Worcester TD 200 Assembly Instructions

Installation and Operating Instructions
Room temperature controller for
heating appliances with bus-enabled
Heatronic 3 and RT 10
TD 200
6 720 612 220-00.1R
Order no 7 719 002 506
6 720 612 220 GB (05.09) OSW
INSTALLATION,
USER INSTRUCTIONS &
CUSTOMER CARE GUIDE
6 720 612 220-00.1R
TD 200
TEXT DISPLAY
FOR WORCESTER HEATING APPLIANCES
WITH BUS-ENABLED HEATRONIC 3 AND RT 10

2
6 720 612 220 GB (05.0 )
Dear customer,
Congratulations on having de ided in favour of a
top-quality produ t from our ompany.
The
TD 200
offers everything you an expe t
from a modern heating ontrol: It is both reliable
and energy saving.
Like all Bos h Group produ ts, the
TD 200
has
been produ ed and tested a ording to the most
stringent quality standards so that you an enjoy
the
WORCESTER
warmth for a long time to
ome.

3
Contents
6 720 612 220 GB (05.0 )
Contents
1 Technical data for the accessory
item 5
1.1 Standard package 5
1.2 Technical data 5
1.3 Accessories 5
2 Regulations 6
3 Installation 7
3.1 Installation 7
3.2 Electrical connections 10
4 Operation 11
4.1 Operating elements and symbols 11
4.2 Change room temperature and
operating mode 13
4.2.1 Set room temperature time
restricted 13
4.2.2 Advance the next switching time
and associated operating mode to
the current time 13
4.2.3 Changing the operating mode 14
4.3 Use menu 15
4.3.1 Program 15
4.3.2 Delete settings 17
4.3.3 Reset factory settings 17
5 MAIN MENU 18
5.1 MAIN MENU-Overview 18
5.2 Operating instructions in brief 1
5.3 Holiday 1
5.4 Heating 20
5.4.1 Program 20
5.4.2 Heating levels 21
5.4.3 Optimum Start 21
5.5 Domestic Hot Water 22
5.5.1 Program 22
5.5.2 Circ. pump runs 22
5.6 General Settings 23
5.6.1 Time and Date 23
5.6.2 Display format 23
5.6.3 Key lock 23
6 INFO 24
7 EXPERT SETTINGS 25
7.1 EXPERT SETTINGS-Overview 25
7.2 Operating instructions in brief 25
7.3 System errors 25
7.4 Maintenance 25
7.5 Service address 25
7.6 System info 26
8 Service display 26
9 General information 27
10 Troubleshooting 28
11 Settings 30
11.1 MAIN MENU-Settings 30
11.2 EXPERT SETTINGS-Settings 31
11.3 Time Programs 32
11.3.1 Heating Program 32
11.3.2 Domestic Hot Water Program 33
Index 34

4
Safety precautions
6 720 612 220 GB (05.0 )
Safety precautions
B
These instru tions must be observed to
ensure orre t operation.
B
Only have the a essories installed by an
authorised heating installer.
B
Only use these a essories in onjun tion
with the heating applian es listed. Observe
onne tion diagram!
B
Never onne t this a essory item to the
230 V mains ele tri ity supply.
B
Before assembling these a essories:
Interrupt voltage supply (230 V AC) to the
heating applian e and all additional devi es
using the bus.
B
For wall mounting: Do not mount these a es-
sories in wet rooms.
Symbols
Signal words indi ate the seriousness of the haz-
ard in terms of the onsequen es of not following
the safety instru tions.
•
Caution
indi ates that minor damage to
property ould result.
•
Warning
indi ates that minor personal injury
or serious damage to property ould result.
•
Danger
indi ates that serious personal injury
ould result. In parti ularly serious ases, lives
ould be at risk.
Notes ontain important information in ases
where there is no risk of personal injury or dam-
age to property.
Safety instructions
in this
document are identified by a
warning-triangle symbol and are
printed on a grey background.
i
Notes
are identified by the sym-
bol shown on the left. They are
bordered by horizontal lines
above and below the text.

