3M MS2 4000 Series User manual

4000 Series Pedestal and Pole-
Mount Cabinets
(Quick Connect)
Instructions
September 2006
34-7018-1701-6-A


3
Contents:
Page
I. GENERAL..................................2
A.Introduction...............................2
B. MS2Cross-Connect Pedestal and
Pole-Mount Cabinets . . . . . . . . . . . . . . . . . . . . . . .2
C. Cross-Connect Pedestal Cabinets
ComponentAssembly .......................4
1. MS24065 (300-Pair) Pedestal Cabinet . . . . . . . . . .4
2. MS24080 (600-Pair) Pedestal Cabinet . . . . . . . . . .4
MS24082 (900-Pair) Pedestal Cabinet . . . . . . . . . .4
3. MS24084 (1800-Pair) Pedestal Cabinet . . . . . . . . .4
MS24086 (2700-Pair) Pedestal Cabinet . . . . . . . . .4
D. Cross-Connect Pole-Mount Cabinets
ComponentAssembly .......................5
1. MS24065 (300-Pair) Pole-Mount Cabinet
with 4098 Conversion Kit . . . . . . . . . . . . . . . . . . . .5
2. MS24094 (1200-Pair) Pole-Mount Cabinet . . . . . .5
MS24095 (1800-Pair) Pole-Mount Cabinet . . . . . .5
E. MS2Cross-Connect Module . . . . . . . . . . . . . . . . . .6
1. Description................................6
2. MS2Cross-Connect Module Chart . . . . . . . . . . . . .6
3. MS2Cross-Connect Module Detail . . . . . . . . . . . .6
II . PEDESTAL CABINET INSTALLATION
ANDPREPARATION ........................7
A.CablePreparation...........................7
1. Stub and Loop Cable Lengths . . . . . . . . . . . . . . . . .7
B. Ground Mount Installation. . . . . . . . . . . . . . . . . . . .7
1. MS24065 (300-Pair) Pedestal Cabinet Ground
MountInstallation ..........................7
2. MS24080 (600-Pair) and 4082 (1900-Pair)
PedestalCabinets...........................8
3. MS24084 (1800-Pair) and 4086 (2700-Pair)
PedestalCabinets...........................8
C. Slab Mount Installation for 4084 and 4086
Cabinets.................................10
1. Ground Preparation . . . . . . . . . . . . . . . . . . . . . . . .10
2. Slab Mounting the Cabinet . . . . . . . . . . . . . . . . . .11
D.SplitSlab ................................15
E. Cable Preparation. . . . . . . . . . . . . . . . . . . . . . . . . .15
F. Assembly of Module Frame Assembly . . . . . . . . . . .
III. PEDESTAL CABINET CABLE ROUTING . . . . .16
A. MS24065 (300-Pair) Cabinet . . . . . . . . . . . . . . . .16
B. MS24080 (600-Pair) Cabinet . . . . . . . . . . . . . . . .16
MS24082 (900-Pair) Cabinet . . . . . . . . . . . . . . . .16
MS24084 (1800-Pair) Cabinet . . . . . . . . . . . . . . .16
MS24086 (2700-Pair) Cabinet . . . . . . . . . . . . . . 16
C. Cable Terminated in Cabinet . . . . . . . . . . . . . . . .16
D. Cable Looped Through Cabinet . . . . . . . . . . . . . .16
IV. POLE-MOUNT CABINET INSTALLATION
AND PREPARATION . . . . . . . . . . . . . . . . . . . . . . .17
A. MS24065 (300-Pair) with 4098. . . . . . . . . . . . . . .17
1. Pole-Mount Conversion Kit . . . . . . . . . . . . . . . . .17
2. Cable Adapter-Top . . . . . . . . . . . . . . . . . . . . . . . .17
3. Bottom Plate and Cable Adapter Installation . . .17
B. MS24094 (1200-Pair) and 4095 (1800-Pair) . . . .18
1. Pole Mount Installation . . . . . . . . . . . . . . . . . . . . .18
2. Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . .18
C. Cable Preparation . . . . . . . . . . . . . . . . . . . . . . . .18
V. TERMINATING............................18
A. Location of Feeder and Distribution Modules . . .18
1. MS2Pedestal Cabinets . . . . . . . . . . . . . . . . . . . . 18
2. MS2Pole-Mount Cabinets . . . . . . . . . . . . . . . . . . 20
B. Identification of Feeder and
Distribution Modules . . . . . . . . . . . . . . . . . . . . . 21
C. Cables Entering From Top of Cabinet . . . . . . . . . 21
D. Cables Entering From Bottom of Cabinet . . . . . .21
E . Terminating Procedure . . . . . . . . . . . . . . . . . . . . 21
1. Laying Pairs into Module . . . . . . . . . . . . . . . . . . 21
2. Crimping ................................23
3. Cable Separator Installation. . . . . . . . . . . . . . . . . .24
4. Module Cover Protectors . . . . . . . . . . . . . . . . . . .24
a. 4019 Protector Cover . . . . . . . . . . . . . . . . . . . . .24
F. Tapping..................................26
1. Tapping a Non-Working Feeder Cable . . . . . . . . .26
2. Tapping into a Working Feeder Cable . . . . . . . . . .26
VI. JUMPERING...............................27
A. Running Jumper Wires. . . . . . . . . . . . . . . . . . . . . 27
B. Routing Jumper Wires . . . . . . . . . . . . . . . . . . . . . 28
1. MS2Pedestal Cabinets . . . . . . . . . . . . . . . . . . . . . 28
2. MS2Pole-Mount Cabinets . . . . . . . . . . . . . . . . . .29
C. Half-Tap Jumpering . . . . . . . . . . . . . . . . . . . . . . . .30
D. MS225-PairProbes........................31
1. 4048 25-Pair Probe . . . . . . . . . . . . . . . . . . . . . . . .31
2. 4048A Kit (25-Pair Probe with Connector). . . . . .31
E. PairTestPlug.............................32
F. Priority Circuit Caps . . . . . . . . . . . . . . . . . . . . . . 32
G. 4016E Bunch Block . . . . . . . . . . . . . . . . . . . . . . 32
H. 4017E Bunch Block . . . . . . . . . . . . . . . . . . . . . . 32
VII.GLOSSARY ...............................33
A. Splicing Head Detail . . . . . . . . . . . . . . . . . . . . . .33
B. MS24030 Air/Hydraulic Crimping Unit . . . . . . .33
C. MS24031 Hand/Hydraulic Crimping Unit . . . . . 33
D. Supply Information . . . . . . . . . . . . . . . . . . . . . . . .34
E. MS2Cross-Connect System Ordering Guide . . . 35

