wirsbo proMIX 101 User manual

proMIX™101
Installation Manual

proMIX™101
Installation Manual
is published by Uponor Wirsbo
5925 148th Street West
Apple Valley, MN 55124
952-891-2000
© 2002 Uponor Wirsbo, All rights reserved.
First Edition
First Printing July 2002
Printed in the United States of America

1
INTRODUCTION
INTRODUCTION - Table of Contents
IMPORTANT NOTE:
If you are not familiar with how
the Wirsbo proMIX 101 operates,
or the theory behind settings for a
radiant system it is important you
review the Control Function
Overview. It will help with
understanding the functions of
the control within the hydronic
radiant heating system.
Quick Guide
If you are only INSTALLING
the proMIX 101 go to:
INSTALLATION
Steps 1-8
If you are only PROGRAMMING
the proMIX 101 go to:
PROGRAMMING
Steps 1-2
TABLE OF CONTENTS
INTRODUCTION
Control Overview .................................................................. 2-3
Navigating the Control ........................................................ 4-5
Viewing the Status of the System Performance................ 6
INSTALLATION
Step 1 – Checking Contents .................................................. 8
Step 2 – Control Base ........................................................ 9-11
Step 3 – Rough-In Wiring...................................................... 12
Step 4 – Attaching the Control to the Base ...................... 13
Step 5 – Mounting the Sensors .................................... 14-15
Step 6 – Electrical Connections to the Control............ 16-19
Powered Input Connection ............................ 16
Output Connections ........................................ 17
Sensor and Unpowered Connections.......... 18
Temperature Resistance Chart ...................... 19
Step 7 – Testing the Wiring ............................................ 20-22
Test the Sensors .............................................. 20
Test the Power Supply .................................... 21
Test the Powered Demand Inputs ................ 21
Test the Outputs .............................................. 22
Step 8 – Completing the Installation .................................. 23
PROGRAMMING
Step 1 – Programming the Control .............................. 25-30
Programming the "Adjust" Menu............ 26-30
Reset Mode ............................................ 26-28
Setpoint Mode ...................................... 29-30
Step 2 – Test Sequence ........................................................ 31
CONTROL FUNCTION OVERVIEW
Section A – General.......................................................... 33-36
Section B – Mixing Zones................................................ 37-39
Section C – Troubleshooting .......................................... 40-42
APPENDIX
IproMIX 101 Menu Tree.............................................. 44-45
II Application Drawings ................................................ 46-49
III Error Message Overview .......................................... 50-51
IV proMIX 101 Program Setup .......................................... 52

2
INTRODUCTION
INTRODUCTION - Control Overview

INTRODUCTION
CONTROL OVERVIEW
The Wirsbo proMIX 101 is a weather responsive,
single temperature reset control for hydronic
radiant heating systems. The proMIX 101 provides
either reset or setpoint supply water temperatures
through the use of a floating action mixing valve.
This control also protects the boiler from low return
water temperatures by monitoring the boiler return
water temperature. The proMIX 101 can function
as a standalone mixing control or function as an
expansion module to the Wirsbo SYSTEMpro 311.
3
INTRODUCTION
INTRODUCTION - Control Overview

