
14
COOLING WATER PIPING
Heat from the absorption chiller is rejected to
a well, river or cooling tower and cooling water is
maintained at 85OF or less during the cooling
season. Provide drain valves at all low points in
the piping so that the circuit can be drained
during the winter and for maintenance.
All 20 and 30 ton absorption chillers (Models
WFC-SC20, WFC-SH20, WFC-SC30 and WFC-
SH30) require cooling water crossover piping to
connect the condenser and absorber in parallel.
Install crossover piping, in accordance with Fig.
9, to ensure balanced cooling water flow through
the condenser and absorber. If the crossover
design is changed, install balancing valves at the
condenser outlet and absorber outlet connections
so that the flow rate through each circuit can be
adjusted in accordance with the chiller
specifications. As an alternative, install the
optional Yazaki cooling water crossover pipe
assemblies.
A balancing valve should be installed
adjacent to the cooling water outlet on each
absorption chiller to facilitate flow rate
adjustments within specified limits. Install a stop
valve adjacent to the cooling water inlet as shown
in Fig. 9. This valve must be in the full open
position when the equipment is operating. DO NOT
CLOSE the stop valve except for disconnection or
relocation of the absorption chiller unit.
If the cooling water inlet temperature is below
65OF and likely to remain at this condition after
the first 30 minutes of cooling operation, a
cooling water temperature control system, as
shown in Fig. 10 must be installed. The
motorized 3-way valve (CWV) will bypass cooling
water to the sump whenever the cooling water
inlet temperature is below 65OF.
Wherever possible, install the cooling tower
at the same level or above the absorption chiller.
If this cannot be accomplished, give careful
consideration to the piping design to avoid
overflowing the cooling tower sump every time
the cooling water pump stops.
If cooling water remains in the condenser and
absorber section of the chiller-heater during
heating operation, and the unit is immediately
switched to cooling mode, a slug of hot water
NOTES:
1. Each standard crossover pipe has similar
pressure losses for balanced cooling water
flow through the absorber and condenser.
2. Install flow balancing valves in each circuit for
non-standard crossover pipe designs.
3. Install cooling water flow valves 5 pipe
diameters (min.) upstream and downstream
of the respective “T” fitting.
4. The crossover pipe configuration must
provide clear access to the rear of the
absorption chiller for maintenance.
Fig. 9 COOLING WATER CROSSOVER PIPING
Fig. 10 COOLING WATER PIPING
CAUTION
1. DO NOT EXCEED 100 - 120% OF
STANDARD COOLING WATER FLOW.
2. DO NOT EXCEED 85.3 PSI IN THE
COOLING WATER CIRCUIT AT THE
ABSORPTION CHILLER.
Balancing
Valve
Stop Valve
3" Cu Tube
3" Cu Tube
Cooling Water
Condenser Outlet
Cooling Water
Absorber Outlet
Cooling Water
Condenser Inlet
Cooling Water
Absorber Inlet
2" Cu Tube (WFC-SC20/SH20)
2 1/2" Cu Tube (WFC-SC30/SH30)
Note 3
Note 3
Union (CxM)
Cooling Water
Outlet
Cooling Water
Inlet
Chiller/Chiller - Heater
Condenser Water
Inlet
Absorber Water
Outlet
Cooling Tower
T
Drain
Cooling Water Pump
Flush
Valve
Flush
Valve
T
Temp. Control (CWTS)
Cooling Water Control
Valve (CWV)
Drain
Water Supply
Crossover Piping
For WFC-SC20/SH20 &
WFC-SC30/SH30 ONLY
PP