manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Xpelair
  6. •
  7. Fan
  8. •
  9. Xpelair LVCF20 User manual

Xpelair LVCF20 User manual

‘‘``````
567-2069-01
Revision D
8
UK: The fan is guaranteed against defects for 3 years fromthe date of purchase.
• Xpelair reserve the right torepair or replace the fan.
• Keep your purchase receipt.
• Anyproblems, contact the address below.
UK: Xpelair have a comprehensive range of services including:
• Free technical advice Help-Desk fromEngineers on all aspects ofventilation
• Free design service, quotations and site surveys
Outside UK: See International section below.
Please ask for detailson:
Tel +44 (0) 8709 000430
Fax +44 (0) 8709 000530
Alsoat the address below
Applied EnergyProducts Ltd, Morley Way, Peterborough, PE2 9JJ, England
Tel: +44 (0) 1733 456789
Fax: +44 (0) 1733 310606
Sales/Spares Hotline: +44 (0) 8709 000420
Sales/Spares Faxline: +44 (0) 8709 000520
Web: http:/www.xpelair.co.uk
Guarantee
Technical Advice & Service
International
Head Office – UK Sales Office and Spares
Guarantee – Contact your local distributoror Xpelair direct
Technical advice and Service – Contact your local Xpelair distributor.
Xpelair
SafetyExtra LowVoltage
Centrifugal Ducted Fans
•LVDX200 Standard
•LVDX200T Timer
Condensation Control Fans
•LVCF20 Pull Cord
•LVCF20T Pull Cord/Timer
Installationand Maintenance Instructions
Retainforfuture reference
Forspeed andease ofinstallation,your
installationmay require someoftheAncillaries
indicated in “Ancillary Options”.
.
1. Mark on thewall the centreof theduct holeA.
2. Use this centreto cut an opening through the
wall 117mm dia. with aslightfall to the
exterior.
3. Fit thewall tube(not supplied), and motar into
place.
1. Mark on thewall the centreof theduct hole A,
and drill a pilot hole through both walls.
2. Use thecentre to mark arectangular holefor
theinner wall using thedimensionsA.
3. Cut therectangular holethrough theinner
wall.
4. Go outsideand cuta117mm diameterholein
theouterwall using the small holeas the
centre.
5. Measurethe wall thickness.
6. Cut thewall tube (notsupplied), sothat it is
64mm less than thewall thickness.
This method requires a spaceabove the ceiling, such
as aloft orattic,to provideaccess for 100mm
internal diameterducting.
1. Mark on theceiling thecentre of theducthole
A,avoiding ceiling joists andburiedcables
etc.
2. Cut a117mm diameter holeusing the marked
centre.
For 100mm diameter ducting:
This method requires a spaceabove the ceiling, such
as aloft orattic,to provideaccess for 100mm
internal diameterducting.
1. Mark arectangular hole using thedimensions
B.
2. Cut the hole, avoiding ceiling joists and buried
cables etc.
For flat ducting:
•This fan can beinstalledwithin a50mm void
without thecircular spigot ?(Fig. E). Flatducting
adapterkit(FDA) available.
1. Removethefront cover •(Fig. C)
2. Fitthe foamtape supplied around the
circular spigot ?(Fig. E).
3. Removethe electrical cover •(Fig. E). The
impellercan be removedto easeaccess (if
required). This is a push on/pull off assembly.
LVCF20 /LVCF20T Only(Fig. D)
4. Thecorrectcondensation control speedshould
beselectedto suittheroomsizein whichthe
fan is to beinstalled.Slide the switch Xto the
requiredposition. Pleasenotethatthe fanis
factory set to “Position 2”.
5. Switch Position Size/ RoomVolume (m³)
1 Large (34 and above)
