Temperature drop in floor covering
The difference between the temperature on the floor surface
and the temperature of the sensor depends on the heat flow and
heat resistance in the intermediate layers. Moreover, there is a
temperature variation in the layer between the pipes.
t = q(d1/1+ d2/2+…)
t = temperature difference °C
q = heat output, W/m²
d = thickness, m
= thermal conductivity, W/m°C
Calculation example
Required maximum floor surface temperature 27°C, installation
in a wooden suspended floor with heat emission plates, 55 W/m²,
floor covering consisting of 22 mm chipboard, = 0,14 W/m°C
and 7 mm laminate, = 0,12 W/m°C.
t = 55 (0,022/0,14 + 0,007/0,12) = 11,9°C
The temperature on the underside of the chipboard should not
therefore exceed 27 + 11.9 = 38.9 °C.
In view of temperature variations in the horiziontal direction in
the floor and the drop in temperature between the chipboard
and the temperaure sensor, the maximum limitation is set at
approximately 40°C.
Technical data
Length: 3 m
Sensor element: NTC, resistance
Precision: +/- 0,2°C @ 0°C to 70°C
Power consumption (25°C): < 75mW
Thermal time constant: < 10 secs. in stationary air.
Article numbers
Please note that not all items are available on every market
concerned.
Sensor, separate:
Wirsbo CoSy External temperature sensor, 3 m, Art no 80463
The sensor can be connected to:
Wirsbo CoSy Room thermostat, Public, 24V, Art no 80464 and
Wirsbo CoSy Room thermostat, Switch, 24V, Art no 80465
Thermostat, complete with sensor:
Room thermostat with temperature lowering, including external
sensor Art no 804651
Resistance , kV
Temperature, °C
Resistance of the temperature sensor
Fig 4
Fig 5 Electrical connection and settings
11 12
2 3 4 5 6
20 45
25 40
30 35 Setting button for max or min. limitation.
Adjustment knob for the limitation temperature of the external
temperature sensor.
The external temperature sensor is connected to terminal 11
and 12.The sensor can be extended by a maximum of 5 metres,
using 0.5 mm2 cable. Joining cables must be carried out safely,
e.g. in a box on the wall.