4
I. General
A. Introduction
The 3M Brand/MS2Cross-Connect is designed to
provide random cross-connecting between Feeder
and Distribution PIC cables of diameter .7 mm - .32
mm (22-28 AWG). Frames within the cabinets hold
banks of terminated 25-Pair Feeder and Distribution
Modules. Cable pairs are terminated and excess cut
off in a single mechanical operation. Modules can
either be installed initially or added at a better date
with no disruption of existing circuits.
Cross-connecting is accomplished using .5 mm
diameter (24 AWG) plastic-insulated wire which is
run from Feeder to Distribution Modules. Jumper
connections are made and excess wire is cut off by
pressing wire in proper “U” contact channels with
an MS24055 Impact Insertion Tool. Wire race ways
are provided for protection of all cable and jumper
pairs as they are installed.
B. MS2Cross-Connect Pedestal and Pole-
Mount Cabinets
Due to the terminal sizes and frequency of
installation visits, the closures should be located
as specified by the engineering plan. The closures
should be located in unobtrusive locations
acceptable to the property owners and where they
are reasonably protected from damage by motor
vehicles and other machinery. They should also be
at least 1.5 m (5 feet) from utility poles and at least
.3 m (1 foot) from buildings, fences or other objects
considered to be potential lightning attractions.
The terminals are constructed of galvanized steel
with a gray/green baked enamel finish.
The pedestal cabinets feature a ventilation system
whereby the vents may be opened or closed
depending on local condensation conditions.
All MS2Cross-Connect Cabinets include:
(1 ) 4047 Pair Test Plug
(2) 4055 Impact Insertion Tool
(3) Talk Block
(4) Jumpering Instructions
(5) Binding Post Log
(6) Wire Run Guide
(7) Spindle for mounting wire spool

