
3711 Iowa Street Phone 320.763.6043
Alexandria, MN 56308 www.aagard.com
Page 2 of 4 ZSE40 Vacuum Switch -ISE40A Pressure Switch - PF2A Flow Switch Setup.doc
ZSE40A Vacuum Switch Setup
1. Enter Function Selection Mode – Press and hold (> 2 sec.) the Skey until the display
shows F 0
a. If LoC is displayed, hold the S key for > 5, press the Down key once, then press
Sbutton once to enter the setting.
2. Reset the unit to default settings – From F 0 press the Down key once to navigate to
F99; Press the S key, then the Up arrow to toggle to on; Hold the Skey and the Down
arrow key for > 5 seconds.
3. From F99 press the UP key once to navigate to F 0 and press the S key once to display
Uni. Press the UP key once to set display to inH.
4. Press the Skey once to return to F 0.
5. From F 0 press the UP key once to navigate to F 1 and press the S key 3 times so the
display reads P_1. Verify that the display reads -15.0 (or the setting stated on the prints;
-18.0 for the system vacuum switch). Press the S key 1 more time so the display reads
H_1. Using the UP and Down keys set display to 3.0.
6. Press the Skey 2 times to return to F 1.
7. Setting F 2 (P_2) is not necessary for Aagard’s standard application.
8. Now return to the main display by pressing the Skey for > 2 seconds. This should bring
you to a screen with a low number on it for the current/live reading.
System vacuum switch settings – P_1 = -18.0
Secondary vacuum switch settings – P_1 = -15.0
By setting these switches up in this manner the system vacuum switch will provide an output when
we get to 18.0 InHg and it will not loose its signal unless we drop below 15.0 InHg. The secondary
vacuum switch set points will be 15.0 & 12.0 respectively.
These switches are sent with a PSI label affixed to the upper right corner of the display (The ZSE
model can sense both vacuum & pressure). There are extra labels that are shipped with each
switch. Be sure to remove the PSI label and replace it with the in/Hg when this
procedure is completed.