiring Diagram 1
Aux E-Power Battery. Emergency Power is provided from Auxiliary Battery. Note center Circuit
Breaker is positioned in the J6-J5 location.
1 2 3 4 5 6 7
TB1
6
3
J1
4
1
4 34 3
1
T1
2
T2
2 1
J1 INPUTS TBI T1 T2
PIN FUNCTION TSP FUNCTION PIN FUNCTION PIN FUNCTION
1 PRESSURE 1 GROUND 1 RLY1 NORM.CLOSED 1 RLY2 NORM.CLOSED
2 AUX TRIG 2 START OUT 2 RLY1 NORM.OPEN 2 RLY2 NORM.OPEN
3 MASTER 3 MAIN POWER (VBAT ) 3 RLY1 NORM.CLOSED 3 RLY2 NORM.CLOSED
4 THROTTLE 4 AUX IN 4 RLY1 NORM.OPEN 4 RLY2 NORM.OPEN
5 START/STOP 5 AUX OUT
6 GROUND 6 IGNITION IN
7 IGNITION OUT

Page 14 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
RED/WHT (J1 PIN-3)
80 AMP
BREAKER
+
WRS PART# CBW 1081
BATTERY +12 VOLTS
EXISTING
EXISTING
STARTER
SOLENOID
INSTALLER MUST CUT
EXISTING IGNITION
WIRE HERE
EXISTING
REFER TO ENGINE ECM
DOCUMENTATION FOR
WIRING INSTRUCTIONS
IGNITION
ELECTRONIC
CONTROL
MODULE
STARTER
BATTERY
ACC
START
ON
WHT/BLU (J1 PIN-5)
WHT/YEL (J1 PIN-4)
20A20A
STARTER
AUX.
E-PUMP IGNITION
D2
D3 D4
MENU UP DOWN
J1 20A T1 T2
TB1
1 7
WHT- GND
ORG/BLK- STARTER
RED-VBAT
PUR/GRN-AUX OUT
ORG-IGN IN
ORG/RED-IGN OUT
D5 D6 D7
IGNITIONAUX.STARTER
THROTTLE
AIR CYLINDER
START/STOP
AIR CYLINDER
PRESSURE SWITCHES
VEHICLE
BATTERY
MASTER
SWITCH
EMERGENCY
HYDRAULIC PUMP
SOLINOID
Wiring Diagram 2
No Aux E-Power Battery, power supplied from main battery through waterproof circuit breaker.
Emergency Power is provided from normal battery (there is no Auxiliary Battery) and E-power control
is from Start/Stop or Throttle signals. Programming state would include “C1” or “C2”.
1 2 3 4 5 6 7
TB1
6
3
J1
4
1
4 34 3
1
T1
2
T2
2 1
J1 INPUTS TBI T1 T2
PIN FUNCTION TSP FUNCTION PIN FUNCTION PIN FUNCTION
1 PRESSURE 1 GROUND 1 RLY1 NORM.CLOSED 1 RLY2 NORM.CLOSED
2 AUX TRIG 2 START OUT 2 RLY1 NORM.OPEN 2 RLY2 NORM.OPEN
3 MASTER 3 MAIN POWER (VBAT) 3 RLY1 NORM.CLOSED 3 RLY2 NORM.CLOSED
4 THROTTLE 4 AUX IN 4 RLY1 NORM.OPEN 4 RLY2 NORM.OPEN
5 START/STOP 5 AUX OUT
6 GROUND 6 IGNITION IN
7 IGNITION OUT

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 15
RED/WHT (J1 PIN-3)
+
BATTERY +12 VOLTS
EXISTING
EXISTING
STARTER
SOLENOID
INSTALLER MUST CUT
EXISTING IGNITION
WIRE HERE
EXISTING
REFER TO ENGINE ECM
DOCUMENTATION FOR
WIRING INSTRUCTIONS
IGNITION
ELECTRONIC
CONTROL
MODULE
STARTER
BATTERY
ACC
START
ON
WHT/BLU (J1 PIN-5)
WHT/YEL (J1 PIN-4)
20A20A
STARTER
AUX.
E-PUMP IGNITION
D2
D3 D4
MENU UP DOWN
J1
20A
T1 T2
TB1
1 7
WHT- GND
ORG/BLK- STARTER
INSTALLER SUPPLIED WIRE
PUR/GRN-AUX OUT
ORG-IGN IN
ORG/RED-IGN OUT
D5 D6 D7
IGNITIONAUX.STARTER
THROTTLE
AIR CYLINDER
START/STOP
AIR CYLINDER
PRESSURE SWITCHES
VEHICLE
BATTERY
MASTER
SWITCH
EMERGENCY
HYDRAULIC PUMP
SOLINOID
Wiring Diagram 3
No Aux E-Power Battery, simplied. Power supplied from main battery through ignition switch
circuit. Please note that this circuit puts extra demand on the ignition circuit. Wire of sufcient
gauge must be used. Check your vehicle electrical specications to be certain that his circuit will not
damage the ignition system. Emergency Power is provided from normal battery (there is no Auxiliary
Battery) and E-power control is from Start/Stop or Throttle signals. Programming state would
include “C1” or “C2”.
1 2 3 4 5 6 7
TB1
6
3
J1
4
1
4 34 3
1
T1
2
T2
2 1
J1 INPUTS TBI T1 T2
PIN FUNCTION TSP FUNCTION PIN FUNCTION PIN FUNCTION
1 PRESSURE 1 GROUND 1 RLY1 NORM.CLOSED 1 RLY2 NORM.CLOSED
2 AUX TRIG 2 START OUT 2 RLY1 NORM.OPEN 2 RLY2 NORM.OPEN
3 MASTER 3 MAIN POWER (VBAT) 3 RLY1 NORM.CLOSED 3 RLY2 NORM.CLOSED
4 THROTTLE 4 AUX IN 4 RLY1 NORM.OPEN 4 RLY2 NORM.OPEN
5 START/STOP 5 AUX OUT
6 GROUND 6 IGNITION IN
7 IGNITION OUT