5
Technical data for the accessory item
6 720 612 220 GB (05.0 )
1 Technical data for the accessory item
• The TD 200 serves to display boiler and sys-
tem information and for hanging the dis-
played values. If the Servi e button is pressed
on the boiler, the TD 200 serves purely as a
display for the Servi e mode.
• The TD 200 is a timer with time programs for:
– Heating : 7 day heating program with
6 swit hing times per day
– Hot water : 7 day hot water program
with 6 swit hing times per day
• Room temperature ontrol of an unmixed
heating ir uit is possible in onjun tion with
the RT 10. The TD 200 re eives the
current
room temperature
via the temperature sen-
sor integrated in the RT 10.
• If no RT 10 is onne ted, the TD 200 works
purely as a timer with On/Off fun tion for the
time program without onsideration of the
room temperature.
• The TD 200 has a battery power reserve of
approx. 20 months. If the TD 200 has not
re eived any power for longer than 20
months, the time and date are deleted. All
other settings are maintained.
• Installation options:
– In the heating applian e with bus-enabled
Heatroni 3
– With optional a essory:
Wall mounting with bus onne tion to the
heating applian e with bus-enabled
Heatroni 3
1 1 Standard package
TD 200 without wall mounting so ket for installa-
tion in the heating applian e.
1 2 Technical data
Fig. 1 Unit dimensions with base (acces-
sory)
1 3 Accessories
• Base for wall mounting
• Room temperature ontroller RT 10 .
i
The TD 200 can only be con-
nected to a heating appliance
with bus-enabled Heatronic 3
circuit board.
Nominal voltage
Bus supply
10...24 V DC
15 V DC
Nominal current
(without
lighting)
6 mA
Controller output
2-wire bus
Permissible ambient
temperature
0 ... +50
˚C
Class of protection
III
Type of protection:
- Installe in Heatronic 3
- Wall mounting
IPX2D
IP20
134
119
35
145
6 720 612 220-02.1R

6
Regulations
6 720 612 220 GB (05.0 )
2 Regulations
Related standards:
• BS EN60730-1:2001
• BS EN60730-2-7:1992
• Ele tro Magneti Compatibility and Radio
Spe trum Matters (ERM); Short Range
Devi es (SRD) ETSI
• EN300 220 1.
EC Directives:
• European Union Law Dire tive 2000/R4/EC
• Low Voltage Dire tive (73/23/EEC)
• Ele tro Magneti Compatibility Dire tive
(89/336/EEC)
• CE Marking Dire tive (93/68/EEC).

7
Installation
6 720 612 220 GB (05.0 )
3 Installation
3 1 Installation
Installation of the TD 200 in heating appliance with bus-enabled Heatronic 3
B
For a detailed des ription of the heating appli-
an e parts, see installation instru tions of the
heating devi e.
Fig. 2 Remove the outer casing
Fig. 3 Remove cover and blanking late
Fig. 4 Insert TD 200 in the guides
Danger:
risk of electric shock!
B
Before assembling these accessories:
Interrupt voltage supply (230 V AC) to the heating appliance and all additional de-
vices using the bus.
6 720 611 792-03.1R
3.
6 720 611 792-04.1R
4.
1. 2. 6 720 612 220-03.1R

8
Installation
6 720 612 220 GB (05.0 )
Fig. 5 Lock TD 200 into lace and re lace
cover
6 720 612 220-04.1R
2.
1.
3.
4.

Installation
6 720 612 220 GB (05.0 )
Installing the TD 200 on the wall
B
Use the wall mounting so ket a essory for
wall mounting.
Fig. 6 Select mounting location
Fig. 7 Wall mounting socket accessory
B
Make ele tri al onne tions (see Figure 10).
Fig. 8 Locate TD 200 u er art and slide
into frame
i
The mounting surface on the wall
must be even.
min.
0,3m
1,2 - 1,5m
6 720 612 220-05.1R
6 720 612 220-07.1R
6 mm 3,5 mm6 mm
3,5 mm
3.
2.
1.
6 720 612 220-06.1R

