ZETTLER PROFILE FBI800 User manual

PROFILE Fire detection system FBI800
Fixing instructions Doc. version 1.0 1/8
FBI800 Fire Brigade Interface Card
Part No. 557.202.845
Introduction
The FBI800 is suitable for use with the Profile
Pro range of panels.The FBI800 performs the fol-
lowing functions:
Connects the serial Fire Brigade Panel (FBF/
FAT) according to DIN 14661 / DIN 14662
standards via redundant serial interfaces and
redundant monitored 24V power supply
paths.
Connects the parallel Fire Brigade Panel (FBF)
according to DIN 14661 standard.
FBI800
REDB1 A
REDB1 B
REDB2 A
REDB2 B
PWR1+
PWR1-
PWR2+
PWR2-
HEAT+
HEAT-
DO PWR+
DO PWR-
DO CNT+
DO CNT-
SB LP+
SB LP-
SB LED+
SB LED-
CNOFLED
TUOFLED
FIALLED
ASOFLED
TUACLED
EXACLED
PWR+
PWR-
RL1 C
RL1 0/C
FIALRST
AS OFF
REV ON
TU OFF
FIC
TU +a
TU -b
TU PWR+
Status
Card Fault
Reset
A d d r e s s
10
1
2
3
4
5
6
7
Fig. 1: FBI800 Fire Brigade Interface card
1– Serial FBF / FAT connector
2– Fire Brigade Key Depot connector
3– Parallel FBF + RL1 connector
4– Parallel FBF + Transmit Unit connector
5– Optical indicators
6– Reset button
7– Slot card address DIP switch
2
3
4
5
Fig. 2: FBI800 terminals, LEDs and jumpers
1– Indicators RX, TX for Bus1 (left channel)
2– Indicators RX, TX for Bus2 (right channel)
3– J2 RL1contact configuration jumper
4– SW3
5– XP2 Debug port (RS232)
6– F200 (FU1) non-replaceable fuse
6
1

2/8 Fixing instructions Doc. version 1.0
FBI800 PROFILE Fire detection system
Connects the Fire Brigade Key Depot (FBKD)
according to DIN 14675 standard.
Connects the Transmit Unit (TU) which trans-
mits the fire alarm to the fire brigade control
centre.
Features
The FBI800 slot card is used as the interface
between the panel and standard fire brigade
interfaces. It operates with its own system
address and communicates with MCPU on
PFI800 over the internal N-Bus.
One FBI800 card can be used in the panel. This
supports a single serial FBF / FAT. In a system
with several panels, each panel can have an
FBI800 with its own FBKD, TU and FBF/FAT
equipment.
Cabling requirements
Use shielded cables to connect the FBF / FAT,
FBKD and TU peripherals to FBI800 card. Select
all cables in accordance with local standards.
Connect the cable shields to the panel earth
stud. At the peripherals, connect the shields to
the earth stud or follow the manufacturer's
instructions.
Maximum cable resistance
Installation
To install the FBI800 module, complete the fol-
lowing steps:
1 Set the optional jumper J2 to the desired set-
ting. See Table 2.
2 Set the optional SW3 DIP switches 5, 6 to
their default positions. Refer to Table 3.
CAUTION
Do not connect the FBKD and TU directly
to the serial FBF or serial FAT peripherals.
They are not accessible in the case of
system fault of the microprocessor on
FBI800 slot card.
FBI800 Maximum cable
resistance (per
conductor)
Serial FBF/FAT
RS485 lines
A1, B1, A2, B2
XT1 pins 1
to 4
20R
Serial FBF/FAT
power lines
Ub1, GND1,
Ub2, GND2
XT1 pins 5
to 8
15R
FBF-260 pins 1
& 2, 0V & +Ub
XT3 pins 7
& 8, PWR-
& PWR+
20R
FBF-260 pins 3
to 15
XT3 pins 1
to 6, XT4
pins 1 to 4
100R
FSD Heater XT2 pins 1
& 2, HEAT+
& HEAT-
6R
FSD door
opener
XT2 pins 3
& 4, DO
PWR+ &
DO PWR-
10R
FSD sabotage
loop, door con-
tact, sabotage
LED
XT2 pins 5
to 10
100R
TU RMS XT4 pin 5
FIC
100R
TU +a, TU-b (total resistance
from FBI800 to FBF-260 to
TU)
50R
Table 1: Maximum cable resistance
NOTICE
Switch the panel OFF during the
installation procedure

