FILTER PERFORMANCE
The airflow capacity data published in the “Blower Perfor-
mance” table represents blower performance WITHOUT fil-
ters.
All applications of these furnaces require the use of field
installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabi-
net. DO NOT attempt to install any filters inside the furnace.
NOTE: Single side return above 1800 CFM is approved as
long as the filter velocity does not exceed filter manufac-
turer’s recommendation and a transition is used to allow use
of a 20 x 25 filter.
NOTES:
1. Air velocity through throwaway type filters may not exceed 300 feet per
minute (91.4 m/min). All velocities over this require the use of high veloc-
ity filters.
2. Do not exceed 1800 CFM using a single side return and a 16x25 filter.
For CFM greater than 1800, you may use two side returns or one side
and the bottom or one return with a transition to allow use of a 20x25
filter.
All furnaces approved for alcove and attic installation.
ACCESSORIES
PROPANE (LP) CONVERSION KIT -
1NP0680 - All Models
This accessory conversion kit may be used to convert natural
gas (N) units for propane (LP) operation.
CONCENTRIC VENT TERMINATION -
S1-1CT0302 (2")
S1-1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Elimi-
nates unslightly elbows for a cleaner installation.
SIDEWALL VENT TERMINATION KIT -
S1-1HT0901 (3")
S1-1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for instal-
lation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).
SIDE RETURN FILTER RACKS -
1SR0200 - All Models
1SR0402 - All Models
1SF0101 - All Models
BOTTOM RETURN FILTER RACKS -
1BR0517 or 1BR0617 - For 17-1/2” cabinets
1BR0521 or 1BR0621 - For 21” cabinets
1BR0524 or 1BR0624 - For 24-1/2” cabinets
1BR05xx series are galvanized steel filter racks. 1BR06xx
are pre-painted steel filter racks to match the appearance of
the furnace cabinet.
COMBUSTIBLE FLOOR BASE KIT -
For installation of these furnaces in downflow applications
directly onto combustible flooring material, These kits are
required to prevent potential overheating situations. These
kits are also required in any applications where the furnace in
installed in a downflow configuration without an evaporator
coil, where the combustible floor base kit provides access for
combustible airflow.
1CB0517 - For 17-1/2” cabinets
1CB0521 - For 21” cabinets
1CB0524 - For 24-1/2” cabinets
EAC TRANSITION KITS -
For installation of EAC accessories with these furnaces to
provide easy transition of return airflow through the EAC to
get the proper sealing and reduced airflow leakage.
1TK1001 - For all models using side return
1TK1017 - For 17-1/2” cabinets using bottom return
1TK1021 - For 21” cabinets using bottom return
1TK1024 - For 24-1/2” cabinets using bottom return
HIGH ALTITUDE - No high altitude kits are required.
ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.
1H/1C, manual change-over electronic non-programmable
thermostat.
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.
Recommended Filter Sizes
CFM Cabinet
Size Side
(in) Bottom
(in)
1200 B 16 x 25 16 x 25
1600 C 16 x 25 20 x 25
2000 D (2) 16 x 25 22 x 25
Unit Clearances to Combustibles
Application Upflow Downflow Horizontal
Top 1" 0" 0"
Vent 0" 0" 0"
Rear 0" 0" 0"
Side 0" 0" 1"
Front1
1.Line contact only permitted between lines formed by the intersection of
the rear panel and side panel (top in horizontal position) of the furnace
jacket and building joists, studs or framing.
0" 0" 0"
Floor Combustible Combustible2
2. For combustible floors only when used with special sub-base.
Combustible
Closet Yes Yes Yes
Line Contact No No Yes