GENERAL OVERVIEW
OPERATION
Example 1.
START
OVERCURRENT
occurs
Low-set I>
triggered
Time out
commences
High-set
I>>
triggered?
N
Y
TRIP!
Timeout
complete?
N
Y
P9650
PRESENTATION
1. Time Multiplier adjustment*
2. Low-Set I> trip adjustment*
3. High-Set I>” trip adjustment*
4. Power Supply green LED indication
5. Low-Set triggered red LED indication
6. High-Set triggered red LED indication
7. RESET button
8. TEST button
* accessible only when the front cover is open
7
8
5
6
4
1 2 3
¬True R.M.S. measurements
¬Adjustable Low-set and High-set tripping threshold ( with option to
disable High-set tripping)
¬Adjustable Time Multiplier for defining curve tripping characteristic
(applicable to Low-set only)
¬Normal Inverse 3/10 tripping characteristics (Low-se t threshold only)
¬Instantaneous tripping on High-set triggering
¬Test and Reset button for simulating and clearing of fault condition
¬Red LED indication of Low-set or High-set triggering and tripping
¬Green LED indication for Auxiliary power supply presence
¬Microprocessor based (self checking) with non- volotile memory
2
¬Terminals suitable for 2 x 2.5mm wires (complete with protective cover)
Inverse Denite Minimum Time
(IDMT) Overcurrent Relay
The P9650 (from the P9600 series family of IDMT/DT relays) is a microprocessor
based relay designed to monitor and detect over currents in 3-phase
applications. Typically the P9650 is wired in conjunction with external current
transformers (1 per phase) of the feeder to be protected.
Adjustments & indicators are laid out in a way to help the user during set-up and
fault finding. eg. The adjustment for the LOW SET has its corresponding red
LED positioned above it so it is clear which function this LED relates to.
The same applies to the HIGH SET adjustment & LED.
Adjustment and LED operation is explained further on the next page.
The adjustment for TM (k), which defines the curve response to tripping, is
assigned to the LOW SET triggering only. The HIGH SET does not have any
additional adjustments nor does the HIGH TRIP INSTANTANEOUS if triggered.
The HIGH SET can be set to disabled, if required.
A T EST mode is provided to confirm the correct operation of the internal relays.
The relay will energize when the TEST button is pressed and de-energise when
the RESET button is pressed.
When an over current occurs in one of the phases and the level of the current
exceeds the LOW-SET I> trip threshold, the corresponding red LED above
the adjustment illuminates. The time out then commences, no matter the
point at which tripping occurred either by:
A) the level of current that is above the trip threshold.
B) the Time Multiplier Setting.
When tripping finally occurs, the red LED will then flash indicating a
tripped condition. If the fault current has been removed, pressing the RESET
button will return the relay back to normal operation & the red LED will
then extinguish.
Example 2.
If a fault current occurs such that it exceeds the HIGH-SET I>> trip
threshold, the relay will de-energise with no delay & the red LED above the
HIGH-SET I>> adjustment will flash indicating a TRIPPED condition.
If the fault current has been removed, pressing the RESET button will
return the relay back to normal operation. The red LED will then extinguish.
In the event of an over current condition, the basic sequence of events is
shown below assuming HIGH-SET trip is enabled.
www.z-trauq.com 877-798-7287 [email protected]
Dimensions:
W x H. 96 x 96mm (front)
W x H. 89.5 x 89.5mm (rear)
D. 107mm
www.z-trauq.com 877-798-7287 [email protected]
INSTALLATION
Installation work must be carried
out by qualified personnel.
BEFORE INSTALLATION, ISOLATE THE SUPPLY. THIS
PRODUCT IS D ESIGNED TO CONNECT TO SEVERAL TYPES
OF CIRCUITS. ENSURE ALL ARE ISOLATED.
Lift the raised part of the side clip in order to remove from the housing.
Insert the P9650 into the panel cut-out and fit side clips back onto the housing.
Slide the clips towards the front of the unit until they come in to contact with
the reverse side of the door. The unit is now secured in place.
Connect wires to the rear terminals as required.
The P9650 is now ready for powering and setting
The front window of the P9650 is supplied with a clear protective film which
can be removed as and when necessary.
NORMAL OPERATION
Apply power to the unit and the green power supply LED will illuminate.
TEST MODE
Press and hold the button and the relay will energize. Both the red I> & I>>
LED’s will illuminate.
Release the button and the relay will remain energized.
Press the button to de-energise the relay. Both red LED’s will extinguish.
Testing should be carried out on a regular basis to check the integrity of the
P9650. DO NOT use this product to provide a means of isolating circuits in
order to work on when placed in the TEST mode. This should only be done by
means of operating isolators, circuit breakers or other methods of removing
power in this application.
= LED on = LED flashing
= LED off
LED FUNCTION SUMMARY
The green LED will remain illuminated for as long as power is applied
to the Aux. connections ( terminals 1 and 2).
In response to an over current condition:
In response to Test and Reset button operation:
Status I> I>>
Normal
Low-set triggered
Low-set Tripped
High-set triggered
High-set Tripped
Button press I> I>>
Setting of the P9650 is carried out using the 3 potentiometers located behind
the transparent cover.
1. TIME MULTIPLIER (TM (k)) defines the tripping
characteristic when the LOW-SET threshold “I>” has
been exceeded. The lower the setting, the faster the
response to tripping. The higher the setting, the slower
the response.
2. LOW-SET TRIP threshold (I>) can be set from 2 to 6A.
When the threshold is exceeded due to an over current
condition, the corresponding red LED above the
adjustment illuminates indicating activity. When tripping
finally occurs, the red LED will then flash.
3. High-Set Trip threshold (I>>) adjustment can be set
from x1 to x10 or disable =
The scale markings are multipliers of what has been set on
the LOW-SET threshold. For example if the LOW-
SET is set to 4A and HIGH-SET to 8, this will be the
equivalent of 4 x 8 or 32A. When the threshold is
exceeded due to an over current condition, the corresponding red LED
above the adjustment illuminates indicating activity. When tripping finally
occurs, the red LED will then flash. If tripping occurs whereby the HIGH-
SET level is exceeded, only the LED for the HIGH-SET will flash. This
allows the user to clearly identify which threshold was triggered causing the
trip. There is no delay associated with HIGH-SET therefore, tripping is
instantaneous.
SETTING & OPERATION
Max. DC Load Breaking Capacity Electrical Endurance
CONNECTION DIAGRAM
L1
L2
L3
N
DIMENSIONS
96
96
10
89.5
96
12
80
Front view Side view
All dimensions are in mm.
t
t (s)
(s)
10
1
0.1
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
1 10 20
I/I>
www.z-trauq.com 877-798-7287 [email protected]
A1 A2
Aux.supply
1 2 3 4 5 6 78
Rly 1
L1 L3
L2
X1
X1 X1
X2
X2
X2
910 11 12 13 14 15 16
95
TECHNICAL SPECIFICATIONS
Supply voltage Un (1, 2): ±15%
230VAC ±15%
(V o lta g e s h ou ld be specified at time of ordering)
Rated frequency: 50/60Hz
Isolation: Over voltage cat. III
Rated impulse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
Power consumption: 3W max.
Rated current input In: 5A (directly connected)
Rated frequency: 50Hz
Burden: <0.4VA @ In
Overload: 4 x In (continuous)
External CT terminals
9, 10, 11, 12, 13, 14 Class C recommended with 5A secondary
Overcurrent settings:
Low-set trip (I>): 2.0 – 6.0A (40 – 120%)
Time multiplier (TM): 0.05 – 1.0
High-set trip (I>>): x1 – x10 or disable
High-set definite time: Instantaneous (<50mS)
Pick up value: +2% of trip setting
Accuracy:
Protection thresholds: ± 5%
Response time: ± 5% (with a minimum of 50mS)
Repeat accuracy: ± 0.5% @ constant conditions
Ambient temperature: -10 to +60°C
Relative humidity: +95% (non-condensing)
Output:
RL1 (3, 4, 5): 1 x SPDT relay
Output rating: AC1 250V 8A (2000VA)
AC15 250V 5A (1250VA)
DC1 25V 8A (200W)
Electrical life:
≥ 150,000 ops at rated load
Dielectric voltage: 2kV AC (rms) IEC 60947-1
Rated impulse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
115VAC
Options:
The P9600 range also includes individual Overcurre nt or Earth fault relays
available with either IDT or IDMT tripping characte ristics.
Please refer to separate data sheets.
Tripping Curve Characteristics (Normal Inverse 3/10).
Housing:
Flame retardant Lexan
Protection: IP55 / IP20 (rear)
Weight: ≈ 590g
Mounting: Panel mounting. Cutout = 91 x 91mm (± 0.5mm)
Max. panel thickness:
Terminal conductor size: 0.05 - 2.5mm 2 (30 - 12AWG)
Recommended tightening
torque: 10in lb (1Nm)
Wire stripping length: 0.24 – 0.30in (6 – 7.5mm )
Approvals: Conforms to IEC. CE and
and RoHS Compliant.
EMC: Immunity: EN/IEC 61000-6-2
Emissions: EN/IEC 61000-6-4
Generic: IEC 60255-26 (EMC), IEC 255-3, IEC
60255-151
12mm