INTRODUCTION
NAVIGATING THE CONTROL
The proMIX 101 (also referred to as "control") has
a Liquid Crystal Display (LCD) that lets users set up the
operation of the system. The proMIX 101 has three
push buttons for selecting and adjusting settings.
(See fig. a)
NOTE: It is recommended that the user record
control settings (for later review) on the Program
Setup Sheet provided in Appendix IV.
Menu (See fig. b)
• All items displayed by the control are organized into two
menus
• Menus are listed on upper right side of the display
• Control displays the “View” menu during normal
operation
• To select the Adjust Menu, press all three buttons
simultaneously for one second
(See fig. c)
• Within specific menu selections, a group of items can be
viewed and selected
Item (See fig. d)
• The abbreviated name of the selected item will be
displayed in the item field of the display
• To view the next available item, press and release the Item
button
• Once you have reached the last available item in a menu,
press and release the Item button to return the display to
the first item in the same menu
Adjustments (See fig. e)
• To make an adjustment to a control setting, first select the
appropriate menu with the Menu button
• Then select the item you want using the Item button
• Finally, use the up and/or down button to make the change
NOTE: You can get more information by viewing the
Status field of the LCD. The status field shows which
of the control’s outputs are active. Most symbols in
the status field can only be seen when the View
menu is selected.
4
INTRODUCTION
INTRODUCTION - Navigating the Control
VIEW
TARGET
I
NDR
DSGN
B
OIL
M
IX
O
UTDR
R
OOM WWSD
ADJUST
MAXMIN
UNOCC
Item
F
o
C
o
Open Close Mix
Demand
Motor
Speed
a
R
OM WWSD
UNOCC
Item
Open Close Mix
Demand
Motor
Speed
d
R
OM WWSD
UNOCC
Item
Open Close Mix
Demand
Motor
Speed
e
VIEW ADJUST
F
o
C
o
b
R
OM WWSD
UNOCC
Item
Open Close Mix
Demand
Motor
Speed
c

5
INTRODUCTION
INTRODUCTION - Navigating the Control
VIEW
TARGET
INDR
DSGN
BOIL
MIX
OUTDR
ROOM WWSD
ADJUST
MAXMIN
UNOCC
Mix
Demand
Item
Number Field
Displays the current value of
the selected item
{
Buttons
Select menus, items
and adjust settings
Menu Field
Displays the
current menu
Status Field
Displays the current
status of the control’s
inputs, outputs and
operation
Item Field
Displays an abbreviated
name of the selected item
F
o
C
o
Motor
Speed
Open Close
Display
Symbol Description
Pump
Displays when the mixing system
pump is in operation
Burner
Displays when the boiler relay
is turned on.
Occupied Schedule
Displays when the control is in
occupied (day) mode.
Unoccupied Schedule
Displays when the control is in
unoccupied (night) mode.
Units of Measurement
Indicates degrees Fahrenheit
or Celsius.
Pointer
Displays the control operation
as indicated by the text.
OCC
UNOCC
F,
o
C
o

INTRODUCTION
VIEWING THE STATUS OF
THE SYSTEM PERFORMANCE
• The View menu is available for viewing the current status of
the system performance
• While in the View menu, push the item button to scroll
through the available menu items showing the current
settings and temperatures in the system
OUTDR (See fig. a)
Shows actual outside temperature at outdoor sensor S4
location
MIX (See fig. b)
Shows actual mix supply temperature to the system at mix
supply sensor S1 during occupied mode
MIX TARGET (See fig. c)
The targeted mixed supply water temperature the control has
calculated in order to meet current conditions
BOIL (See fig. d)
Shows actual boiler return water temperature at the boiler
return sensor S3
6
INTRODUCTION
INTRODUCTION - Viewing the Status of the System Performance
a
b
c
d

INSTALLATION
TABLE OF CONTENTS
Step 1 – Checking Contents .................................................. 8
Step 2 – Control Base ........................................................ 9-11
Step 3 – Rough-In Wiring...................................................... 12
Step 4 – Attaching the Control to the Base ...................... 13
Step 5 – Mounting the Sensors .................................... 14-15
Step 6 – Electrical Connections to the Control............ 16-19
Powered Input Connection ............................ 16
Output Connections ........................................ 17
Sensor and Unpowered Connections.......... 18
Temperature Resistance Chart ...................... 19
Step 7 – Testing the Wiring ............................................ 20-22
Test the Sensors .............................................. 20
Test the Power Supply .................................... 21
Test the Powered Demand Inputs ................ 21
Test the Outputs .............................................. 22
Step 8 – Completing the Installation .................................. 23
7
INSTALLATION
INSTALLATION - Table of Contents