2 Medium(28 – 34)
3 Small (less than 28)
LVCF20 /LVCF20T Only(Fig. D)
6. Thefan can besetso thatit providesconstant
trickleextraction. Slide theswitch Yto the
requiredposition. Pleasenotethatthe fanis
factory set to “Position 0”.
7. Switch Position Setting
0 Trickleextraction OFF
1 Trickleextraction ON
LVDX200T/ LVCF20T Only(Fig. D)
8. Thefan can besetso that there is a2-minute
delayed start to its operation whenusedwith
an external on/offswitch. Slidethe switch Zto
therequired position. Please notethatthefan
is factoryset to “Position 0”
9. Switch Position Setting
0 Time delaystart OFF
1 Time delaystart ON
Thefan mustnot bemountedwhere ambient
temperatures are likely to exceed 40°C.
1. Place the ducting into thehole and align to the
required position. If wall mounting, ensurethat
theducting slopesdownand awayfromthe
fan.
2. Mark the positions of the threefixing holes A
in fan box ?(Fig. E).
3. Ifwall mounting, drill three holes 5.5mm
diameterforwall plugs (supplied).Ifceiling
mounting B,use appropriate fasteners (not
supplied).
4. Cutoutthecable inlethole,if required, inthe
surround ?and slitthecablegrommet. Slide
thesurround ?over the fanbox ?.
5. Pass theelectrical cables intothefan box ?
through therearcable inletholeand surround,
and re-fitthecablegrommet. Ensure that the
cable grommetis inplace and a tight fit.
6. Offerthefanbox ?uptothewall or ceiling.
Ensurethecircular spigot ?enters the
ducting.
7. Fixthefan box ?tothe wall using screws ?
or to theceiling using appropriatefasteners
(notsupplied).
Thesurround ?is not required. Fitthe ducting to
the circular spigot?.
Ifthe hole size is as recommended:
1. Assemblethe three fan bodyclamps ?to the
fan box ?using screws ?.
2. Slit the cablegrommet. Pass theelectrical
cables into thefanbox ?through thecable
inlet hole and cable grommet.
Ensure cable grommet is inplaceandatight fit.
3. Offer the fan box ?up to thewall.
4. Tighten up thethree screws ?until thefan is
clampedto the innerwall. Thefan body
clamps ?will rotateto an automaticstop
position. DO NOT OVERTIGHTEN.
Ifthehole sizeis largerthanrecommended i.e.
larger thantheflange onthefanbox ?(Mostly
related to“retro-fit” installations):
1. Thefan bodyclamps ARE NOT suitable.
Constructawooden frame of INTERNAL
dimensions 203 x233mm.Depth should beat
least50mm.Fitthe wooden frame intothe
internal wall and makegood thehole.
2. Offer the fan box ?up to thewall.
3. Screwthefan box ?to thewoodenframe
using the slots in theflange(screwsnot
supplied).
1. Thesurround ?is not required.
2. Insertthefan box ?into thehole and mark
four positions using the slots in theflange B.
3. Removethefan box ?fromceiling andfit the
four ceiling clips (supplied) overthe edgeof
thehole, so that theclips align with the marks
on the ceilingB.
4. Drill 4pilotholesintotheceilingthrough the
hole ofeachclip, ensuring notto damage the
clip, and fittheclips ensuring correct
alignment.
5. Fit theducting tothe circular spigot?.
6. Offer the fan box ?up to theceiling.
7. Slit the cablegrommet. Pass theelectrical
cable intothe fanbox ?through thefront
cable inlethole.
Ensure cable grommet is inplaceandatight fit.
8. Using the screws 11 (Fig B),fixthefan box
flangeto the ceiling clips.
Fit an outergrille(CF20 variants only)to theouter
wall. Forceiling mounting, useappropriate
ancillaries (notsupplied).