Popular Relay manuals by other brands

GE IJCS2A instructions

GE

GE IJCS2A instructions

GE 745 TRANSFORMER MANAGEMENT RELAY instruction manual

GE

GE 745 TRANSFORMER MANAGEMENT RELAY instruction manual

GE IAV51A instructions

GE

GE IAV51A instructions

GRI PRM-1 manual

GRI

GRI PRM-1 manual

LOVATO ELECTRIC PMF20 quick start guide

LOVATO ELECTRIC

LOVATO ELECTRIC PMF20 quick start guide

GEYA GRV8-SN instruction manual

GEYA

GEYA GRV8-SN instruction manual

hitin RTT8 quick start guide

hitin

hitin RTT8 quick start guide

Honeywell TRADELINE R8184G quick start guide

Honeywell

Honeywell TRADELINE R8184G quick start guide

GE DFF1000 Series instructions

GE

GE DFF1000 Series instructions

BECKWITH ELECTRIC M-0245C Instruction book

BECKWITH ELECTRIC

BECKWITH ELECTRIC M-0245C Instruction book

Doepke SIWR Installation and operating manual

Doepke

Doepke SIWR Installation and operating manual

BENDIX R-8P installation instructions

BENDIX

BENDIX R-8P installation instructions

Mitsubishi Electric MELSEC-WS user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC-WS user manual

Neets Switching Relay - 8 Installation guides

Neets

Neets Switching Relay - 8 Installation guides

Plejd LED-10 installation manual

Plejd

Plejd LED-10 installation manual

ABB Relion 615 series Engineering manual

ABB

ABB Relion 615 series Engineering manual

Emerson Liebert IntelliSlot IS-RELAY user manual

Emerson

Emerson Liebert IntelliSlot IS-RELAY user manual

Basler BE1-25 instruction manual

Basler

Basler BE1-25 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.