10
Installation
6 720 612 220 GB (05.0 )
3 2 Electrical connections
TD 200 in the heating appliance with bus-
enabled Heatronic 3 circuit board
B
Installation of the TD 200 automati ally re-
ates the bus onne tion via the three onta ts
(Figure 4).
Fig. 9 TD 200 integrated in the bus-enabled
Heatronic 3.
TD 200 on the wall
B
Bus onne tion from the TD 200 to additional
devi es using in the bus (e. g. RT 10):
Use ele tri al ables orresponding to type
H05 VV-... (NYM-I...) minimum.
Permissible able lengths of the bus-enabled
Heatroni 3 to the TD 200:
B
To avoid indu tive influen es, lay all ables
arrying low voltage lines of 230 V or 400 V
separately (minimum spa ing 100 mm).
B
Shield the ables in the ase of external
indu tive influen es.
This ensures that the ables are shielded
against external influen es (e.g. heavy urrent
ables, overhead onta t wires, transformer
stations, radio and television applian es, ama-
teur radio stations, mi rowave applian es
et ).
Fig. 10 TD 200 connected to the bus-enabled
Heatronic 3.
Fig. 11 Connection of the bus connections via
junction box (A)
Cable length Cross section
≤
80 m 0.40 mm
2
≤
100 m 0.50 mm
2
≤
150 m 0.75 mm
2
≤
200 m 1.00 mm
2
≤
300 m 1.50 mm
2
TD 200
124BB
RT 10
BB
6 720 612 218-03.1J
ST 19
Heatronic 3
AF
i
If the cable cross sections of the
bus connections from the TD 200
and from the
RT 10
to the bus-en-
abled Heatronic 3 are different:
B
Connect bus connections via a
junction box.
TD 200
124BB
RT 10
BB
6 720 612 220-09.1J
ST 19
AF
B
B
Heatronic 3
B
2
BB
A
B
2
BB
B
2
BB
6 720 612 220-08.1J
100 mm 100 mm

11
Operation
6 720 612 220 GB (05.0 )
4 Operation
4 1 Operating elements and symbols
Fig. 12 Standard dis lay when connected RT 10
912h15
18
21
24 h
3
6
6 720 612 220-01.1O
menu info
a
b
cd
e
f
h
g
advance advance
i
If no
RT 10
is connected, this standard display appears as follows:
912h15
18
21
24h
3
6
6 720 612 220-16.J

12
Operation
6 720 612 220 GB (05.0 )
Operating elements
a
Turn selection knob in the
+
direction: Select upper Menu/Info
texts or set value higher
Turn selection knob in the
-
direction: Select bottom Menu/Info
texts or set value lower
Press selection knob :
Open or save Menu/value
b
Operating mode switch:
Heating Hot water
Automatic mode Automatic mode
Continuous
High
or
On
Continuous
On
Continuous
Low
or
Off
Automatic mode
Continuous
Frost
Continuous
Off
c
Button :
To advance the next switching time
and the associated operating mode
=
High
or
On
=
Low
or
Off
=
Frost
for the heating to the current time.
Button :
To advance the next switching time
and the associated operating mode
On
or
Off
for hot water heating to the
current time
e
Button : Display values
f
Button : Open Menu
g
Button :
Show previous menu level
h
Button :
Delete/Reset value
i
In order to simplify this document,
the operating elements and oper-
ating modes will sometimes only
be identified by symbols, e.g.
or .
advance
advance
info
menu
Symbols
Current room temperature
(only with
RT 10
)
Flashing segment:
current time from
09:30
until
09:45
Full segments:
Heating program current day for
=
High
or
On
(1 Segment = 15 min)
Empty segments:
Heating program current day for
=
Low
or
Off
(1 Segment = 15 min)
No segments:
Heating program current day for
=
Frost
(no segments)
Operating mode
High
or
On
for
heating
Operating mode
Low
or
Off
for
heating
Operating mode
Frost
or
Off
for
heating
Automatic mode for heating
Holiday program
Burner on
+
Upper Menu/Info texts or value
higher
-
Bottom Menu/Info texts or value
lower
ok
Open or save Menu/value
Call up parent menu level
Delete/Reset value
Advance next switching time and
the associated operating mode
=
High
or
On
=
Low
or
Off
=
Frost
for the heating to the current time.
Advance next switching time and
the associated operating mode
On
or
Off
for hot water heating to the
current time.
9
21
15
3
advance
advance