PROFILE Fire detection system FBI800
Fixing instructions Doc. version 1.0 3/8
3 Set the optional SW3 DIP switches 7, 8
according to project configuration. Refer to
Table 3.
4 The FBI800 slot card is pre-assembled. To
mount it, line it against the side rails of the
slot in the backplane cage. Slide the card
backwards until it clicks and ensure that it fits
firmly. For more information on slot cards,
see the PROFILE panel Product Application
and Design Information.
5 Connect the Fire Brigade peripherals. Refer to
Figures 3 to 6.
Firmware Update
If a firmware update is required, refer to the
steps in the relevant Technical Information Bulle-
tin (TIB).
Table 3 lists the DIP switch settings for a firm-
ware update. The operational default settings of
the DIP switches are marked by *.
Slot card addressing
One FBI800 card can be installed in the control
panel. The FBI800 has its own configured sys-
tem address. Refer to Table 4 for the decimal to
binary conversion
Jumper 1 – 2 2 – 3 OPEN
J2 RL1 Normally
closed con-
tact
Normally
open con-
tact *
---
Table 2: Jumper setting for installation.
SW3 Function ON OFF
1
2
3
4
DIP1
DIP2
DIP3
DIP4
Reserved*
Reserved
Reserved
Reserved
Reserved
Reserved*
Reserved*
Reserved*
5 Boot Mode Active Disabled *
6 Debug
Mode
Enabled Disabled *
7 EA Door EA signal
activates
the FBKD
door opener
output
EA signal
doesn’t acti-
vate the
FBKD door
opener *
Table 3: SW3 DIP Switch settings
8 FIC TU FIC signal
activates
the TUA-
CLED out-
put
FIC signal
doesn’t acti-
vate the
TUACLED
output *
J2 RL1 jumper defines the normal state
of relay RL1 contacts (relay is not
energized).
Address DIP Switch
1 2 3 4 5 6 7 8
001 1 0 0 0 0 0 0 0
002 0 1 0 0 0 0 0 0
003 1 1 0 0 0 0 0 0
004 0 0 1 0 0 0 0 0
005 1 0 1 0 0 0 0 0
006 0 1 1 0 0 0 0 0
007 1 1 1 0 0 0 0 0
008 0 0 0 1 0 0 0 0
009 1 0 0 1 0 0 0 0
010 0 1 0 1 0 0 0 0
011 1 1 0 1 0 0 0 0
012 0 0 1 1 0 0 0 0
013 1 0 1 1 0 0 0 0
014 0 1 1 1 0 0 0 0
015 1 1 1 1 0 0 0 0
016 0 0 0 0 1 0 0 0
017 1 0 0 0 1 0 0 0
018 0 1 0 0 1 0 0 0
Table 4: FBI800 Decimal to binary DIP switch address con-
version
Table 3: SW3 DIP Switch settings

4/8 Fixing instructions Doc. version 1.0
FBI800 PROFILE Fire detection system
Optical Indicators – front Optical Indicators – on the card
Status (Microprocessor)[Green]
ON permanently Microprocessor failed
Blink ON 0.5 / OFF 0.5: Normal function
Blink ON 0.1 / OFF 0.9 Firmware update mode
or checksum error
Blink ON 0.9 / OFF 0.1 Configuration mode or
configuration error
Blink ON 0.1 / OFF 0.1: Stand alone / Emergency
mode (contact lost with
PFI800)
OFF permanently 5V or 3.3V is missing or
error writing to flash
Fault (Card fault)[Yellow]
ON Fault
OFF No fault
Table 5: Optical indicators on the front panel
RX1 (Received data, Bus1 left)[Green]
ON: flickering Data is received on the Bus1 left
channel.
OFF: permanent Nothing is received on the Bus1
left channel
TX1 (Transmitted data, Bus left)[Green]
ON: flickering Data is transmitted on the
Bus1 left channel.
OFF: permanent Nothing is transmitted on the
Bus1 left channel
RX2 (Received data, Bus right)[Green]
ON: flickering Data is received on the Bus2
right channel.
OFF permanent: Nothing is received on the Bus2
right channel
TX2 (Transmitted data, Bus right)[Green]
ON: flickering Data is transmitted on the Bus2
right channel.
OFF: permanent Nothing is transmitted on the
Bus2 right channel
Table 6: Optical indicators on the Redundant Bus left and
right channels

