A-T Controls Triac TMC-4 User manual

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
1 07/02/21
www.atcontrols.com IOM08139 REVISION 04
Installation and Operation Manual
TMC-4 Control Card (v3.00)
Features
4-20mA, 0-10VDC, 0-5VDC, Potentiometer,
Open/Close command inputs
4-20mA or 0-10VDC self-powered transmitter
Programmable fail positions on loss of command
signal: In Place, CW, CCW, % Value
LCD screen with 5-point joystick for menu navigation
Expansion module slot
External brake control for spring return actuators
Motor temperature monitor by thermistor input
Sleep mode
Overview
The Triac TMC4 control card is a motor controller intended to be used in electric actuators rated for running current loads
up to 10 amps. The TMC4 control card is available in two versions. An AC version can drive reversible AC motors with a
85-250VAC supply voltage, or a DC version can drive DC motors with a 24VDC supply voltage.
The LCD screen provides easy viewing of status and configuration while a 5-point joystick allows easy navigation through
the various configuration menus and settings. An optional module slot permits expansion on the capabilities of the
controller to support various communication busses or other control and interface options.
The TMC4 provides two main positioning options; proportional or two position. When operated as a proportional controller,
the TMC4 compares an external command signal to a position feedback from a potentiometer connected to the output
shaft of the actuator. When the two signals differ by a given magnitude, the TMC4 controller will energize the motor to
operate either clockwise or counterclockwise to reduce the difference between the two signals. When operated as two-
position controller, the TMC4 receives an open or close command, and drives the actuator clockwise or counterclockwise
until activation of a position limit switch is detected.
The TMC4 is designed to be mounted using PEM Snap-Top spacers for easy mounting and removal without the need for
screws, while still providing a secure mount for most conditions.
The TMC4 must be installed in an appropriate enclosure to avoid electrical shocks. When operating,
high voltages will be present on the controller, requiring caution during the installation process. Power
should be deenergized before making wire connections to the TMC4. A heater and thermostat should
be used when possible, to prevent condensation.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
2 07/02/21
www.atcontrols.com IOM08139 REVISION 04
Contents
1. Layout .................................................................................................................................................................. 3
1.1. Dimensions .......................................................................................................................................................... 4
2. Wiring and Operation ........................................................................................................................................... 5
2.1. Terminals ............................................................................................................................................................. 6
2.2. Wiring Diagrams .................................................................................................................................................. 7
2.3. Input / Output Signal Configurations ................................................................................................................... 8
3. Menu .................................................................................................................................................................... 9
3.1. STATUS Screens / MANUAL Mode .................................................................................................................. 10
3.2. COMMAND CONFIG submenu ......................................................................................................................... 11
3.3. FEEDBACK CONFIG submenu ........................................................................................................................ 12
3.4. POSITION CONFIG submenu ........................................................................................................................... 13
3.5. COMMS CONFIG submenu .............................................................................................................................. 14
3.6. AUX. I/O CONFIG submenu .............................................................................................................................. 15
3.7. SYSTEM CONFIG submenu ............................................................................................................................. 16
4. Setup and Calibration ........................................................................................................................................ 17
4.1. Positioning Devices ........................................................................................................................................... 17
4.1.1. Feedback Potentiometer (P7) ..................................................................................................................... 17
4.1.2. Position Limit Switch (P5) ........................................................................................................................... 18
4.1.3. Stop/Torque Limit Switch (P9) .................................................................................................................... 18
4.2. Analog Control Calibration ................................................................................................................................. 19
4.2.1. Command and Feedback Values ................................................................................................................ 19
4.3. Two-Position Control Calibration ....................................................................................................................... 20
4.4. Communication Bus Control Calibration ........................................................................................................... 20
4.5. Reverse Action / Direct Action ........................................................................................................................... 21
5. Options .............................................................................................................................................................. 21
5.1. Motor Temperature Monitor ............................................................................................................................... 21
6. Troubleshooting ................................................................................................................................................. 22
7. Specifications ..................................................................................................................................................... 23