13
Operation
6 720 612 220 GB (05.0 )
4 2 Change room temperature and
operating mode
4 2 1 Set room temperature time
restricted
To permanently hange the room temperature,
see Chapter 5.4.2 on page 21.
Without the RT 10 this fun tion is not available.
If an RT 10 is onne ted and the standard dis-
play is displayed in Automati mode :
B
Set required room temperature with .
The temperature setting is effe tive until the
next swit hing time. After this the room tem-
perature set for the heating program is valid.
4 2 2 Advance the next switching time
and associated operating mode to
the current time
To permanently hange the operating mode, see
Chapter 4.2.3 on page 14.
Heating Advance
If the standard display is displayed in Automati
mode :
B
Press to advan e the next swit hing
time and asso iated operating mode
=
High
or
On
=
Low
or
Off
=
Frost
for the heating to the urrent time.
The display shows
Heating Advance on
and the altered data.
If the next swit hing time of the heating pro-
gram is ex eeded,
Heating Advance on
is
reset and Automati mode is a tive again.
To an el
Heating Advance on
:
B
Press again.
Hot Water Advance
If the standard display is displayed in Automati
mode or ontinuous e onomy is displayed:
B
Press to advan e the next swit hing
time and asso iated operating mode
On
or
Off
for hot water heating to the urrent time
The display shows
Hot Water Advance on
and the altered data.
If the next swit hing time of the hot water pro-
gram is ex eeded,
Hot Water Advance on
is
reset and Automati mode is a tive again.
Hot Water Advance on
Can el in advan e:
B
Press again.
iUse the function if there is no
longer a demand for heat or if the
home is to be left for a longer pe-
riod or if an unexpected return to
the property occurs.
advance
advance
advance
advance

14
Operation
6 720 612 220 GB (05.0 )
4 2 3 Changing the operating mode
Automatic mode
(default setting)
•Heating with RT 10:
Automati hange between High /
Low / Frost orresponding to the heat-
ing program. The TD 200 ontrols the room
temperatures set in the submenu Heating
levels (see Chapter 5.4.2 on page 21).
•Heating without RT 10:
Automati hange between On / Off
orresponding to the heating program. During
On the flow temperature set on the heating
applian e is ontrolled.
•Hot water:
Automati hange On / Off orresponding to
the hot water program entered.
Continuous heating
•Heating with RT 10:
The TD 200 ontinuously ontrols to the room
temperature set in the submenu Heating lev-
els for High (see Chapter 5.4.2 on
page 21). The heating program is ignored.
•Heating without RT 10:
A ontinuous ontrol to the flow temperature
set on the heating applian e is performed.
The heating program is ignored.
•Hot water with combination heating
appliance:
If the ECO button is not pressed on the heat-
ing applian e, hot water is immediately availa-
ble. The hot water program is ignored.
•Domestic hot water storage tank:
Hot water is ontinuously ontrolled to the hot
water temperature set on the heating appli-
an e. The hot water program is ignored.
Continuous low mode
•Heating with RT 10:
The TD 200 ontinuously ontrols to the room
temperature set in the submenu Heating lev-
els for Low (see Chapter 5.4.2 on
page 21). The heating program is ignored.
•Heating without RT 10:
A ontinuous ontrol to the flow temperature
whi h orresponds to the heating applian e
frost prote tion is performed. The heating pro-
gram setting is ignored. The heating remains
swit hed off apart from the heating applian e
frost prote tion
•Hot water:
Automati hange On / Off orresponding to
the hot water program entered.
Continuous frost protection
•Heating with RT 10:
The TD 200 ontinuously ontrols to the room
temperature set in the submenu Heating lev-
els for Frost (see Chapter 5.4.2 on
page 21). The heating program is ignored.
•Heating without RT 10:
A ontinuous ontrol to the flow temperature
whi h orresponds to the heating applian e
frost prote tion is performed. The heating
remains swit hed off apart from the heating
applian e frost prote tion. The heating pro-
gram is ignored.
•Hot water with combination heating
appliance:
Hot water is immediately available. The hot
water program is ignored.
•Domestic hot water storage tank:
The hot water an ool down to 10˚C. The hot
water program is ignored.