5

6
C. Cross-Connect Pedestal Cabinets Component
Assembly
1. MS24065 (300-Pair) Pedestal Cabinet
The 4065 cabinet consists of hinged front doors equipped
with one lock, a removable hinged panel and backboard
assembly, bond bar, module mounting frame and base, spool
for Jumper Wire and Adjustable Wire Run Guide. Figure 1
is an exploded view of the 4065 cabinet.
2. MS24080 (600-Pair) Pedestal Cabinet MS24082
(900-Pair) Pedestal Cabinet
The 4080 and 4082 cabinets consist of hinged front doors
equipped with one lock, impact tool, test probe and an
internal bond bar, module mounting frame, a base and two
anchor stakes. Figure 2 is an exploded view of the 4080
cabinet. The 4082 differs only in height.
3. MS24084 (1800-Pair) Pedestal Cabinet MS24086
(2700-Pair) Pedestal Cabinet
The 4084 and 4086 cabinets consist of hinged front and
back doors equipped with two locks, a wrap-around bonding
bar, a removable skirt, a module mounting frame, two
impact tools and two test probes. Figure 3 is an exploded
view of the 4084 cabinet. The 4086 differs only in height.
Figure 1.
Figure 2.
Figure 3.
76643

7
D. Cross-Connect Pole-Mount Cabinets Component
Assembly
1. MS24065 (300-Pair) Pole-Mount Cabinet with 4098
Conversion Kit
The 4098 Conversion Kit adapts the 4065 pedestal cabinet
to pole-mount applications. In addition to 4065 components,
the 4098 Conversion Kit consists of top and bottom pole-
mount brackets, plastic cable adapters, bottom plate, and
necessary hardware. Figure 4 is an exploded view of the
4065 cabinet with 4098 pole-mount conversion kit.
2. MS24094 (1200 pair) Pole-Mount Cabinet MS24095
(1800 pair) Pole-Mount Cabinet
The 4094 and 4095 cabinets consist of test probe, impact
insertion tool, hinged front doors equipped with two
locks, two internal bond bars, a center wire nun guide,
module mounting frames, and a pre-drilled backboard for
pole mounting. Figure 5 is an exploded view of the 4094
cabinet. The 4095 differs only in height. Cable port I.D.
of these cabinets is 68.1 mm (2.68”).
Figure 4.
Figure 5.

8
E. MS2Cross-Connect Module
1. Description
Each cross connect application is based on the 25-Pair MS2
Module, a two-part block which contains U contacts, wire
channels, and cut-off blades. Molded of polycarbonate
with phosphor bronze U-contacts and stainless steel cut-
off blades, the module body-cover assembly and base are
crimped together to terminate Feeder or Distribution pair
with a 3M hand or air hydraulic crimping unit The U-
contacts strip the insulation and mate with the conductors,
and the cut-off blades trim excess wire, in the mechanical
crimping operation. Binder groups may be identified on
the module mounts, and pairs can be identified on tagging
labels on the cover protector.
2. MS2Cross-Connect Module Chart:
Item Description
Plastic Polycarbonate
Color Green (4010E:Feeder)
Blue (4011 E:
Distribution)
Contacts “U” Contact phosphor-
bronze
Cut-off Blades Stainless Steel
Wire Range 7 - .32 mm (22-28 AWG)
(sizes maybe mixed)
Insulation PIC-Air Core or Filled
Jumper Wire 5 mm (24 AWG)
3. MS2Cross-Connect Module Detail (Figure 6)
Figure 6.