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
3 07/02/21
www.atcontrols.com IOM08139 REVISION 04
1. Layout
1 – Power / Motor Terminals (P1)
Terminals for connecting supply power, motor
connections, enclosure heater, and for external brake for
spring return actuators. Refer to 2.1 for details.
2 – Signal Terminals (P2)
Terminals for connecting control signal, analog
feedback signal, +24VDC output and Earth/chassis
ground connection. Refer to 2.1 for details.
3 – Fuse
The fuse is a standard 5x20mm time delay fuse rated for
10A, 250V. Replacement fuses shall not exceed this
maximum rating.
4 – Expansion Header (P4) (option)
14 point connection header for optional accessory
interfaces.
5 – Position Switches Header (P5)
3 point connection header for positioning limit switches
when required for actuator control. Switches connected
to this header provide position limits when operating as
two-position actuator, and provide Open/Close status for
the TMC4.
7 – Feedback Potentiometer Header (P7)
3 point connection header for feedback potentiometer
when required for actuator control. This provides
positioning feedback for when operating as a
proportional control actuator.
8 – Thermistor Header (P8) (option)
2 point connection header for optional motor
temperature monitor thermistor to prevent motor
overheating.
9 – Stop (Torque) Switches Header (P9)
3 point connection header for motor stop limit switches
when required for actuator control. Switches connected
to this header will stop the motor when activated, without
providing Open/Close status. These switches are useful
when driving motor directly with the control card, rather
than driving the motor through limit or torque switches.
This would typically be for DC motor applications, where
operating motor through limit switches is not practical.
10 – Option Module Slot
mSATA / Mini PCI Express connection point for optional
feature modules such as for serial communication or
other control types. Option modules can be installed with
(2) 4-40 screws, 3/16” to 1/4" in long.
Insert option module into
connector and rotate flat. Tighten
with #4-40 screws.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
4 04/06/22
www.atcontrols.com IOM08139 REVISION 04
11 – Joystick
5-way joystick (up, down, left, right, center) for menu
navigation and adjustment of parameters and settings.
Direction
Function
UP ▲
[PREVIOUS]
Navigate up in menus.
Choose previous setting selection or
increase setting value.
Motor CCW in Manual Mode or POSITION
CONFIG calibrate settings.
DOWN ▼
[NEXT]
Navigate down in menus.
Choose next setting selection or decrease
setting value.
Motor CW in Manual Mode or POSITION
CONFIG
calibrate settings.
LEFT ◄
[CANCEL]
Navigate left in menus.
Return to previous menu screen or exit
menu subgroup.
Cancel or exit setting without saving.
RIGHT ►
or
CENTER ◙
[CONFIRM]
Navigate right in menus.
Enter parameter screen to adjust setting.
Parameter value will flash indicating it can
be changed.
Confirm or save setting when finished
changing.
NOTE: When incrementing/decrementing a setting value, the
value step increases in value every 6 presses for more rapid
adjustment. Reset the step back to +1 by pressing back in
opposite direction.
12 – Display
OLED screen to show actuator status and menu options.
Display will enter a sleep mode where the display is shut
off if joystick has not been used for 5 minutes. Remote
functionality is still enabled while in sleep mode. Status
LED will flash while in sleep mode. Pressing any
direction on joystick will wake up display.
13 – LEDs
Status:
Flashes 1 second on when in Sleep Mode.
Power:
Solid to indicate the TMC4 is powered
either by the supply terminals, or through
the USB connector.
USB:
Solid to indicate USB cable is connected to
the micro USB connector.
14 – Run/Program Switch
Used by factory for programming and setup. Switch
should be in off position (pointed away from USB
connector) for normal operation.
15 – USB Connector
Micro USB receptacle. Used by factory for programming
and setup. Can be used to power board for configuration
without having supply power connected.
1.1. Dimensions
UP ▲
(PREVIOUS)
DOWN ▼
(NEXT)
LEFT ◄
(CANCEL) RIGHT ►
(CONFIRM)
CENTER ◙
(CONFIRM)

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
5 04/06/22
www.atcontrols.com IOM08139 REVISION 04
2. Wiring and Operation
The supply voltage and motor should be connected as
shown in the wiring section.
SUPPLY
Supply voltage is connected to terminals (P1-2) and (P1-
3). Line/+ should be connected to (P1-2) and Neutral/-
should be connected to (P1-3). The AC version can
accept a single phase supply voltage of 85-250VAC, 50-
60Hz, while the DC version can accept a supply voltage
of 24VDC. An Earth ground connection is provided on
terminal (P2-7).
MOTOR
For AC type motors, the winding that drives the actuator
clockwise should be connected to the Motor CW terminal
(P1-5), and the winding that drives the actuator
counterclockwise should be connected to the Motor
CCW terminal (P1-6). The motor neutral wire should be
connected to the Motor N terminal (P1-7).
For DC type motors, the wires should be connected to
the Motor CW (P1-5) and Motor CCW (P1-6) terminals
only. When operating DC motors, the Motor CW and
Motor CCW terminals switch polarity to the motor. A
clockwise operation will apply the positive supply voltage
to the Motor CW terminal (P1-5), and a counterclockwise
operation will apply the positive supply voltage to the
Motor CCW terminal (P1-6). The motor wires should be
connected accordingly.
BRAKE
An external brake connection is provided on terminal
(P1-4) to operate spring return type actuators that use a
motor brake to hold the actuator in position. The output
is the same voltage as the supply voltage. The maximum
brake output rating of 300mW, 350V, 120mA continuous
load must not be exceeded.
The AC version of the TMC4 keeps the external brake
output energized until either of the motor outputs is
activated, at which point, the external brake output
deenergizes. The DC version of the TMC4 keeps the
external brake output deenergized until the motor
outputs are activated, at which point the external brake
output energizes.
The brake setting is currently configured exclusively for
use on Triac SRX series actuators and is not
configurable. Care must be taken when using with other
type of actuator motor brakes.
Using brake output on incorrect brake type
may damage the TMC4 card, brake or
actuator.
HEATER
The TMC4 also provides a dedicated terminal (P1-1) for
a heater output that is internally connected directly to the
Line/+ supply terminal (P1-2). An enclosure heater is
strongly recommended to prevent moisture inside the
actuator enclosure. The other heater connection should
either be to motor neutral terminal (P1-7) or supply
Neutral/- terminal (P1-3).
I/O
Standard analog control inputs for 4-20mA, 0-5V, 1-5V,
0-10V, 2-10V should be connected to signal input A1
terminals (P2-2) and (P2-3). 0-20mA and 0-10V analog
feedback signals should be connected to A2 terminals
(P2-4) and (P2-5). This feedback signal is self-powered
by the TMC4 controller, so no loop power is required by
the user.
The TMC4 can also be configured to operate by a
variable resistor input, such as a slide wire or
potentiometer by connecting the ends across the
+24VDC (P2-1) and AGND (P2-3), and the wiper to the
input A1 terminal (P2-2).
The +24VDC output across (P2-1) and (P2-6) is
available to drive a single device up to 30mA or use with
handheld loop calibrator set as 2-wire transmitter to
locally control the actuator while conserving battery
power. Refer to wiring diagrams in following section.
The input A1 and output A2 terminals also serve to
operate as a two-position actuator when configured for
ON-OFF command type using an external 12-24VDC
signal, or using the internally supplied +24VDC output.
In ON-OFF command type, A1 terminal (P2-2) functions
as the Open/CCW input, and A2 terminal (P2-4)
functions as the Close/CW input. This can be useful if
driving AC motor with isolated low power command
signal.
NOTE: If driving the motor through limit switches, the
actuator can be operated like a standard on/off, but will
not display end of position unless limit switches are
wired to the on-board position limit switch connection
header (P5).