15
Operation
6 720 612 220 GB (05.0 )
4 3 Use menu
4 3 1 Program
Call up Main Menu
BPress button .
The display lights up and the Main Menu is
shown.
Fig. 13 Main Menu
Select submenu
BTurn sele tion knob until the the required
menu item is highlighted.
In the example: Sele t Heating.
BPress sele tion knob to onfirm the
sele tion.
The submenu is displayed.
Fig. 14 Submenu: Heating
BTurn sele tion knob until the the required
menu item is highlighted.
In the example: Sele t Program.
BPress sele tion knob to onfirm the
sele tion.
The next submenu is displayed.
Fig. 15 Submenu: Heating Program
BTurn sele tion knob until the the required
menu item is highlighted.
In the example: Sele t Mo - Fr.
BPress sele tion knob to onfirm the
sele tion.
The next submenu with the pre-programmed
swit hing times and operating modes P1 to
P6 is displayed.
Fig. 16 Submenu: Heating Program Mo - Fr
iThe programing steps are always carried out according to the same principle. The func-
tions of the operating elements and the meaning of the symbols are described in
Chapter 4.1 from page 11, e.g. to enter a heating program, perform the following pro-
gramming steps (example with RT 10 present).
menu
912h15
18
21
24h
3
6
6 720 612 220-10.1R
912h15
18
21
24h
3
6
6 720 612 220-11.1R
iThe segments for the heating pro-
gram are only displayed if all
switching times for Mo - Fr are
the same.
912 15
18
21
24
3
6
h
h
6 720 612 220-12.1J
912 15
18
21
24
3
6
h
h
6 720 612 220-13.1O

16
Operation
6 720 612 220 GB (05.0 )
Set values
BTurn sele tion knob until the the required
menu item is highlighted.
In the example: Sele t P1.
BPress sele tion knob to onfirm the
sele tion.
The swit hing time to be hanged and the
asso iated segment flashes.
Fig. 17 Submenu: Heating Program Mo - Fr
BTurn sele tion knob to set the swit hing
time.
In the example: Set 05:30.
The asso iated segments hange at the same
time.
BPress sele tion knob to save the swit h-
ing time.
The swit hing time saved is also a epted for
the individual days Monday to Friday.
The operating mode to be hanged and the
segment of the new swit hing time flashes.
Fig. 18 Submenu: Heating Program Mo - Fr
BTurn sele tion knob to set the operating
mode.
In the example: Set Low .
BPress sele tion knob to save the operat-
ing mode.
The operating mode saved is also a epted
for the individual days Monday to Friday.
The setting for P1 is now omplete. The
altered swit hing time, operating mode and
segments are displayed.
Fig. 19 Submenu: Heating Program Mo - Fr
BSet further swit hing times and operating
modes P2 to P6 as des ribed above.
-or-
BSele t menu level:
– Push button or
– Turn sele tion knob until the menu
item back is highlighted and press the
sele tion button to onfirm the sele -
tion.
The parent menu is displayed.
End programming
BPress the button.
912 15
18
21
24
3
6
h
h
6 720 612 220-14.1J
912 15
18
21
24
3
6
h
h
6 720 612 220-24.1O iThis process can be repeated for
Saturday and Sunday program-
ming and individual days.
912 15
18
21
24
3
6
h
h
6 720 612 220-25.1O
menu

17
Operation
6 720 612 220 GB (05.0 )
4 3 2 Delete settings
Either overwrite the value for delete it using the
button .
BSele t the value to be deleted in the Menu.
In the example: Sele t P1.
BPress the button.
The deleted value flashes.
Fig. 20 Submenu: P1 deleted
BPress the sele tion knob to save the
swit hing time.
BPress the button to return to the stand-
ard display.
4 3 3 Reset factory settings
Reset a program
Example for resetting a heating program:
BSele t the menu Heating > Program >
Reset to factory.
BPress the sele tion knob to onfirm the
sele tion.
BTurn the sele tion knob to set Yes.
BPress the sele tion knob to save the set-
ting.
In the example Heating Program appears
when resetting this help text:
Fig. 21 Hel text: Reset to factory
BPress the sele tion knob to return to the
Menu.
Reset all settings
If the standard display is set:
BKeep and pressed at the same
time until the following warning text is dis-
played:
Fig. 22 Warning text: Total reset
BIf you wish to perform the total reset:
Continue to keep pressed at the
same time until the following help text is dis-
played:
Fig. 23 Hel text: Total reset
All personal settings have been reset to the
fa tory setting.
BPress the sele tion knob to return to the
standard display.
912 15
18
21
24
3
6
h
h
6 720 612 220-17.1O
menu
912h15
18
21
24h
3
6
6 720 612 220-18.1R
iAll personal settings are reset to
the default settings with this func-
tion.
menu
912h15
18
21
24h
3
6
6 720 612 220-19.1R
menu
912h15
18
21
24h
3
6
6 720 612 220-20.1R