Fig. 3 Wiring of Schraner serial FBF/FAT and transmit unit to
FBI800
Serial
FBF/
FAT
Transmit
Unit
Bus1
Power 1
Bus2
Power 2
TU signals
PROFILE Fire detection system FBI800
Fixing instructions Doc. version 1.0 5/8
Wiring
Serial FBF/FAT FBI800
ERDE -------
Ub1 XT1_5 PWR1+
GND XT1_6 PWR1-
Ub2 XT1_7 PWR2+
GND XT1_8 PWR2-
A2 XTI_3 REDB2 A
B2 XTI_4 REDB2 B
A1 XTI_1 REDB1 A
B1 XT1_2 REDB1 B
Table 7: Wiring of Schraner serial FBF/FAT to FBI800
Transmit Unit FBI800
0V XT4_7 TU-b
+24V XT4-8 TUPWR+
RMS XT4_5 FIC
-b XT4_7 TU -b
+a XT4_6 TU +a
Table 8: Wiring of Transmit Unit to FBI800

6/8 Fixing instructions Doc. version 1.0
FBI800 PROFILE Fire detection system
Fig. 4: Wiring of parallel Fire Brigade Panel FBF-260
by Schraner to FBI800
FBF-260 FBI800
1 XT3_8 PWR-
2 XT3_7 PWR+
3 XT3_6 EXACLED
4 XT3_4 ASOFLED
5 XT3_2 TUOFLED
6 XT4_4 TU OFF
7 ---
8 XT4_2 AS OFF
9 ---
10 XT3_5 TUACLED
11 XT3_1 CNOFLED
12 XT3_3 FIALLED
13 ---
14 XT4_1 FIALRST
15 XT4_3 REV ON
16 ---
BMZ-A XT4_6 TU +a
BMZ-B XT4_7 TU -b
UE-A to Transmit Unit +a
UE-B to Transmit Unit -b
Transmit Unit
RMS
XT4_5 FIC
Table 9: Wiring of FBF-260 to FBI800
CAUTION
Figure 4 is the parallel FBF installation
example only. The national standards and
local regulations should be considered in
the case of parallel Fire Brigade Panel
wiring.

PROFILE Fire detection system FBI800
Fixing instructions Doc. version 1.0 7/8
Fig. 5: Wiring of Fire Brigade Key Depot FSD-S3 by
Schraner to FBI800
Fig. 6: Wiring of Transmit Unit S24226-A12 by Siemens
to FBI800 and FBF-260
FSD-S3 FBI800
K1 XT2_7 SB LP+
K2 XT2_8 SB LP-
K3 ---
K4 ---
K5 XT2_3 DO PWR+
K6 XT2_4 DO PWR-
K7 XT2_5 DO CNT+
K8 XT2_6 DO CNT-
K9 XT2_1 HEAT+
K10 XT2_2 HEAT-
K11 XT2_9 SB LED+
K12 XT2_10 SB LED-
Table 10: Wiring of FSD-S3 to FBI800
S24226 FBI800/FBF-260
X1/1 UE-B -b (0V)
X1/2 XT4_8 TU PWR+
X1/3 -
X1/4 XT4_5 FIC
X1/5 UE-B -b (0V)
X1/6 UE-A +a
Table 11: Wiring of Transmit Unit S24226-A12 by Siemens
to FBI800 and FBF-260