Thetransformer Acan befixed directlyto the wall.
Thetransformercan besitedin aloft or in a
convenientposition on awall (notceiling). The
transformer must not becovered by loft
insulation. For wall mountingthe Fan mustbe
orientatedas shownin Htofulfil ingress
protectionrequirements.
IMPORTANT
1. READ ALL THESEINSTRUCTIONS & WARNINGS FULLYBEFORE COMMENCINGINSTALLATION.
2. INSTALLATIONSANDWIRINGMUST CONFORM TO CURRENT IEE REGULATIONS(UK),LOCALOR APPROPRIATE
REGULATIONS(OTHER COUNTRIES). IT IS THEINSTALLER’S RESPONSIBILITY TOENSURE THAT THEAPPROPRIATE
BUILDING CODESOF PRACTICE ARE ADHEREDTO.
3. A QUALIFIED ELECTRICIAN MUSTSUPERVISE ALL INSTALLATIONS.
4. THESE APPLIANCES ARE INTENDED FOR CONNECTIONTO FIXED WIRING.
5. CHECK THAT THEELECTRICAL RATING SHOWN ONTHE TRANSFORMERMATCHESTHE MAINS SUPPLY.
6. SITE BOTHFANAND TRANSFORMER AWAY FROM DIRECT SOURCES OF HEAT (I.E. GAS COOKERSOREYELEVEL
GRILLES.THEFAN MUST NOTBEMOUNTED WHEREAMBIENT TEMPERATURESARE LIKELYTOEXCEED 40ºC. THE
TRANSFORMER MUSTNOTBE MOUNTED WHERE AMBIENT TEMPERATURES ARELIKELY TOEXCEED 40ºC.
7. WHEN THEFANIS INSTALLED IN AROOMCONTAININGAFUEL BURNINGAPPLIANCE,THE INSTALLER MUSTENSURE
THAT AIR REPLACEMENT ISADEQUATEFOR BOTH THE FAN AND THEFUELBURNING APPLIANCE.
8. ENSURETHAT ALLRELEVANTSAFETYPRECAUTIONS(CORRECT EYE PROTECTION AND PROTECTIVECLOTHINGETC)
ARE TAKEN WHEN INSTALLING, OPERATING AND MAINTAINING THIS FAN.
9. GENERALGUIDANCE FOR SITINGTHE FAN SEE “FIG.G”. ALWAYSSITE FAN AS HIGHASPOSSIBLE.
10. IF ANYSECTIONOFTHEDUCTWORK IS POSITIONED HIGHER THAN THE FANACONDENSATIONTRAP (XCT100)MUSTBE
FITTED AS CLOSEASPOSSIBLE TO THE FAN.
11. THIS APPLIANCE IS NOT INTENDED FOR USE BY YOUNGCHILDREN OR INFIRM PERSONS WITHOUT SUPERVISION. YOUNG
CHILDRENSHOULD BE SUPERVISEDTO ENSURE THEY DO NOT PLAY WITH THEAPPLIANCE.
If installing the fan on awall (surface
mounting)
If installingthefan in a wall (flush mounting)
If installingthefan on a ceiling (surface
mounting)
If installingthefan in a ceiling (flush
mounting)
Preparing the fan for installation
Setting thecondensation speed
Setting thetricklespeed
Setting thetime delay start
Mounting theFan
Mounting thefanon awall or ceiling (surface
mounting)
Ifmounting the fan in a wall (flush mounting)
Ifmounting thefan in a ceiling (flush
mounting)
Terminating theducting
Mounting thetransformer
2
7
F
E
G
6
Thetransformer must also notbe mounted
within0.6mofabath or shower cubicle, uptoa
height of2.25m.
Thetransformer must not be mountedwhere
ambient temperatures are likely to exceed40°C.
1. Remove thetwoscrewssecuring thecover,
removecover.
2. Position thetransformeron thewall, and mark
thetwo fixing holes.
3. Drill and plug thetwoholesandfixthe
transformer with thescrews supplied.
Forloft mounting:
Thetransformercan be fixedto awoodensurface
with thetwo screws supplied.
Forfixed surface wiring:
Usetherectangular knockouts on eachside(X).
Theseaccept25 x 16mmtrunking (not supplied)
Forconcealed wiring:
Usetheroundknockouts (Y).
Forconnectionto a window mounted fan:
Useknockout (Z). Useflexiblecable.
Whenusing thesideentrieswith flexible cable, a
hole suitablefor thecablesizemustbemade
centrallyin the rectangularsection.
1. Isolate theelectricitysupplyandremove all
fuses.
Theterminal blockwill acceptcable upto
1.5mm².
2. Ameans fordisconnection in all poles must be
incorporated in thefixedwiring in accordance