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
6 04/06/22
www.atcontrols.com IOM08139 REVISION 04
2.1. Terminals
(P1)
Power / Motor
Terminals
Function
1 Heater L/+ Supply power output for heater.
Internally connected to Supply L/+ terminal.
2 Supply L/+ Supply Power Line or (+)
3 Supply N/- Supply Power Neutral or (-)
4 External
Brake
Output for spring return electric actuator brakes.
Switches supply power when motor outputs are
energized.
AC version: Switch off when motor on.
DC version: Switch on when motor on.
5 Motor CW
AC version: Energize clockwise motor winding.
DC version: Switch (+) supply voltage for
clockwise operation.
6 Motor CCW
AC version: Energize counterclockwise motor
winding.
DC version: Switch (+) supply voltage for
counterclockwise operation.
7 Motor N
Internally connected to Supply N/- terminal. Can
be used for second heater connection.
AC version: Motor neutral
DC version: No motor functionality
(P2)
Signal / Comm
Terminals
Function
1 +24V Out Auxiliary 24VDC output.
2 I/O 1 (A1)
Signal In Command signal input.
3 Signal GND Command signal reference.
4 I/O 2 (A2)
Signal Out Feedback signal output.
5 Signal GND Feedback signal reference.
6 GND / 0V 0V reference for +24V output.
7 Earth Connected to enclosure through
TMC4 mounting bracket.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
7 04/06/22
www.atcontrols.com IOM08139 REVISION 04
2.2. Wiring Diagrams
AC Proportional Control AC Two Position Control
DC Proportional Control DC Two Position Control

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
8 04/06/22
www.atcontrols.com IOM08139 REVISION 04
2.3. Input / Output Signal Configurations
Command Type = mA Sinking
Externally Powered Loop Control
Command Type = mA Sinking
2-Wire Transmitter Control
Command Type = 5V and 10V
Command Type = Potentiometer
Command Type = On-Off
Externally Powered Inputs
Command Type = On-Off
Using TMC-4 +24V Output
Feedback = mA or V

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
9 04/06/22
www.atcontrols.com IOM08139 REVISION 04
3. Menu

