FORM 150.68-EG1 (0212)
3JOHNSON CONTROLS
Product Description
YLPA air-to-liquid reversible heat pumps are completely
factory assembled with all interconnecting refrigerant
piping and wiring ready for field installation. The unit is
pressure tested, evacuated, and fully factory charged
with refrigerant R410Aand oil in each of the independent
refrigerant circuits. After assembly, an operational test is
performedwithwaterflowingthroughtheheatexchanger
to ensure that each refrigerant circuit operates correctly.
The unit structure is manufactured from heavy-gauge,
galvanised steel coated with baked-on powder paint
(Champagne (RAL 7006, Munsell No. 9.8YR4.36/1.2)).
YLPAheatpumpsaredesignedinaccordancewithNFPA
70 (National Electric Code), ASHRAE/ANSI 15 Safety
code for mechanical refrigeration, ASME and rated in
accordance with ARI Standard 550/590.
COMPRESSORS
Theunithassuction-cooled, hermetic scrollcompressors.
High efficiency is achieved through a controlled orbit and
the use of advanced scroll geometry. The compressors
incorporate a compliant scroll design in both the axial
and radial directions. All rotating parts are statically and
dynamically balanced. The compressor motors have
integralprotectionagainst overloadsthatwill automatically
reset. Starting is direct on line, and soft start is available
as an option.
The compressors are switched On and Off by the
unit microprocessor to provide capacity control. Each
compressor is fitted with a crankcase strap heater. All
compressors are mounted on isolator pads to reduce
transmission of vibration to the rest of the unit.
The motor terminal boxes have IP54 weather protection.
REFRIGERANT CIRCUITS
Twoindependentrefrigerantcircuitsare provided oneach
unit. Each circuit uses copper refrigerant pipe formed
on computer controlled bending machines to reduce the
number of brazed joints resulting in a high integrity and
reliable system.
Eachcircuit shallincorporateallcomponentsnecessary for
the designed operation including: a suction accumulator;
a liquid receiver; a four way reversing valve which
changes the direction of the refrigerant flow and the
function of the heat exchanger when switching between
coolingandheatingmodes; service valves; isolation(ball/
angle) valves; pressure relief valves; a high absorption
removable core filter-drier; a sight glass with moisture
indicator; a cooling mode thermal expansion valve and a
heat pump mode thermal expansion valve. Suction lines
shall be covered with closed-cell insulation.
REFRIGERANT TO WATER HEAT EXCHANGER
The2-passdualcircuitshellandtubetypedirectexpansion
(DX)heatexchanger hasrefrigerantin thetubesandliquid
flowing through the baffled shell. The waterside (shell)
design working pressure is 10 barg. The refrigerant side
(tubes)designworkingpressureis45 barg.Therefrigerant
side is protected by pressure relief valve(s).
The heat exchanger is equipped with a heater for frost
protectionto-4°F(belowthistheballvalveinthedischarge
line must be closed) and insulated with flexible closed-
cell foam. Water connection to the heat exchanger is via
victaulic grooved connections. Victaulic groove to flange
converters are available as an option
AMBIENT COILS
The ambient coils are seamless copper tubes, arranged
in staggered rows, mechanically expanded into coated
aluminium fins. Integral sub-cooling is included.
Thecondenserfanshave composite metal/plastic `sickle`
blades integrated into the rotor of an external rotor motor.
They are designed for maximum efficiency and statically
and dynamically balanced for vibration free operation.
They are directly driven by independent motors, and
positioned for vertical air discharge. The fan guards
are constructed from heavy-gauge, corrosion resistant,
coated steel.
TheIP54fanmotorsarethe totally enclosed air-over type
with permanently lubricated double-sealed ball bearings.
POWER AND CONTROL PANELS
All power and controls are contained in an IP 55 cabinet
with hinged and gasket sealed outer doors. The power
panel includes:
• Factory mounted non-fused disconnect switch
with external red/yellow, lockable handle to enable
connection of the unit power supply. The disconnect
switch can be used to isolate the power for servicing
and as a emergency stop.
• Factory mounted compressor contactors and
compressor fuses provide short circuit protection.
Overload protection for each compressor is provided
by inherent motor winding temperature sensing and
a trip module.
• Factory mounted fan contactors and fuses provide
short circuit protection. Overload protection for
each fan is provided by a inherent motor winding
temperature device.
• Factorymountedcontroltransformertoconverttheunit
supply voltage to 115 V - 1 Ø - 60 Hz for the control
system.
• Control supply fuses and connections for a remote
emergency stop device.