withthewiring rules.
3. Use suitably rated3-core or4-core cable
dependenton application.
4. Remove the retaining screwsof theterminal
cover •, if still in position.
5. Wirethefan asshownin Fusing thecable
clampprovided. Check fan model to diagram.
LVDX200T: “LH” =Live(High Speed) /
“LL”= Live(LowSpeed)
6. Replacethe terminal cover •and fasten the
retainingscrews.
7. See section on “User adjustments” if you wish
to usesettingsother than thosethathavebeen
factory set.
8. Refitthe front cover •(Fig. C).
9. Connect thecablefromthe isolating switchto
electrical supplywiring, and re-check
installation.
10. Refitfuses before turning on electricitysupply.
11. For fixedwiring circuits, theprotectivefuse
forthe appliancemust not exceed 5A.
ForAustralia Only
LVCF20 – Connection to the supply – flexible3-
core cablewith 3pinplug top for insertion into an
approved 10A wall mountedsurfaceswitchwithat
least3mm clearancebetween contacts.
ALL OTHERS – Permanentlyconnectedto the
supplyand a remoteswitchcontrols operation. They
shouldbedirectlywired to the supply through an
approved 10A wall mountedsurfaceswitchwithat
least3mm clearancebetween contacts.
Always wire via the cable clamp.
1. Removethecable clamps.
2. Wirethetransformeras shownin F. Checkthe
fan model to diagram.
3. Ensureall connections aretight.
4. Replacethe clamps and two screws. Ensurethe
cableis firmlyretained bytheclamp.
5. Replacethe transformercoverwith thetwo
screws.
6. Switchoff themainselectrical supplyand
remove fuses.
7. Connect thecablefromthe isolating switchto
theelectrical supply wiring.
8. For fixedwiringcircuits theprotectivefusefor
theappliance mustnot exceed 5A.
Before makinganyadjustments, isolate thefan
completely fromthemainssupply,check
specificationbelow to see which features apply to
your fan.
1. Remove thefront coverand replaceafter
adjustment(Fig.C).
There areno useradjustments for theLVDX200 fan.
1. Thetimerover-run periodcan beadjusted
between approximately 30seconds and 20
minutes.Usean electrician’s screwdriverand
turnscrew “T” (Fig. D), clockwise toincrease
time,anti-clockwisetodecrease.(Factory
preset toapproximately10 minutes).
1. Thehumidity setting is adjustablebetween
approximately50%and 90%relative
humidity. Usean electrician’sscrewdriver, and
turnscrew “RH” (Fig. D),clockwiseto
increase therelativehumidity setting and anti-
clockwise to decrease. (Note: the fan is more
sensitive at50% RHthan at90%).
1. Thetimerover-run periodcan beadjusted
between approximately 30 seconds and 20
minutes.Usean electrician’s screwdriverand
turnscrew “T” (Fig. D), clockwise toincrease
time,anti-clockwisetodecrease.(Factory
preset toapproximately10 minutes).
2. Thehumidity setting is adjustablebetween
approximately50%and 90%relative
humidity. Usean electrician’sscrewdriver, and
turnscrew “RH” (Fig. D),clockwiseto
increase therelativehumidity setting and anti-
clockwise to decrease. (Note: the fan is more
sensitive at50% RHthan at90%).
Operatethefan using theexternal On/Off switch.
Repeatto switchoff. Thefan speed is pre-setbythe
Installertoeither high or lowspeed.
Both speeds can beselectedwhenwiredthrough a
changeover switch Part No. 90108AW.
Operatethefan using theexternalon/off switch.
Repeattoswitch off.
Whenthe switchis turnedoff,the fan continuesto
operateforthe selected over-run timerperiod. Top