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
10 04/06/22
www.atcontrols.com IOM08139 REVISION 04
3.1. STATUS Screens / MANUAL Mode
The STATUS screen group contains various screens displaying functional information such as positioning values, motor
status and control parameters. Pressing [CANCEL ◄] from any screen will return to the Home screen. Pressing
[CONFIRM ►/◙] three times from the Home screen will enter a manual control screen where the actuator can manually
be controlled open or close with the joystick. Pressing [CANCEL ◄] three times from the manual control screen escapes
back to the Home screen.
P O S : x x x x
C M D : x x x x
M T R : x x x x
Home
POS:
Current travel position.
Percentage with “Position Type” set to Potentiometer positioning in POSITION CONFIG submenu.
OPEN, N/A, or CLOSE with “Position Type” set to Limit Switch positioning in
POSITION CONFIG
submenu.
CMD:
Setpoint command position.
Percentage with “Position Type” set to Potentiometer positioning in POSITION CONFIG submenu.
0.0%, 100.0% or STOP with “Position Type” set to Limit Switch positioning in POSITION CONFIG submenu.
May show LOST if command signal is disconnected depending on command type.
MTR:
Motor status. OPEN, CLOSE or IDLE
If motor temperature limit feature is enabled, will display as HEAT DELAY during forced motor off periods
while traveling.
C O N T R O L
C M D : x x x x
F B : x x x x
Control
CMD:
Command signal type set in “Command Type” setting in
COMMAND CONFIG
submenu
FB:
Feedback signal type set in “Feedback Type” setting in
FEEDBACK CONFIG
submenu.
T E M P E R A T .
M T R : x x x x
A M B : x x x x
Temperature
MTR:
Motor temperature. Only displays with motor temperature monitoring option connected and
enabled.
AMB:
Ambient temperature of TMC4 electronics. Note this may be slightly higher than internal
ambient temperature of the installation enclosure.
L I M I T S W T
O P E N : x x x
C L O S : x x x
Position & Stop
Switches
Alternates between showing state of Position limit switches connected to (P5) and Stop/Torque
switches connected to (P9). Switch state is determined by N.O. or N.C. contact logic set in
POSITION CONFIG
submenu.
OPEN:
State of Open Position or Stop limit switch. ON if limit switch activated. OFF if limit switch is
not activated.
CLOS:
State of Close Position or Stop limit switch. ON if limit switch activated. OFF if limit switch is
not activated.
C O M M S
I D : x x x x
S T A T : x x x x
Communication
ID:
Value set in “Unit ID” setting in
COMMS CONFIG
submenu.
STAT:
Communication status. Indicates if communication is active, idle or lost. Shows time of
last communication.
= = = = = = = = = =
C O N F I G U R E
> >
Configure
Enters configuration submenus.
Note, remote command signals will not operate actuator when entering configuration settings.
M A N U A L O P
- - - - - - - - - -
P O S : X X X X
Manual Mode
Manually operate actuator with joystick.
Press [CONFIRM ►/◙] 3x times to enter. Press [CANCEL ◄] 3x to escape back to Home screen.
[PREVIOUS ▲] energizes CCW motor ouput. [NEXT ▼] energizes CW motor output.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
11 04/06/22
www.atcontrols.com IOM08139 REVISION 04
3.2. COMMAND CONFIG submenu
The COMMAND CONFIG menu group contains various parameters associated with the control and response of the
actuator. The command signal type and limits are set in this submenu, as are loss of signal behavior and deadband.
C O M M A N D
T Y P E :
x x x x
Command
Signal Type
Sets type of command signal used. Zero and Span should be recalibrated when changed. DEFAULT = mA Sink
10V:
0-10V or 2-10V, configurable with the zero and span setting.
5V:
0-5V or 1-5V, configurable with the zero and span setting.
mA
Sink:
4-20mA sinking. Loop is powered by user.
135 Ohm
:
Variable resistance input. For typical 135 Ω slide wire.
1k Ohm:
Variable resistance input. For 1 kΩ potentiometer.
ON
-
OFF:
Independent Open and Close inputs. Feedback is disabled.
Comms: Communication protocol (e.g. Modbus RTU) Specific protocol must be
selected in the
COMMS CONFIG
submenu.
C A L I B R A T E
Z E R O
x x x x
Calibrate
Command Zero
Sets command signal zero digital count value. When selected, provide minimum command signal for direct action,
and maximum control signal for reverse action. An input of this magnitude will drive actuator toward the
programmed “Calibrate Close Pos” in the POSITION CONFIG menu.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range. Typical values can be
found in Section 4.2.1.
C A L I B R A T E
S P A N
x x x x
Calibrate
Command Span
Sets command signal span digital count value. When selected, provide maximum command signal for direct
action, and minimum control signal for reverse action. An input of this magnitude will drive actuator toward the
programmed “Calibrate Open Pos” in the POSITION CONFIG menu.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range. Typical values can be
found in Section 4.2.1.
D E A D B A N D
x . x %
Deadband
Sets deadband range by percent. RANGE = 0.5% to 50.0% DEFAULT = 1.0%
This value determines the acceptable deviation from command setpoint the controller will recognize as valid
position. If set to 1.0%, when provided a 50.0% setpoint, the controller will position to between 49.0% and 51.0%.
A setpoint outside a value in this range must be provided to move.
When selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust value.
L O S S O F
S I G N A L :
x x x x
Loss of Signal
Sets behavior of actuator when command signal is lost. DEFAULT = Fail Close
In Place:
Remains in current position on loss of command signal.
Open:
Moves to programmed Open position on loss of command signal.
Close:
Moves to programmed Close position on loss of command signal.
Percent
:
Moves to position specified in “Fail to Percent” setting.
F A I L T O
P E R C E N T :
x x x x
Fail to
Percent
Sets percent position between 0% and 100% for actuator to control to on loss of command signal. Is only utilized if
“Loss of Signal” type is set as “Position”.
DEFAULT = 50.0%.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
12 04/06/22
www.atcontrols.com IOM08139 REVISION 04
M O T O R T E M P
L I M I T :
x x x x
Motor
Temperature
Monitor
Sets temperature ranges for the motor temperature monitor connected to (P8). Below values indicate duty cycle
restriction. DEFALUT = Disabled
Disabled
:
Ignores input to thermistor header (P8).
75C
:
Below 75C = normal 75C to 90C = 60% 90C to 105C = 40% Above 105C = 20%
90C
:
Below 90C = normal 90C to 105C = 60% 105C to 120C = 40% Above 120C = 20%
105C
:
Below 105C = normal 105C to 120C = 60% 120C to 135C = 40% Above 135C = 20%
3.3. FEEDBACK CONFIG submenu
The FEEDBACK CONFIG menu group contains parameters associated with the position feedback signal for the actuator.
The analog feedback signal can be set and adjusted here.
F E E D B A C K
T Y P E :
x x x x
Feedback
Signal Type
Sets type of feedback signal. DEFAULT = mA
mA:
0.0 to 21.5 mA
Disabled:
When command type is set for ON-OFF
C A L I B R A T E
Z E R O
x x x x
Calibrate
Feedback Zero
Sets feedback signal zero digital count value. When selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust
feedback until desired value is measured. Note, this feedback will correspond to the programmed “Calibrate Close
Pos” position in the POSITION CONFIG menu. If command is set for reverse action, set this value accordingly.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range. Typical values can be
found in Section 4.2.1.
C A L I B R A T E
S P A N
x x x x
Calibrate
Feedback Span
Sets feedback signal span digital count value. When selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust
feedback until desired value is measured. Note, this feedback will correspond to the programmed “Calibrate Open