9
II. Pedestal Cabinet Installation
and Preparation
A. Cable Preparation
1. Stub and Loop Cable Lengths (See Figure 7)
TABLE I
Stub Loop
Cabinet Length Min. Length Min.
m (ft.) m (ft.)
4065 (300-Pair) 1.5 (5) 2.7 (9)
4080 (600-Pair) 1.5 (5) 2.7 (9)
4082 (900-Pair) 1.5 (5) 2.7 (9)
4084(1800-Pair) 2.1 (7) 2.7 (9)
4086 (2700-Pair) 2.1 (7) 2.7 (9)
Carefully remove earth from around cables as follows:
TABLE II
Length Width Depth
Cabinet mm (in.) mm (in.) mm (in.)
4065 (300-Pair) 305 (12) 457 (18) 457 (18)
4080 (600-Pair) 457 (18) 457 (18) 457 (18)
4082 (900-Pair) 457 (18) 457 (18) 300 (12)
4084 (1800-Pair) 1000 (40) 500 (20) 300 (12)
4086 (2700-Pair) 100C (40) 500 (20) 300 (12)
NOTE: Uncover cables sufficiently to definitely establish
their location so that anchor stakes will not injure them.
B. Ground Mount Installation
1. MS24065 (300-Pair) Pedestal Cabinet Ground Mount
Installation
a. Carefully remove earth from around cables per Table II.
b. Open doors on Cabinet Assembly. Cabinet has a
removable Hinged Panel and Base Assembly for
easy access.
c. Fill excavation with coarse gravel to within 102 mm
(4") of ground level.
d. Place Cabinet over cables in a vertical position so
that the Cabinet is centered in the excavation.
e. Place Anchor Stake (optional) to rear of Cabinet.
(Protect Stake top with wood block to prevent
damage while driving.) See Figure 8.
f. Using a sledge, drive until Stake top is 406 mm (16")
above ground level as shown in Figure 9.
NOTE: Do not hammer on Cabinet to drive the Stake
into ground.
g. Secure Anchor Stake to rear of Cabinet with the 3/8"
x 1" bolts and nuts provided. See Figure 10.
h. Fill cabinet base with pea gravel to within 102 mm
(4") of top of skirt.
Figure 7.
Figure 8.
Figure 9.
Figure 10.

10
2. MS24080 (600-Pair) and 4082 (900-Pair)
Pedestal Cabinets
a. Carefully remove earth from around cable per
Table II.
b. Fill excavation with coarse gravel to within 153
mm (6 in.) of ground level.
c. Place Cabinet over cables in a vertical position
so that the Cabinet is centered in the excavation.
d. Place Anchor Stake next to Cabinet side.
(Protect Stake top with wood block to prevent
damage while driving.)
e. Using a sledge, drive until Stake top is at
ground level. (See Figure 11.) Repeat for
opposite side.
NOTE: Do not hammer on Cabinet to drive Stakes
into ground.
f. Align and secure Anchor Stakes to Cabinet with
the 3/8" x 1" bolts and nuts provided.
g. Fill cabinet base with pea gravel to within 102
mm (4 in.) of top of skirt.
3. MS24084 (1800-Pair) and 4086 (2700-Pair)
Pedestal Cabinets
NOTE: The MS24056S Stakes are needed for this
installation.
a. Carefully remove earth from around cables per
Table II. See Figure 12.
b. Fill excavation with pea gravel to within 150
mm (6”) of ground level. See Figure 13.
Figure 11.
Figure 12.
Figure 13.