8
INSTALLATION
INSTALLATION - Step 1 - Checking Contents
INSTALLATION - STEP 1
CHECKING CONTENTS
Check the contents of this package.
The Wirsbo proMIX 101 should have:
proMIX 101
(A3040101)
Outdoor Sensor
(A3040070)
Two Universal Sensors
(A3060071)
Product Manual
If any of the contents listed are missing or damaged,
please contact your wholesaler or your Wirsbo sales
representative for assistance.
CAUTIONS AND
DISCLAIMERS
Failure to install and/or
operate this control
properly could result in:
• Damage to the
equipment
• Personal injury
• Property damage
It is up to you to make
sure this control is
installed safely in a way
that meets all codes and
standards that apply. Do
not use this electronic
control as a primary limit
control. Other controls
that are meant to be used
and certified to be used
as safety limits must be
placed into the control
circuit.
Carefully read the
Control Overview (page 3)
to make sure you have
chosen the proper control
for your application.
Warning Symbol: Indicates
presence of hazards which
can cause severe personal
injury, death or substantial
property damage if ignored
proMIX
™
101
Installation Manual

INSTALLATION - STEP 2
THE CONTROL BASE
Removing the Control from the Base
Follow steps a - g
Press down at the fingertip grips on top of the
front cover and pull out and down.
(See fig. a)
Lift the front cover up and away from the control.
(See fig. b)
Loosen the screws at the front of the wiring cover.
(See fig. c)
The wiring cover pulls straight out from the wiring
chamber.
(See fig. d)
9
INSTALLATION
INSTALLATION - Step 2 - The Control Base
a
b
c
d

Remove the safety dividers from the wiring chamber by
pulling them straight out of their grooves.
(See fig. e)
Press the control release clip on the base inside the
wiring chamber and slide the control upwards.
(See fig. f)
The control lifts up and away from the base.
(See fig. g)
Mounting the Base (See fig. h)
1) Find a convenient and accessible location typically in
the mechanical room
2) Following the hole pattern, mount the control base
using appropriate screws or bolts
10
INSTALLATION
INSTALLATION - Step 2 - The Control Base
e
f
g
hMounting holes
Knockout Locking Clip
Release Clip

The control can also be mounted on a standard
DIN rail. (See fig. i)
First remove the control from its base and then, using the
hooks and spring clip on the back of the control, mount
it onto the DIN rail. This will be a popular option for those
who prefer to mount the control inside a larger electrical
panel.
The wiring can enter the bottom or the back of the
enclosure. Knockouts provided in the base allow the
wiring to be run in conduit up to the enclosure. The base
also has holes that line up with the mounting holes of
most common electrical boxes.
11
INSTALLATION
INSTALLATION - Step 2 - The Control Base
i

INSTALLATION - STEP 3
ROUGH-IN WIRING
Things to note before you start wiring:
• All electrical wiring should end in the control base wiring
chamber
• The base has standard 7/8” (22 mm) knockouts
• Knockouts accept common wiring hardware and conduit
fittings
• Before removing knockouts, check wiring diagram and
select those sections of the chamber with common
voltages
• Do not allow the wiring to cross between low/high voltage
sections or else wires will interfere with safety dividers
(these dividers should be installed at a later time)
• Do not apply power to any of the wires during rough-in
wiring stage
• All wires should be stripped to 3/8"L (9 mm) for the correct
connection to the control
Wiring Components:
1) Install the various sensors indicated below as per instructions
listed and run the wiring back to the control base and label all
wires for later installation
Main Sensors:
• Outdoor Sensor S4
• Boiler Return Sensor S3
• Mixing Sensor S1
2) Run appropriate wire from all other system components
(pump, boiler, etc.) to the control base
3) Run wires from the 120 VAC power to the control base
• Use a clean power source to ensure proper operation
• Comply with local codes for minimum gauge and breaker
requirements
12
INSTALLATION
INSTALLATION - Step 3 - Rough-In Wiring
CAUTION
All wiring must be
performed by a licenced
professional and comply
with local trade practices
and codes.
Wirsbo does not take
responsibility for any
damage caused due to
failure to comply.