Pos” position in the POSITION CONFIG menu. If command is set for reverse action, set this value accordingly.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range. Typical values can be
found in Section 4.2.1.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
13 04/06/22
www.atcontrols.com IOM08139 REVISION 04
3.4. POSITION CONFIG submenu
The POSITION CONFIG menu group contains parameters associated with the positioning of the actuator. There are two
types of positioning methods used; one using limit switches for two position operation, and the other using feedback
potentiometer for modulating for proportional control operation.
When using limit switches, the open and close limits are set using the mechanical cams and limit switches in the actuator.
These switches should be connected to (P5) Limit Switch header. When using feedback potentiometer, the open and
close limits are programmed in this submenu and the potentiometer should be connected to (P7) Feedback Potentiometer
header.
P O S I T I O N
T Y P E :
x x x x
Position Type
Sets type of feedback used for positioning. Default is set for potentiometer positioning.
Limit SW: Uses position limit switches to detect discrete end of travel position for two-position
on/off control. “Calibrate Close” and “Calibrate Open” settings are not used.
Potent: Uses potentiometer to detect position for modulating and proportional positioning
control. Limits are determined by the “Calibrate Close” and “Calibrate Open” position
settings.
C A L I B R A T E
C L O S E P O S
x x x x
Calibrate Close
Position
Only used with potentiometer feedback to set position limit when the CW motor output is energized to move
actuator in clockwise direction. This position will correspond to the “zero” value set in COMMAND CONFIG
submenu. When selected, use [PREVIOUS ▲] or [NEXT ▼] to drive motor to desired close/clockwise position. If
limit switch position type is selected, this value is not used during operation.
Value is scaled between 12 bit count of 0 and 4095 based on the measured feedback potentiometer position.
There is no “correct” value to set to, but it is recommended to fall within the range of 400-3700.
C A L I B R A T E
O P E N P O S
x x x x
Calibrate Open
Position
Only used with potentiometer feedback to set position limit when the CCW motor output is energized to move
actuator in counterclockwise direction. This position will correspond to the “span” value set in COMMAND
CONFIG submenu. When selected, use [PREVIOUS ▲] or [NEXT ▼] to drive motor to desired
open/counterclockwise position. If limit switch position type is selected, this value is not used during operation.
Value is scaled between 12 bit count of 0 and 4095 based on the measured feedback potentiometer position.
There is no “correct” value to set to, but it is recommended to fall within the range of 400-3700.
T R A V E L
T I M E O U T
x x S
Travel Timeout
Only used with communication bus options. Value should be greater than the normal actuator travel time. The
TMC4 begins a timer when the motor outputs are energized to control the actuator to the commanded position. If
the timer exceeds the timeout value before the command position is reached, the motor output is turned off. When
selected, use [PREVIOUS ▲] or [NEXT ▼] to adjust value. Can also be configured via communication protocol.
DEFALUT = 60 seconds
S W A C T I N G
L I M . T O R Q .
x x x x x x x x
Switch Action
Sets contact logic of the position limit switches connected to header (P5) and stop/torque switches connected to
(P9).
N.O. indicates normally open action where input is activated when switch contact is closed.
N.C. indicates normally closed action where input is activated when switch contact is opened.
DEFAULT = N.O. / N.O.
NOTE: Calibrate Close and Calibrate Open value is scaled between 12 bit count of 0 and 4095 based on potentiometer reading. It may
increase or decrease depending on how potentiometer is wired, but should never jump between 0 and 4095 extremes.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
14 04/06/22
www.atcontrols.com IOM08139 REVISION 04
3.5. COMMS CONFIG submenu
The COMMS CONFIG menu group contains parameters associated with the various communication protocols supported
by the TMC-4 control card. While some parameters in other menus are configurable via communication link, the
communication parameters necessary to establish the link such as device ID or address must be set here first.
C O M M S
T Y P E :
xxxx
Communication
Type
Sets type of communication protocol when using one of the communication module options. “Comms” command
type must be selected in the COMMAND CONFIG submenu.
Modbus
RTU
Modbus RTU
M
od
bus
TCP
Modbus/TCP
Profibus
Profibus DP
U N I T I D :
x x
Unit ID
Actuator ID address. Selectable from 1 to 246.
DEFAULT = 1
B A U D R A T E
x x x x
Baud Rate
Communication channel data rate. 9600, 19200, 57600, 115200 bps
DEFAULT = 9600
P A R I T Y :
x x x x
Parity
Communication channel parity setting. None, Odd, Even
DEFAULT = None
T I M E O U T :
x x . x x S
Timeout
Communication timeout. Determines duration of time which the actuator must receive communication before
entering fault condition.
DEFAULT = 10 seconds
I P
S E T T I N G S
IP
Settings
Shows the IP settings for the actuator. Cycled through displaying the IP address, the IP subnet mask and the IP
gateway. Note that this information is not adjustable and can only be viewed here. Refer to appropriate
communication module instructions on how to set the IP address.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
15 04/06/22
www.atcontrols.com IOM08139 REVISION 04
3.6. AUX. I/O CONFIG submenu
The AUX. I/O CONFIG menu group contains parameters associated with additional I/O modules that can be added with
specific options.
A U X . D O
S I G N A L :
xxxx
Auxiliary Digital
Output Function
Sets functionality of the auxiliary digital outputs.
O-C Cmd Digital outputs provide programmable auxiliary limit switch outputs based on values set in the
“Calibrate Aux. DO Close” and “Calibrate Aux. DO Open” settings. This setting can only be used
with proportional control applications since it requires a percentage value based
on using a
feedback potentiometer.
DO1 = Programmed Aux Close position
DO2 = Programmed Aux Open position
Lim SW Digital outputs mirror the position limits of the switches connected to position switch header (P5).
DO1 = Close position limit
DO2 = Open position limit
Motor Out Digital outputs mirror the motor outputs. When specified motor output is energized, the
corresponding digital output is activated.
DO1 = CW motor output
DO2 = CCW motor output
A U X . D I
S I G N A L :
xxxx
Auxiliary Digital
Input Function
Sets functionality of the auxiliary digital inputs.
Disable
Digital inputs are disabled.
Local Ctrl Digital inputs are configured for local/remote inputs.
DI1 = Local close switch input. When DI1 terminals are powered, the TMC4 commands a 0.0%
signal and moves to programmed 0.0% position while DI3 detects local input. If operating
as on/off actuator, it will drive to the close position limit switch.
DI2 = Local open switch input. When DI2 terminals are powered, the TMC4 commands a
100.0% signal and moves to programmed 0.0% position while DI3 detects local input. If
operating as on/off actuator, it will drive to the open position limit switch.
DI3 = Local/remote switch input. When DI3 terminals are powered, the TMC4 goes into local
control mode and disables remote signals. It will only operate with signals input to DI1 and
DI2 terminals.
A U X . A O
S I G N A L :
xxxx
Auxiliary Analog
Output Function
Sets functionality of the auxiliary analog outputs.
Feedback Provides auxiliary 0-20mA analog output independent of standard feedback signal based on
calibrated auxiliary output zero and span.
4mA
Provides constant 4mA analog output based on calibrated auxiliary output zero and span.
