www.abelko.se
User name: cong
Password: ef56
2. Go to the menu Communication and Network, and set the IP
address and netmask, in order to congure the settings for the port
marked Ethernet.
You can also use DHCP, the unit will then automatically get network
settings. After a while, you can see which IP address it received. You
can use this IP address to access the device from a PC, connected to the
same network.
HTTPS
The rst time that you log in to an Ultra, you will be warned that the
connection is not private, secure, or similar. This is because the system uses
HTTPS for a secure and encrypted connection. The security is guaranteed by a
certicate that is issued for a specic address. Since the address is adjustable,
there is only a self-signed certicate for the unit.
You need to accept and add this exception. The procedure diers depending on
which browser you are currently using. The communication is still encrypted, so
no-one can see, for example, which passwords are being used.
Graphical programming
Graphical programming is available as an installable program. Download it at
www.abelko.se.
There is also a link to the program in your units user interface under
Conguration and Graphical programming.
Analog outputs
There are eight analog outputs for 0-10 V, marked
AO.
The gure to the rigth is an example on how you
can connect an AC-powered valve controller.
Digital outputs
There are eight digital outputs marked DO. These are open drain outputs with
breaking capacity 0,5 A and 24 VDC at resistive load.
Temperature sensor inputs
There are eight inputs for resistive temperature sensors marked with T. They
have a measurement range 800 till 1580 Ohm and works for example with
PT1000 sensors (approximately -50ºC till 150ºC) and Ni1000 sensors.