Page 16 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
APPENDIX II. CONNECTION TABLES
Ignition relay on SST-4 is “Normally Closed”. If power is not supplied to the board, the
ignition circuit will be closed and the ignition function will not be interrupted.
The SST-4 hour meter can be triggered either by the MASTER signal or the SPARE signal
on J1 Pin 1. This is user-programmable, as described in Section 5. PROGRAMMING.
T1 and T2 are identical, except T1 controls Relay 1 and T2 controls Relay2.
1.
2.
3.
T1 Pin Label Function Vehicle Wire Label
1 RLY1 N.C. Common to throttle control relay one, Normally Closed Throttle Circuit RLY 1 NC
2 RLY1 N.O. Common to throttle control relay one, Normally Open Throttle Circuit RLY 1 NO
3 RLY1 N.C. Output from throttle control relay one, Normally Closed Throttle Circuit RLY 1 NC
4 RLY1 N.O. Output from throttle control relay one, Normally Open Throttle Circuit RLY 1 NO
T1 & T2 Connections
TB1
Pin# Label Function Vehicle Wire Label
(typical)
1 GND Ground (Use negative battery connection, not
vehicle chassis.) Battery (-) GND
2 START OUT Supplies power to starter when relay is enabled Output from key
“Start” STARTER
3 VBAT Supplies +12V to board in normal operation Battery (+) VBAT
4 AUX IN Auxiliary input. May be used for Emergency
Power or other user dened function. E-Power battery AUX BAT
5 AUX OUT Auxiliary output supplies high current output to
E-pump or other function when relay is enabled E-Pump AUX OUT
6 IGN IN Ignition input signal. Key side of ignition
splice IGN IN
7 IGN OUT Ignition output ECM side of
ignition splice IGN OUT
TB1 Connections
J1# Label Function Vehicle Wire Label
1 PRESSURE Pressure sensor trigger input. Engine oil or PTO
hydraulic uid sensor. PRESSURE
2AUX
TRIGGER
Triggers Auxiliary circuitry used for E-
power E-Pump switch AUX TRIG
3 MASTER Enables SST-4 operation and triggers on-
board hour meter Master enable switch MASTER POS
4 THROTTLE Triggers throttle circuitry on SST-4 board Bucket Throttle switch THROTTLE
5 START/STOP Triggers Start/Stop circuitry on SST-4
board
Bucket Start/Stop
switch START TRIG
6 GROUND Ground (Use negative battery connection,
not vehicle chassis.) Battery (-) GND
J1 Connections
T1 Pin Label Function Vehicle Wire Label
1 RLY2 N.C. Common to throttle control relay two, Normally Closed Throttle Circuit RLY 2 NC
2 RLY2 N.O. Common to throttle control relay two, Normally Open Throttle Circuit RLY 2 NO
3 RLY2 N.C. Output from throttle control relay two, Normally Closed Throttle Circuit RLY 2 NC
4 RLY2 N.O. Output from throttle control relay two, Normally Open Throttle Circuit RLY 2 NO
1 2 3 4 5 6 7
TB1
6
3
J1
4
1
4 34 3
1
T1
2
T2
2 1
J1 INPUTS TBI T1 T2
PIN FUNCTION TSP FUNCTION PIN FUNCTION PIN FUNCTION
1 PRESSURE 1 GROUND 1 RLY1 NORM.CLOSED 1 RLY2 NORM.CLOSED
2 AUX TRIG 2 START OUT 2 RLY1 NORM.OPEN 2 RLY2 NORM.OPEN
3 MASTER 3 MAIN POWER (VBAT) 3 RLY1 NORM.CLOSED 3 RLY2 NORM.CLOSED
4 THROTTLE 4 AUX IN 4 RLY1 NORM.OPEN 4 RLY2 NORM.OPEN
5 START/STOP 5 AUX OUT
6 GROUND 6 IGNITION IN
7 IGNITION OUT