20mA
Provides constant 20mA analog output based on calibrated auxiliary output zero and span.
C A L I B . A U X
A O Z E R O
x x x x
Calibrate Aux.
Analog Out Zero
Sets auxiliary analog output signal zero digital count value. When selected, use [PREVIOUS ▲] or [NEXT ▼] to
adjust feedback until desired value is measured. Note, this feedback will correspond to the programmed
“Calibrate Close Pos” position in the POSITION CONFIG menu. If command is set for reverse action, set this
value accordingly.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range.
C A L I B . A U X
A O S P A N
x x x x
Calibrate Aux.
Analog Out Span
Sets auxiliary analog output signal span digital count value. When selected, use [PREVIOUS ▲] or [NEXT ▼]
to adjust feedback until desired value is measured. Note, this feedback will correspond to the programmed
“Calibrate Open Pos” position in the POSITION CONFIG menu. If command is set for reverse action, set this
value accordingly.
Value is scaled between 12 bit count of 0 and 4095 for the selected command type range.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
16 04/06/22
www.atcontrols.com IOM08139 REVISION 04
C A L I B . A U X
D O C L O S E
25%
Calibrate Aux.
Digital Out Close
Sets percentage value for when DO1 is activated when Aux. DO Output set for “O-C Cmd” function. DO1 is
activated between this set value and the close (0%) position set in the POSITION CONFIG submenu. Default
value of 25% meaning between 0% and 25%, DO1 will remain activated.
C A L I B . A U X
D O O P E N
75%
Calibrate Aux.
Digital Out Open
Sets percentage value for when DO2 is activated when Aux. DO Output set for “O-C Cmd” function. DO2 is
activated between this set value and the open (100%) position set in the POSITION CONFIG submenu. Default
value of 75% meaning between 75% and 100%, DO2 will remain activated.
3.7. SYSTEM CONFIG submenu
The SYSTEM CONFIG menu group contains information for the TMC-4 control card such as software version and cycle
count as well as setting for selecting type of motor being operated and restoring factory defaults.
M O T O R
T Y P E :
x x
Motor Type
Displays type of motor braking based on if AC version of TMC4, or DC version. AC indicates motor brake output
turns off when either motor output is energized. DC indicates motor brake output turns on when either motor
output is energized.
This option is not configurable and is designed for use with A-T Controls SRX series actuators.
C Y C L E C N T
O P E N : x x x
C L O S : x x x
Cycle Count
Displays count for open and close position since power supplied to controller.
C L E A R C Y C L
C O U N T S
> >
Clear Count
Clears cycle count. Press [ CONFIRM ►/◙] to select, then press again to confirm and clear counts.
R E S T O R E
D E F A U L T S
> >
Restore Defaults
Restores all settings to their default value. Press [CONFIRM ►/◙] to select, then press again to confirm and reset
to default values.
S O F T W A R E
V E R S I O N
x x . x x
Software and
Hardware
Version
Alternates between showing current software version number and current generation of circuit board. Gen 2 circuit
board will display if AC version or DC version.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
17 04/06/22
www.atcontrols.com IOM08139 REVISION 04
4. Setup and Calibration
4.1. Positioning Devices
4.1.1. Feedback Potentiometer (P7)
A feedback potentiometer connected to header (P7) is used to
detect the position of the actuator between the 0% to 100%
limits for modulating and proportional control applications. The
feedback potentiometer is typically coupled to the actuator
output indicator shaft by a set of gears.
To ensure the potentiometer remains within its limits through the
actuator operating range, the actuator should first be moved to
the halfway, or 50%, position. The feedback potentiometer is
then adjusted to the midpoint of its effective electrical range. For
example, a 1kΩ potentiometer should be adjusted to 500Ω. If
the potentiometer jumps from one end to another within the
actuator’s operation range, for example 0Ω to 1000Ω, the TMC4
may not be able to position correctly.
The potentiometer resistance is translated into a 12 bit count value of 0 to 4095 by the TMC4, and displayed in the
“Calibrate Close Pos” or “Calibrate Open Pos” settings in the POSITION CONFIG submenu. When the feedback
potentiometer is at its midpoint, the digital count value shown in either setting will be 2048, as this is the midpoint value
between the limits of 0 and 4095.
It is not critical to adjust the potentiometer to exactly 2048 at the 50% position but should be close so that the value will
not jump between the extremes of 0 and 4095 within the operating range. Centering the potentiometer approximately
between 1900-2200 should be sufficient for most applications.
The effective electrical angle of the potentiometer, actuator rotation angle, and ratio of the feedback gears determine the
maximum and minimum digital count values at the full open and full close positions, and the subsequent range that can be
expected. Typical digital count values are shown below for different gearing ratios or operating angles with the 50%
position set exactly to a value of 2048.
Gear Ratio / Actuator Rotation
Minimum
Maximum
Range
1:1 / 90° 1506 2590 1084
1:1 / 180° or 2:1 / 90° 964 3132 2168
1:1 / 270° or 3:1 / 90° 422 3674 3252
Note that the maximum and minimum values could be swapped depending on the rotation direction of the potentiometer
in relation to the rotation direction of the actuator. The TMC4 will correctly interpret the readings when positions are
calibrated. It is also not important to fall exactly at the values shown as long as the range of operation does not permit the
digital count value to jump from 0 to 4095, or vice versa. However, as the gear ratio or actuator rotation angle increases,
and the range increases, the allowance for deviation is reduced.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
18 04/06/22
www.atcontrols.com IOM08139 REVISION 04
4.1.2. Position Limit Switch (P5)
Position limit switches connected to header (P5) are used to detect the Open
and Close position of the actuator for two position and on/off applications.
These switches will stop the actuator at the limits and provide Open or Close
status indication to the TMC4 when “Position Type” is set for Limit Switch in
POSITION CONFIG submenu.
Typically, the auxiliary switches (AOLS and ACLS) in an actuator would be
used, and the motor travel stop switches (OLS and CLS) would be set just
outside of the operating range. The “Switch Action” setting in the POSITION
CONFIG submenu must be set according to if using normally open contact
(N.O. switch action) or a normally closed contact (N.C. switch action).
4.1.3. Stop/Torque Limit Switch (P9)
Motor travel stop or torque switches connected to header (P9) are used to stop the actuator regardless of set position
limits. This switch input should be used when the TMC4 motor outputs are not wired through limit switches, such as for
DC motors. This switch input provides no position indicator for the TMC4 since if an in-line switch stopped the motor from
some over torque situation, a false Open or Close status may be given.
When the motor outputs are wired through limit or torque switches, the switches should be connected through the N.C.
contact to open the motor circuit when activated. As such, the switches connected to the Stop/Torque input (P9) should
preferably also use a N.C. contact configuration. Ensure “Switch Action” setting in the POSITION CONFIG submenu is set
for N.C. action for the stop/torque switches.
AC
DC
Motor outputs connected to motor through switches.
Stop/Torque switch input not required.
Motor outputs connected directly to motor.
Stop/Torque switch input required.