INSTALLATION - STEP 4
ATTACHING THE CONTROL
TO THE BASE
1) Push the proMIX 101 control into the base you mounted in
step 2
2) Slide the control down until it snaps firmly into place
(See fig. a)
13
INSTALLATION
INSTALLATION - Step 4 - Attaching the Control to the Base
a

INSTALLATION - STEP 5
MOUNTING THE SENSORS
Outdoor Sensor (S4) (See fig. a)
The Outdoor Sensor includes a 10 kΩthermistor which
provides an accurate measurement of the outdoor
temperature. The sensor is protected by a white U.V.
resistant PVC plastic enclosure.
Step One – Mounting (See fig. b)
NOTE: The temperature sensor (thermistor)
is built into the enclosure.
• Remove the screw and pull the front
cover off the sensor enclosure.
• The outdoor sensor can either be
mounted directly onto a wall or a 2" x 4"
electrical box. When the sensor is wall
mounted, the wiring should enter
through the back or bottom of the
enclosure. Do not mount the sensor with
the conduit knockout facing upwards as
rain could enter the enclosure and
damage the sensor.
• In order to prevent heat transmitted through the wall from
affecting the sensor reading, it may be necessary to install an
insulating barrier behind the enclosure.
• The outdoor sensor should be mounted on an exterior wall
which best represents actual outdoor temperature (a north
facing wall). It should not be exposed to heat sources such
as solar gain, exhaust ventilation or window openings.
• The outdoor sensor should be installed at an elevation
above the ground that will prevent accidental damage or
tampering. Installing the sensor in the shadow of the roof
eave is common.
Step Two – Wiring and Testing (See fig. c)
• Connect 18 AWG or similar wire to the two terminals provided
in the enclosure and run the wires from the outdoor sensor to
the control.
CAUTION: Do not run sensor wires parallel to
telephone or power cables. If the sensor wires
are located in an area with strong sources of
electromagnetic interference (EMI), shielded cable or
twisted pair should be used or the wires can be run
in a grounded metal conduit. If using shielded cable,
the shield wire should be connected to the Com Sen
terminal on the control and not to earth ground.
• Follow the sensor testing instructions in this brochure and
connect the wires to the control as per installation – step 6.
• Replace the front cover of the sensor enclosure.
14
INSTALLATION
INSTALLATION - Step 5 - Mounting the Sensors
Wires from outdoor
sensor to control terminals
(Com Sen - Out Sen)
Sensor is built into
the enclosure
c
Sensor with rear
entry wiring
Sensor
with bottom
entry wiring
Sensor mounted
onto 2” x 4”
electrical box
a
b

Universal Sensors (S1 and S3)
(See fig. d)
These Universal Sensors have a zinc sleeve for fast response
and a wide operating range. They can be used in a multitude
of applications. They are supplied with 10 inches (250 mm) of
2 conductor wire.
Step One – Mounting (See figs. e thru g)
NOTE: The Sensor is designed to mount on
a pipe or in a temperature immersion well.
• The Universal Sensor can be strapped directly to the pipe
using the cable tie provided. Insulation should be placed
around the sensor to reduce the effect of air currents on the
sensor measurement.
• The Universal Sensor should be placed downstream of a
pump or after an elbow or similar fitting. Proper sensor
location requires that the fluid is thoroughly mixed within the
pipe before it reaches the sensor.
Step Two – Wiring and Testing
CAUTION: Do not run sensor wires parallel to
telephone or power cables. If the sensor wires
are located in an area with strong sources of
electromagnetic interference (EMI), shielded cable or
twisted pair should be used or the wires can be run
in a grounded metal conduit. If using shielded cable,
the shield wire should be connected to the Com Sen
terminal on the control and not to earth ground.
• If it is necessary to connect 18 AWG wire to the two sensor
wires, wire nuts can be used to hold the wires together.
• Follow the sensor testing instructions given in this brochure,
and then connect the wires to the control.
15
INSTALLATION
INSTALLATION - Step 5 - Mounting the Sensors
e
f
d
g

