
20
The rocker switch on the front of the
Control Panel must be set to “REMOTE” in
order for the unit to be controlled by the BMS
in this manner.
It is recommended that field-supplied
SPDT relays be used to prevent conflicting
signals. The wiring diagram designates the
relay controlling Cool/Heat as ESC and the
relay controlling Enable/Disable as ESON. If
a WFC-SC model chiller is being wired to a
BMS, then there is no heat mode available,
therefore, the ESC relay is not needed.
Be aware that if the unit receives the
voltage from terminal E back on both
terminals A and B at the same time or on
terminals C and D at the same time, the unit
will be receiving conflicting commands. The
unit the unit will attempt to satisfy the
commands by switching back and forth
between the two conflicting commands until
the conflict is resolved.
REMOTE MONITORING
There are two optional methods of remote
monitoring. The first is by use of the LON
Adapter and the second is by use of the
Arotrend Remote Monitoring package. It is
possible to use both options at the same
time on the same unit.
The optional LON Adapter accessory will
allow the direct interface of the supported
output data from the Yazaki controls to any
LON-compatible control system. It mainly
provides output data. The only input allowed
is the Enable/Disable signal.
Figure 21 –Arotrend and LON Adapter
Connections in the Junction Box
The LON Adapter installation and wiring
instructions are included with the accessory
package. The LON Adapter is a field-
installed option, though it could be factory-
installed on the WFC-SC50 if ordered as
such.
The available output data from the LON
Adapter is as follows: Alarm condition (with
2-digit error code number), Enable/Disable
mode feedback (is the unit Enabled or
Disabled), Mode feedback (is the unit in Heat or
Cool mode), Operation feedback (is the unit
operating or in standby mode), the entering and
leaving cooling water temperature (CTI and
CTO thermister reading), and leaving
chilled/hot water temperature (WTO thermister
reading). At the time of this writing, no other
data is available through the LON Adapter.
If the LON Adapter is not suitable for use
with the BMS in place, a number of feedback
dry contacts are available in the Junction
Box that can be used to provide information
to the BMS. Consult the Controls Wiring
Diagram in the wiring section for further
details.
A second method of remote monitoring is
the use of the Arotrend Remote Monitoring
package. The Arotrend can connect the unit
to a Yazaki-monitored server or to a
computer that has the proper software
installed. Contact Yazaki Energy Systems,
Inc., for more information on the software
and monitoring services offered as these
options can change or be discontinued
without notification at any time.
The Arotrend Remote Monitoring package
wires to terminals 1 and 2 in the Junction
Box (see Figure 21). The Arotrend package
can report much more data than the LON
Adapter can provide, including temperatures.
It is permitted to use both the LON Adapter
and the Arotrend at the same time.
Finally, Arotrend remote monitoring can
do nothing except monitor. There is no
ability for any input commands through the
Arotrend.
It is not possible in any way to remotely
adjust the leaving water temperature set
points.