11
c. Place Cabinet over cables and center on excavation.
See Figure 14.
d. Place an Anchor Stake next to Cabinet side. (Protect
Stake top with a wood block to prevent damage
while driving.) See Figure 15.
e. Using a sledge, drive until Stake holes are aligned
with appropriate holes in Support Column. Repeat
for opposite side.
f. Align and secure Anchor Stakes to the Cabinet with
the 3/8" x 1" bolts provided. See Figure 16.
g. Loosen the four door bolts, remove the four skirt
bolts and remove the Cabinet Skirt. See Figure 17.
h. Upon completion of bonding, preparation and
termination of cables, replace the cabinet skirt
making sure the skirt fits under the cabinet doors.
i. Replace the four skirt bolts and tighten the four door
bolts.
j. Fill cabinet base with pea gravel to within 100 mm
(4") of top of the skirt. See Figure 18.
Figure 14.
Figure 15.
Figure 16.
Figure 17.
Figure 18.

12
C. Poured Slab Mount Installation of 4084 and 4086
Cabinets
NOTE: The MS24056 Mounting Ring Kit is needed for
this installation. See Figure 19.
1. Ground Preparation
a. Excavate slab site to a depth of 300 mm (12 in.)
below ground level allowing for slab dimensions of
1.8 m (6 ft.) x 1.8 m (6 ft.). See Figure 20.
b. Set forms for a 1.8 m (6 ft.) x 1.8 m (6 ft.) x 100 mm
(4 in.) slab.
NOTE: Construct forms so that slope of slab from center
is at the rate of 20 mm per running meter (1 /4 in. per
running foot).
c. Fill excavation with pea gravel to within 100 mm
(4 in.) of ground level. See Figure 21.
d. Attach Concrete Inserts and Support Legs to the
Mounting Ring with the M12 x 25.4 mm (1 /2" x 1")
bolts provided. See Figure 22.
e. Nail wood stakes to Mounting Ring for ease in
leveling. Center Mounting Ring in slab excavation
and level. See Figure 23. (Nails must be cut off when
wooden stakes are removed.)
f. Place concrete reinforcing rods or wire mesh in
slab area.
g. Pour and finish slab.
Figure 19.
Figure 20.
Figure 21.
Figure 22.
Figure 23.

13
h. Wipe excess concrete from top surface of Mounting
Ring. See Figure 24.
2. Slab Mounting the Cabinet
a. After concrete has cured sufficiently, loosen bolts
that secure Support Legs. See Figure 25.
b. Position Cabinet over cables and onto Mounting
Ring.
c. Secure Support Legs to Side Column of Cabinet with
the four 3/8" x 1" bolts provided. See Figure 26.
d. Retighten bolts which secure Support Legs to the
Mounting Ring.
e. Loosen the four door bolts, remove the four skirt
bolts and remove the Cabinet Skirt. See Figure 27.
f. Upon completion of bonding, preparation and
termination of cables, replace the Cabinet Skirt
making sure the Skirt fits under the cabinet doors.
g. Replace the four skirt bolts and retighten the four
door bolts.
h. Fill cabinet bas with pea gravel to within 100 mm
(4") of top of the skirt. See Figure 28.
3. 4056L Support Legs (Refer to Figure 19)
4056L Support Legs are available for surface mounting all
3M Brand Pedestal Cabinets in poured slab applications.
Support Legs may be mounted to slab prior to Cabinet
Installation and will provide firm support for 4065 ,4080,
4082, 4084 or 4086 Pedestals. (Instructions included with
4056L Kits.)
Figure 24.
Figure 25.
Figure 27.
Figure 28.
Figure 26.

14
D. Split Slab Mount Installation for 4084 and
4086 Cabinets
Local Sources should be contacted to make the slabs per the
diagrams in Figure 29.
Figure 29. Dimensions for Split Slab.