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 17
APPENDIX IV. TRUCK MANUFACTURER TECH SUPPORT
Additional information from the truck manufacturers is provided in the references below:
General Motors:
www.gmuptter.com
Hotline 800-875-4742
Ford Motor Company:
www.eet.ford.com
Cummins:
www.cummins.com
Customer Assistance 1-800-DIESELS (1-800-343-7357)
International:
www.internationaldelivers.com
Tech Central Help Line 1-800-448-7825
Freightliner:
www.freightlinertrucks.com
APPENDIX III. REPLACEABLE PARTS
The following are replaceable parts on the SST-4. To order please see website at http://store.wiredrite.
com/store.
WRS # DESCRIPTION AMP # QTY
CBA1031 Circuit Breaker 3
RLY1164 Relay 3
CON7135 Amp, Mini Mate N’ Loc 6 Pos. Plug 172168-1 1
CON7120 Amp, Mini Mate N’ Loc 4 Pos. Plug 172167-1 2
CON7125 AMP, Mini Mate N’ Loc Socket 171639-1 14

Page 18 © Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0
APPENDIX V. AUTO STOP ON LOSS OF PRESSURE MODE
This mode will force the SST-4 into STOP mode if loss of pressure is detected on a user-
installed circuit. This will then allow the user-specied stop mode settings to control. This
mode is especially useful in the situation where the vehicle stalls and the e-pump must be
used to control the aerial device. Setting the SST-4 and supplying a pressure switch to monitor
either the engine oil or the PTO hydraulic pressure will permit an automatic fail-over to the
e-pump without operator intervention.
Two inputs are used: the MASTER (J1 pin 3) input, usually connected to a switch controlled
by the operator to activate the SST-4, and the PRESSURE (J1 pin 1) input, which should be
connected to a pressure switch that senses either engine oil or hydraulic uid pressure. When
in this mode, and pressure is lost, the SST-4 will be forced into STOP mode after the delay
specied in parameter “o”.
Since there are many different types of pressure switches available in the market, parameter
“P” is used to describe how your particular switch functions.
When the system is in this mode, the hour meter counts only when both the MASTER input
and the PRESSURE input are true.
The pressure switch may be installed to measure either engine oil pressure or PTO hydraulic
uid pressure. If the switch is on the PTO, it is possible that the truck will be stopped
automatically if the operator-controlled master switch is turned on, but the operator does not
engage the PTO before the time out interval specied in parameter “o”. For this reason, it is
strongly suggested that the MASTER and PTO function be combined onto one switch.
Be certain to specify a delay interval in parameter “o” of sufcient duration to allow any
other timers to complete. This is especially true if you are utilizing parameter “F” (Glow Plug
Delay) as it is possible to set up a situation where the vehicle can never be restarted if “F” is
set to a period longer than “o”.
APPENDIX VI. TIMER NOTES
By using Menu “E - Throttle Mode Timer,” a delay can be created to use with the parameters of
Menu b marked with a †.
Parameter 5, Timed Operations: (start with T1 & T2 OFF)
Throttle trigger input > Menu “E” Delay > T1 ON
Next Throttle trigger input > Menu “E” Delay > T1 OFF, T2 ON
Next Throttle trigger input > Menu “E” Delay > T1 & T2 ON
Next Throttle trigger input > Menu “E” Delay > T1 & T2 OFF
REPEAT cycle
Parameter 9:
As soon as MASTER power is applied > Menu “E” Delay > T1 latches ON
Throttle trigger input > NO DELAY, then T2 momentary
REPEAT cycle without delay until STOP mode is entered, then the DELAY is activated again
Parameter A:
As soon as MASTER power is applied > Menu “E” Delay > T1 latches ON
Throttle trigger input > NO DELAY, then T2 Latches ON
Next Throttle trigger input > NO DELAY, then T2 Latches OFF
REPEAT cycle without delay until STOP mode is entered, then the DELAY is activated again

© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 19
NOTES

© 2006 WIRED RITE SYSTEMS, INC.
5793 Skylane Blvd
Windsor, CA 95492
800.538.7483
Fax: 707.838.1050
info@wiredrite.com
www.wiredrite.com
This manual suits for next models
1
Table of contents
Popular Computer Hardware manuals by other brands

AMX
AMX RDD-DM4/277 Schematic diagram

Euresys
Euresys Picolo.net HD1 Reference manual

Atmel
Atmel Microcontroller with LIN Transceiver ATA6602 product manual

Opal-RT
Opal-RT OP5607 Installation and configuration

Trinamic
Trinamic PD 108-28-SE-485 Series Hardware manual

SilverStone
SilverStone argon series quick start guide

Renesas
Renesas Converter Board M3T-FLX-80NSD user manual

Cypress Semiconductor
Cypress Semiconductor CY7C1522AV18 Specification sheet

Digilent
Digilent chipKIT Network Shield Reference manual

Omega Engineering
Omega Engineering OMG-P232 manual

Kontron
Kontron CP-RIO6-923 user guide

Analog Devices
Analog Devices EV-RPG2 user guide