light“I”islitwhentheexternal on/off switchis
turned on.
Thefan speedis pre-setby theinstallerto either
high orlowspeed. (If a change overswitch has been
installed thentheuser can switch between high
speed and low speed.)
Time delay start featureonoroff
This is setbytheinstaller to providea2-minute time
delaystart when thefan is switched onusing the
external on/offswitch.
Switched Operation
Thefan can bewired with aseparateon/off switch.
Fan operatesatcondensation speedwhenswitched
on. Top light“I”is lit when theseparateon/off
switch is switched on. Whenswitched off, thefan
will continueto operateif thehumidity level has not
reachedthatsetbyadjusting screw “RH”.
LVCF20Tonly: Whenswitched off, the fan
continuesto operatefor the adjustable timerover-
run period.
CondensationOperation
Thefan operatesatcondensation control speed,
when the relativehumidityexceeds thesetlevel, and
turns off when thehumidity drops.
BoostOperation
Theintegral pull cord switch switches thefan to run
athigh speed. Bottomlight “II” is lit when the fan is
operating athigh speed. Note: Iftheseparateon/off
switchand integral pull cordarebothon, thelights
“I”and “II”willboth belit and thefan will run at
high speed.
Trickle feature on or off
This isset bythe installerto provide continuous
background extraction, when thehumiditylevel is
belowthat set byadjusting screw “RH”.
Time delay stat feature on or off
This is set bytheinstallertoprovidea 2-minute time
delaystart whenthefan isswitchedon using a
separateon/offswitch.
1. Before cleaning, isolatethefancompletely
fromthe mains supply.
2. Only clean theexternal surface ofthefan,
using a damp lint free cloth.
3. Do notusestrong detergents, solvents or
chemical cleaners.
4. Allowthefan to drythoroughly beforeuse.
5. Apart fromcleaning, no othermaintenanceis
required.
SeeDiagram E
1. BafflePlate
2. Front Cover
3. Impeller
4. Fixing Screws
5. Terminal Cover
6. Fan Box
7. CircularSpigot
8. Clamp screws and wall plugs– 3 off
9. Fan body clamps– 3 off
10. Surround
11. Ceiling screws 25mmlong - 4 off (Diagram B)
12. FoamTape
PLEASELEAVE THIS LEAFLETWITH THE
FAN FOR THEBENEFIT OFTHE USER
Forspeedand easeof installation, your installation
mayrequire some of theAncillaries listed below:
WD100 Wall Duct
CFWG100 Wall Grille
XCT100 Condensation Trap
DGW/B Air Replacement Grille
SP100 SpigotPlate
XAA Air BrickAdaptor
VC10 VentCowl
WT10 Termination Ducting Kit
XF/FM Flat Ducting (Plastic/Metal)
(Plastic234x29
Metal 230x25)
VK10 Wall VentKit
FD100 FlexibleDucting
WDC5 WormDriveClips
XCMK Ceiling Mounting Kit
XBP In-Line Back Draught Shutter
EFT EasyFit Termination Kit
GMK Glass Mounting Adaptor
PDXGF GreaseFilter
FDA Flat Duct Adaptor Kit
Spares
Listedbelow aresome of the sparesavailable.See
back pageof this bookletfor ordering details:
41756SK Motor(LVDX200T)
41757SK Motor(LVCF20/LVCF20T)
41758SK PCB Assy. (LVDX200T)
41759SK PCB Assy. (LVCF20)
41760SK PCB Assy. (LVCF20T)
41769SK FrontCover c/wBaffle
(LVDX200T)
41770SK FrontCover c/wBaffle
(LVCF20 / LVCF20T)
41740SK Surround Moulding
(EntireRange)
41741SK Pull-Cord Assembly
(EntireRange)
41742SK Impeller(EntireRange)
Fixing the transformer directly
Wirethe Fan
Wirethe Transformer
Useradjustments
LVDX200
LVDX200T
LVCF20
LVCF20T
Using theFan
LVDX200
LVDX200T
LVCF20 / LVCF20T
LVCF20T only
Cleaning
Key
AncillaryOptions
3
A
B
4
C
D H
5