15
1. Carefully remove earth from around cables per Table I.
See Figure 30.
Length Width Depth
1780mm (70") 1015mm (40") 150mm (6")
Table I
2. Fill excavation with coarse gravel to within 75mm (3")
of ground level. See Figure 31.
3. Place cabinet over cables and center on excavation.
4. Attach a sib mount Angle Iron to each side of the
cabinet using the six 3/8" x 1" bolts provided. Do not
tighten. See Figure 32.
NOTE: Anchor Stakes must be used in conjunction with
split slab.
5. Place an Anchor Stake next to cabinet side. (Protect
stake top with wood block to prevent damage while
driving.) Using a sledge, drive until stake top is 150mm
(6") above ground level. Repeat for opposite side. See
Figure 33.
Figure 30. Remove earth around cables
Figure 31. Filling with gravel
Figure 32. Bolt on Angle Irons
Figure 33. Drive in Stake

16
6. Secure Anchor Stakes to cabinet with the 3/8" x 1"
bolts provided. See Figure 34.
7. Slide slab sections into place. Insert four slab mount
bolts (not included) trough the Angle Irons and thread
loosely into slab sections.
8. Drive Anchor Stakes so Angle Irons are flat on the slab.
Tighten all mount bolts securely. See Figure 35.
9. Fill cabinet base with pea gravel to within 100 mm (4")
of top of the skirt.
Figure 34.
Figure 35.

17
E. Cable Preparation
1. Feeder cables terminated in the cabinet will be secured
per standard procedure at the center of the Bond Bar.
2. If Feeder Cable is to loop through, secure Cables as
close together as possible at the center of the bar.
NOTE: On 4084 and 4086 Cabinets, the Bond Bar may
be moved from outside bracket to center bracket location if
center Bond Bar application is desired. See Figure 36.
3. Using the top of the Bond Bar as a guide, mark cables.
NOTE: For easy cable preparation, Cabinet Skirt, Bond
Bar and Frame Assembly may be removed.
4. Remove cable jacket(s), shield and core wrapper this
mark.
NOTE: If cables are to be sealed against moisture, a just
sheath opening so that top of end seal is flush with top of
Bond Bar. Bond Straps should be long enough to project
from the top of the end seal one of the Bond Bar fastening
bolts.
5. Bond cables to Bar per standard procedure. Repeat until
all cables are bonded and secured.
6. If grounding of cabinet is required, do so per standard
procedure.
7. Plug all ducts per standard procedure.
8. Fill cabinet base with pea gravel to within 102 mm (4
in.) of the top.
Figure 36.

18
III.Pedestal Cabinet Cable Routing
A. MS24065 (300-Pair) Cabinet
1. Pairs to be terminated must run through the grommeted
holes in Hinged Panel.
2. Form a .6 m (2 ft.) gooseneck behind Panel to allow for
slack. See Figure 37.
3. The loop through cable (express pairs) should be taped
or wrapped and secured to rear of cabinet.
4. Cable Ties are provided to secure cable to Backboard.
B. MS24080 (600-Pair) Cabinet
MS24082 (900-Pair) Cabinet
MS24084 (1800-Pair) Cabinet
MS24086 (2700-Pair) Cabinet
1. Allow 76 - 102 mm (3" - 4") of cable slack by forming
a dog-leg and temporarily tie cable in place. This
prevents stress damage to Modules during normal
settling and shifting of ground. See Figure 38.
2. Remove tie after completion of terminating.
C. Cable Terminated In Cabinet
1. If feeder or distribution pair count exceeds the capacity
of the front side of the Frame, the balance should be
terminated on the rear Frame.
2. Bond and secure cables to Bond Bar per standard
procedure.
3. Repeat until all cables are bonded and secured.
D. Cable Looped Through Cabinet
1. Identify binder groups that will terminate in this
Cabinet.
2. Lay express binder groups in unused Frame (or behind
Frame on MS24065, 4080 and 4082 Cabinets).
3. If future additions are to be made, store involved
express binder groups in Frame where they will
eventually be used. Wrap express binder groups if
required.
4. Bond and secure cables to Bond Bar per standard
procedure. See Figure 39.
5. Repeat until all cables are bonded and secured.
Figure 37.
Figure 38.
Figure 39.