INSTALLATION - STEP 6
ELECTRICAL CONNECTIONS
TO THE CONTROL
IMPORTANT: Test to be certain
no voltage is present in any wires.
120 VAC Power (See fig. a)
• Connect 120 VAC power supply to Power L and neutral N
terminals (3 and 4)
• Provides power to microprocessor and control display as well
as power to Mix P1 terminal (5) from Power L terminal (3)
Demand Connections
Demand to the control is generated from a thermostat zone
control module or external relay. This connection must have
24 VAC supplied to the demand terminals.
Mixing Demand (See fig. b)
• Apply a voltage between 24 VAC and 240 VAC across Mixing
Demand terminals (1 and 2)
Mixing Demand with Wirsbo Thermostat
NOTE: When connecting a Wirsbo Thermostat WT1
or WT2 directly to the Mix Demand Terminals 1 and 2,
a 0.5 watt 1000 ohm resistor needs to be installed
parallel as shown. A packet with the resistor and
schematic is included in the box.
Powered Input Connections
16
INSTALLATION
INSTALLATION - Step 6 - Electrical Connections to the Control
L
3
N
4
120 VAC
Power
Mix
Demand
1
2
24 to 240 VAC
b
a
1
24 VAC
TRANSFORMER
120 VAC
L
N
2
WIRSBO
RH W
WIRSBO
THERMOSTAT
WT 1
(A3030101)
or
WT 2
(A3030102)
NOTE:
0.5w 1000 Ohm
Resistor
54321
Mix
Demand

17
INSTALLATION
INSTALLATION - Step 6 - Electrical Connections to the Control
1) Boiler Contact (See fig. c)
Boiler terminals (7 and 8) are an isolated output. No power is
available on these terminals from the control.
• Use terminals as switch to make or break the boiler circuit
• When the proMIX 101 requires the boiler to fire, contact
closes between terminals 7 and 8
2) Mixing System Pump (Mix P1) (See fig. d)
Mixing System Pump (Mix P1) output terminals (5 and 6) are
powered outputs. When relay in the control closes, 120 VAC is
provided to Mix P1 terminal (5) from Power L and neutral
terminal (6). To operate the System Pump:
• Connect one side of system pump circuit to terminal (5)
• Connect the second side of pump circuit to neutral (N)
terminal (6)
4) Floating Action Mixing Valve (R Opn/R Cls/C)
(See fig. e)
The proMIX 101 utilizes a floating action mixing valve
to control the mixing system water temperature. Terminals
(9, 10 & 11) are powered 24 VAC from the control. There is no
need to provide a separate power source for the mixing valve
actuator.
• Connect to “Opn” (open) terminal from the mixing valve
actuator to the R Opn terminal (9) on the control
• Connect to “Cls” (close) terminal from the mixing valve
actuator to the R Cls terminal (10) on the control
• Connect to “C” (common) terminal from the mixing valve
actuator to the C terminal (11) on the control
Output Connections
4
LNMix
P1
6
N
120V (ac)
Power
LN
System
pump
35
d
910
R
Opn
R
Cls
C
11
Powered Output
Com
C
1
2
Cls
910 11
3
Opn
Mixing valve actuator
e
Boiler
Enable
7
8
c

18
INSTALLATION
INSTALLATION - Step 6 - Electrical Connections to the Control
WARNING: Do not apply power to these
terminals as this will damage the control
Connect the two wires from sensors to terminals described
below:
1) Outdoor Sensor S4 wires to Com and Out S4
terminals (16 and 17) (See fig. f)
• Measures outdoor air temperature
2) Boiler Return Sensor S3 wires to Com and
BRet S3 terminals (13 and 14) (See fig. g)
• Measures boiler return water temperature
3) Mixing Supply Sensor S1 wires to Com and
Mix S1 terminals (13 and 15) (See fig. h)
• Measures the mixed supply temperature after the mixing
system pump (P1)
NOTE: Sensor is normally attached
downstream of system pump (P1).
4) Unoccupied External Timer or Switch wires
to UnO Sw and Com terminals (12 and 13)
(See fig. i)
• When continuity is detected between terminals 12 and 13,
the control registers an unoccupied signal (Night mode)
Sensor and Unpowered Connections
Com
13
14
BRet
S3
Boiler
Sensor
g
Com
13
BRet
S3
14
Mix
15
S1
h
Com
16
17
Out
S4
f
UnO
Sw
12
13
Com
i
This manual suits for next models
1
Table of contents
Other wirsbo Measuring Instrument manuals