This manual suits for next models

3

Other Xpelair Fan manuals

Xpelair DX100B User manual

Xpelair

Xpelair DX100B User manual

Xpelair SLDC150 User manual

Xpelair

Xpelair SLDC150 User manual

Xpelair GX12 User manual

Xpelair

Xpelair GX12 User manual

Xpelair GX6 EC2 User manual

Xpelair

Xpelair GX6 EC2 User manual

Xpelair LVCF20TX User manual

Xpelair

Xpelair LVCF20TX User manual

Xpelair LV100HP and User manual

Xpelair

Xpelair LV100HP and User manual

Xpelair Premier CF40RSTD User manual

Xpelair

Xpelair Premier CF40RSTD User manual

Xpelair Simply Silent C4S User manual

Xpelair

Xpelair Simply Silent C4S User manual

Xpelair GX12 User manual

Xpelair

Xpelair GX12 User manual

Xpelair Natural Air 180 Vertical User manual

Xpelair

Xpelair Natural Air 180 Vertical User manual

Xpelair GX12 User manual

Xpelair

Xpelair GX12 User manual

Xpelair VX100 User manual

Xpelair

Xpelair VX100 User manual

Xpelair Simply Silent LVCV4SR User manual

Xpelair

Xpelair Simply Silent LVCV4SR User manual

Xpelair 100MM/4" RANGE DX100 User manual

Xpelair

Xpelair 100MM/4" RANGE DX100 User manual

Xpelair Premier CF20 and User manual

Xpelair

Xpelair Premier CF20 and User manual

Xpelair Simply Silent LVCV User manual

Xpelair

Xpelair Simply Silent LVCV User manual

Xpelair WX12 User manual

Xpelair

Xpelair WX12 User manual

Xpelair DX100R User manual

Xpelair

Xpelair DX100R User manual

Xpelair GX9 EC3 User manual

Xpelair

Xpelair GX9 EC3 User manual

Xpelair GX6EC User manual

Xpelair

Xpelair GX6EC User manual

Xpelair Natural Air PH 180 User manual

Xpelair

Xpelair Natural Air PH 180 User manual

Xpelair Simply Silent SSWIN User manual

Xpelair

Xpelair Simply Silent SSWIN User manual

Xpelair LV100PC and User manual

Xpelair

Xpelair LV100PC and User manual

Xpelair Premier CF20T and User manual

Xpelair

Xpelair Premier CF20T and User manual

Popular Fan manuals by other brands

Sulion CARPE manual

Sulion

Sulion CARPE manual

Ebmpapst W2S130-AB03-21 operating instructions

Ebmpapst

Ebmpapst W2S130-AB03-21 operating instructions

Dimplex DCTFE77 instruction manual

Dimplex

Dimplex DCTFE77 instruction manual

LSL Products Super Stanker installation instructions

LSL Products

LSL Products Super Stanker installation instructions

Holmes HASF1650 owner's guide

Holmes

Holmes HASF1650 owner's guide

Frico PTA 01 manual

Frico

Frico PTA 01 manual

Litex Industries E-FR52ABZ5CR installation guide

Litex Industries

Litex Industries E-FR52ABZ5CR installation guide

Lifetime Air ATF-003R instruction manual

Lifetime Air

Lifetime Air ATF-003R instruction manual

YASKAWA CIPR-FP6 Series manual

YASKAWA

YASKAWA CIPR-FP6 Series manual

Craftmade Sterling STL60 installation guide

Craftmade

Craftmade Sterling STL60 installation guide

ATD Tools ATD-30342A owner's manual

ATD Tools

ATD Tools ATD-30342A owner's manual

Oster 1693 instruction manual

Oster

Oster 1693 instruction manual

Daikin VAM-J8 Series manual

Daikin

Daikin VAM-J8 Series manual

King Canada 8500AM instruction manual

King Canada

King Canada 8500AM instruction manual

Hunter 28672 Parts guide

Hunter

Hunter 28672 Parts guide

Relaxxnow VTX200 user manual

Relaxxnow

Relaxxnow VTX200 user manual

S&P OZEO FLAT H ECOWATT manual

S&P

S&P OZEO FLAT H ECOWATT manual

Airflow QuietAir QT 150B Installation and operating instructions

Airflow

Airflow QuietAir QT 150B Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.