19
IV. Pole-Mount Installation and Preparation
A. MS24065 (300-Pair) with 4098 Conversion Kit
1. Pole-Mount Conversion Kit
a. Remove front Skirt and Hinged Panel for easy
access.
b. Locate Cabinet in desired position on pole per
Figure 40.
c. Assemble A1, A2, and A3 to Top Pole-Mount
Bracket and tighten.
d. Attach Top Pole-Mount Bracket assembly to pole
with B-1.
e. Assemble Bottom Pole-Mount Bracket to Cabinet
with C1, C2, and C3.
f. Hang Cabinet assembly on Bolt A1, and secure with
D1 and D2.
g. Screw E1 through Cabinet, bottom Pole-Mount
Bracket and into pole.
2. Cable Adapter-Top
a. Remove appropriate knockout.
b. Remove foam around inside of knockout hole for
Adapter Nut clearance.
c. Install Cable Adapter per Figure 41.
d. Insert Cable leaving 1.8 m (6 ft.) stub length.
e. Tighten Adapter Nut securely.
f. Secure Adapter on Cable with 3 half-lapped layers of
Vinyl Plastic Tape.
g. Secure Cable to Tab in rear of cabinet top using
standard hose clamp.
h. Install bond clamp per standard practice.
i. Attach bonding strap to Bond Bar.
NOTE: Do not clamp cable to pole any closer than
304.8mm (12") from top of cabinet.
3. Bottom Plate and Cable Adapter Installation
a. Attach Bottom Plate with Nuts and Bolts provided as
shown in Figure 42.
b. Tighten securely.
c. Install Cable Adapter per Figure 42.
d. Insert cable leaving 1.8 m (6 ft.) stub length.
e. Secure Adapter on Cable with 3 half-lapped layers of
Vinyl Plastic Tape.
f. Bond and secure cables to Bond Bar.
g. Attach bonding strap directly to Bond Bar.
Figure 37.
Figure 38.
Figure 39.

20
B. MS24094 (1200-Pair) and 4095 (1800-Pair)
1. Pole Mount Installation:
Mount cabinet in desired position on pole using hardware
included. Follow standard procedure. See Figure 43.
2. Cable Installation:
a. Cables should enter cabinet through ports directly in
line with appropriate module frame. If only a single
cable is to be terminated, place cable in center port to
provide the best protection for the cable.
b. The preferred method is to mount the feeder cable in
center Module frames and mount distribution cables
in outer frames as shown in Figure 44.
c. Loop through cables may be installed in the bottom
of a cabinet by removing cabinet End Cap Plate. See
Figure 36.
d. The stub length should be a minimum of .6 m (2 ft.)
longer than the farthest termination.
C. Cable Preparation
1. Remove cable sheath and shield flush the top of tabs on
the Bond Bar.
2. Install Bond Clamp per standard procedure and secure
to holes in Bond Bar.
3. Place a standard hose clamp around the cable and Bond
Bar Tab. Tighten securely. Repeat for all cables.
4. Identify binder groups.
NOTE: The 4097 Split Gland Kit is available for sealing
cable entrance in top or bottom of pole cabinets.
V. Terminating
A. Location of Feeder and Distribution Modules
1. MS2Pedestal Cabinets
Figures 45, 46 and 47 illustrate the recommended location
of Feeder (green Cover) and Distribution (blue Cover)
Modules. Cable handling will be simplest with these
layouts. However, alternate locations for feeder and
Distribution Modules will in no way change the principle of
cross connecting with MS2.
a. Feeder and Distribution Module Location in 4065
Pedestal Cabinet. See Figure 45.
NOTE: Feeder Module Locations are Interchangeable
from Top to Bottom by relocating the adjustable jumper
wire run.
Figure 43.
Figure 44.
Figure 45.
This manual suits for next models
7
Table of contents
Other 3M Enclosure manuals