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
19 04/06/22
www.atcontrols.com IOM08139 REVISION 04
4.2. Analog Control Calibration
For when operating as modulating actuator using some analog control input.
To change values or settings, press [CONFIRM ►/◙] so value or setting flashes, change setting with [PREVIOUS ▲] or
[NEXT ▼], press [CONFIRM ►/◙] to save setting of value. To escape from setting without saving, press [CANCEL ◄].
1) Select and calibrate input command signal.
a) Enter COMMAND CONFIG submenu.
b) Select desired command signal type in “Command Type” setting and confirm.
c) Connect command signal source to input terminals per appropriate wiring
diagram.
d) Enter “Calibrate Zero” setting, send 0% command signal and confirm.
e) Enter “Calibrate Span” setting, send 100% command signal and confirm.
Typical command signal values are given in 4.2.1 Command and Feedback Values.
C O M M A N D
C O N F I G :
> >
C O M M A N D
T Y P E :
x x x x
C A L I B R A T E
Z E R O
x x x x
C A L I B R A T E
S P A N
x x x x
2) Select and calibrate output feedback signal.
a) Enter FEEDBACK CONFIG submenu.
b) Select desired feedback signal type in “Feedback Type” setting and confirm.
c) Connect feedback signal monitor to output terminals per appropriate wiring
diagram.
d) Enter “Calibrate Zero” setting and adjust feedback signal using [PREVIOUS ▲]
or [NEXT ▼] until desired 0% feedback is achieved and confirm.
e) Enter “Calibrate Span” setting and adjust feedback signal using [PREVIOUS ▲]
or [NEXT ▼] until desired 100% feedback is achieved and confirm
Typical feedback signal values are given in 4.2.1 Command and Feedback Values.
F E E D B A C K
C O N F I G
> >
F E E D B A C K
T Y P E :
x x x x
C A L I B R A T E
Z E R O
x x x x
C A L I B R A T E
S P A N
x x x x
3) Set position limits.
a) Enter POSITION CONFIG submenu.
b) Set to “Potent” in “Position Type” setting.
c) Adjust feedback potentiometer to center at 50% position.
i) In “Calibrate Close Pos” or “Calibrate Open Pos”, press [PREVIOUS ▲] or
[NEXT ▼] to drive actuator to 50% position.
ii) Rotate feedback potentiometer until display reads between 1900-
2200, then
tighten gears.
d) In “Calibrate Close Pos”, press [PREVIOUS ▲] or [NEXT ▼] to drive actuator to
desired clockwise position and confirm.
e) In “Calibrate Open Pos”, press [PREVIOUS ▲] or [NEXT ▼] to drive actuator to
desired counterclockwise position and confirm.
P O S I T I O N
C O N F I G
> >
P O S I T I O N
T Y P E :
P o t e n t
C A L I B R A T E
C L O S E P O S
x x x x
C A L I B R A T E
O P E N P O S
x x x x
* Swap 0% and 100% signals for zero and span calibration in the above steps if setting up for reverse acting.
4.2.1. Command and Feedback Values
These are the approximate digital count values that will show according to command and feedback signals. Actual count
value may differ slightly. Values will also differ depending on revision of the display board. Check display board revision
level to confirm approximate values.
0mA
4mA
20mA
0V
1V
2V
5V
10V
Command
0 750 3740 0 380 760 1900 3800
Feedback
280 925 3550

TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
20 04/06/22
www.atcontrols.com IOM08139 REVISION 04
4.3. Two-Position Control Calibration
For when operating as two position on/off actuator.
To change values or settings, press [CONFIRM ►/◙] so value or setting flashes, change setting with [PREVIOUS ▲] or
[NEXT ▼], press [CONFIRM ►/◙] to save setting of value. To escape from setting without saving, press [CANCEL ◄].
1) Select On-Off input command type.
a) Enter COMMAND CONFIG submenu.
b) Select “On-OFF” command in “Command Type” setting.
C O M M A N D
C O N F I G :
> >
C O M M A N D
T Y P E :
O N - O F F
2) Set position limits.
a) Enter POSITION CONFIG submenu.
b) Set to “Limit SW” in “Position Type” setting.
c) Set position limit cams in the actuator.
It is recommended to use the Manual Operation screen to manually drive the actuator
when setting the limit switch cams since this will display “Open” or “Close” status when
switches are connected to header (P5). However, it is possible to drive the actuator from
the “Calibrate Close Pos” or “Calibrate Open Pos” settings, but this will not show position
status. For either method, press [PREVIOUS ▲] or [NEXT ▼] to manually drive the
actuator.
P O S I T I O N
C O N F I G
> >
P O S I T I O N
T Y P E :
L i m i t S W
4.4. Communication Bus Control Calibration
For when using one of the optional communication bus add-on modules.
To change values or settings, press [CONFIRM ►/◙] so value or setting flashes, change setting with [PREVIOUS ▲] or
[NEXT ▼], press [CONFIRM ►/◙] to save setting of value. To escape from setting without saving, press [CANCEL ◄].
1) Select communication input command type.
a) Enter COMMAND CONFIG submenu.
b) Select “Comms” command in “Command Type” setting.
C O M M A N D
C O N F I G :
> >
C O M M A N D
T Y P E :
C o m m s
2) Configure communication setting.
a) Enter COMMS CONFIG submenu.
b) Select communication protocol in “Communication Type” setting.
c) Set address and other communication parameters in appropriate setting within
the COMMS CONFIG submenu as needed.
C O M M S
C O N F I G
>>
C O M M S
T Y P E :
xxxx
3) Set position limits if using Two Position Control.
a) Enter POSITION CONFIG submenu.
b) Follow instructions for setting position limits per 4.3Two-Position Control
Calibration.
P O S I T I O N
C O N F I G
> >
P O S I T I O N
T Y P E :
L i m i t S W
4) Set position limits if using Proportional Control.
a) Enter POSITION CONFIG submenu.
b) Set to “Potent” in “Position Type” setting
c) Follow instructions for setting position limits per 4.2 Analog Control Calibration.
P O S I T I O N
C O N F I G
> >
P O S I T I O N
T Y P E :
P o t e n t
C A L I B R A T E
C L O S E P O S
x x x x
C A L I B R A T E
O P E N P O S
x x x x
Table of contents
Other A-T Controls Control Unit manuals
Popular Control Unit manuals by other brands

CD Automation
CD Automation Revo C 3Ph 60A user manual

GST
GST DI-9300E quick start guide

Topway
Topway LM8053-1 user manual

Samson
Samson 2335 Mounting and operating instructions

IFM Electronic
IFM Electronic Ecomat100 CR1083 PDM360 NG installation instructions

Siemens
Siemens SIMOCODE pro Programming and operating manual