18
MAIN MENU
6 720 612 220 GB (05.0 )
5 MAIN MENU
5 1 MAIN MENU-Overview
MAIN MENU Submenu Description
1 2 3 Page
back
Holiday back
1
Start - -
End - -
Heating level - -
Domest. hot water - -
Heating back
Program back
20
Mo - Fr back
P1, P2 ... P6
Sa - Su back
P1, P2 ... P6
All days back
P1, P2 ... P6
Monday, Tuesday ... Sunday back
P1, P2 ... P6
Reset to factory -
Heating levels1) back
21
High -
Low -
Frost -
Optimum Start1) -- 21
Domestic Hot Water back
Program back
22
Mo - Fr back
P1, P2 ... P6
Sa - Su back
P1, P2 ... P6
All days back
P1, P2 ... P6
Monday, Tuesday ... Sunday back
P1, P2 ... P6
Reset to factory -
Circ. pump runs - - 22
General Settings back
Time and Date back
23
Time -
Date -
Summer-/Wintertime -
Time adjustment -
Display format back
23
Time -
Date -
Temperature -
LCD contrast -
Key lock - - 23
1) Heating with RT 10

1
MAIN MENU
6 720 612 220 GB (05.0 )
5 2 Operating instructions in
brief
: MAIN MENU open/ lose
: Sele t submenu/Set value
: Open submenu/Save value
or back: Call up parent menu level
Navigation in the menu stru ture, programming,
deleting values and resetting ba k to the fa tory
settings are des ribed in detail in Chapter 4.3 on
page 15.
5 3 Holiday
The Holiday program ontrols the heating and
hot water heating for the operating mode set in
the holiday program (frost prote tion is ensured).
•Holiday > Start:
– If the date for Start is today, the Holiday
program starts immediately.
– If the date for Start is from tomorrow or
later, the Holiday program starts at 00:00
(= 12:00 am) on the day set.
•Holiday > End:
The Holiday program ends at
23:59 (= 11:59 pm) on the day set
•Holiday > Heating level:
Operating mode for the heating during the
Holiday program
•Holiday > Domest hot water:
Operating mode for the hot water during the
Holiday program.
If the Holiday program is a tive, the following will
appear for example:
Fig. 24 Holiday active
Can el Holiday mode in advan e:
BSele t Menu Holiday > Start and press
.
The display shows --:--:----.
BPress the sele tion knob to save the set-
ting.
iFactory settings, setting range and personal settings:
Chapter 11 from page 30.
menu
912h15
18
21
24 h
3
6
6 720 612 220-26.1O

20
MAIN MENU
6 720 612 220 GB (05.0 )
5 4 Heating
5 4 1 Program
Default setting (Automatic mode)
Heating with RT 10:
• Automati hange between High /
Low / Frost orresponding to the heat-
ing program entered.
• Operating mode High :
The TD 200 ontrols to the room temperature
set for the the operating mode High.
• Operating mode Low :
The TD 200 ontrols to the room temperature
set for the the operating mode Low.
• Operating mode Frost :
The TD 200 ontrols to the room temperature
set for the the operating mode Frost.
Heating without RT 10:
• Automati hange between heating On /
Off orresponding to the heating program
entered.
• Operating mode On :
The heating applian e ontrols to the flow
temperature set.
• Operating mode Off :
The heating applian e ontrols to the flow
temperature whi h orresponds to the heat-
ing applian e frost prote tion.
Setting options
•Heating with RT 10: Maximum six swit hing
times per day with three different operating
modes (High / Low / Frost).
•Heating without RT 10: Maximum six
swit hing times per day with two different
operating modes (On / Off).
• optionally the same times for ea h day, Mon-
day - Friday, Saturday - Sunday or different
times for ea h day
• optionally different times for ea h day or the
same times for:
– Ea h day (All days)
– Monday to Friday (Mo - Fr)
– Saturday and Sunday (Sa - Su)
• shortest swit hing period is 15 minutes
(= 1 Segment).
Set switching times and operating mode
•Mo - Fr: Begin Monday to Friday at the same
time with the sele ted operating mode.
•Sa - Sun: Begin Saturday and Sunday at the
same time with the sele ted operating mode.
•All days: Begin ea h day at the same time
with the sele ted operating mode.
• individual week day (e.g. Thursday): Begin
ea h Thursday at the same time with the
sele ted operating mode.
•Reset to factory: Reset swit hing times and
operating modes, see Chapter 4.3.3 on
page 17.
iSet the flow temperature control-
ler on the heating appliance to
the maximum inlet temperature
required.
iDeactivate unrequired switching
times by deleting them.
Table of contents