Accutrol AccuValve AVT3000 User manual

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification
Airflow Control Valve
Patented: U.S. 6,991,177 & 7,543,759
Manufactured by: Accutrol Representative:
AVT3000 MANUAL REV B - 2018-06-26
21 Commerce Drive
Danbury, CT 06810 USA
WWW.ACCUTROLLLC.COM

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page ii
LIMITED WARRANTY
Accutrol LLC, having its principal place of business at 21 Commerce Drive, Danbury, CT USA
("Manufacturer") warrants its AccuValve®, Model AVT3000/H-AVT3000 product (the
"Products") as follows:
1. Limited Warranty.
Manufacturer warrants that the Products sold hereunder will be free from defects in material
and workmanship for a period of sixty (60) months from the date of purchase. If the Products
do not conform to this Limited Warranty during the warranty period (as herein above
specified), Buyer shall notify Manufacturer in writing of the claimed defects and demonstrate to
Manufacturer’s satisfaction that said defects are covered by this Limited Warranty. If the
defects are properly reported to Manufacturer within the warranty period, and the defects are
of such type and nature as to be covered by this warranty, Manufacturer shall, at its own
expense, furnish, replacement Products or, at Manufacturer's option, replacement parts or
services for the defective Products. Shipping and installation of the replacement Products or
replacement parts shall be at Buyer's expense.
2. Other Limits.
THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT
NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. Manufacturer does not warrant against damages or defects arising out
of improper or abnormal use or handling of the Products; against defects or damages arising
from improper installation (where installation is by persons other than Manufacturer), against
defects in products or components not manufactured by Manufacturer, or against damages
resulting from such non-Manufacturer made products or components. Manufacturer passes on
to Buyer the warranty it received (if any) from the maker thereof of such non-Manufacturer
made products or components. This warranty also does not apply to Products upon which
repairs have been affected or attempted by persons other than Manufacturer or pursuant to
written authorization by Manufacturer. This warranty also does not apply to any product
provided by the Buyer and mounted by the Manufacturer to Products.
3. Exclusive Obligation.
THIS WARRANTY IS EXCLUSIVE. The sole and exclusive obligation of Manufacturer shall be to
repair or replace the defective Products in the manner and for the period provided above.
Manufacturer shall not have any other obligation with respect to the Products or any part
thereof, whether based on contract, tort, and strict liability or otherwise. Under no
circumstances, whether based on this Limited Warranty or otherwise, shall Manufacturer be
liable for incidental, special, or consequential damages.
4. Other Statements.
Manufacturer's employees or representatives' ORAL OR OTHER WRITTEN STATEMENTS DO NOT
CONSTITUTE WARRANTIES, shall not be relied upon by Buyer, and are not a part of the contract
for sale or this limited warranty.
5. Entire Obligation.
This Limited Warranty states the entire obligation of Manufacturer with respect to the
Products. If any part of this Limited Warranty is determined to be void or illegal, the remainder
shall remain in full force and effect.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page iii
TABLE OF CONTENTS
LIMITED WARRANTY................................................................................................................ii
TABLE OF CONTENTS...............................................................................................................iii
SECTION 1 - INTRODUCTION................................................................................................... 4
SECTION 2 - SPECIFICATIONS ................................................................................................. 6
SECTION 3 –PHYSICAL DIMENSIONS & WEIGHTS .......................................................... 11
SECTION 4 - INSTALLATION.................................................................................................. 12
SECTION 5 –WIRING................................................................................................................ 15
SECTION 6 –ACCUVALVE INSIGHT USER INTERFACE SOFTWARE............................ 16
SECTION 7 –OPTIONAL BACNET MS/TP............................................................................. 25
SECTION 8 –MAINTENANCE ................................................................................................. 27
APPENDIX –ACTUATOR DRAWINGS ................................................................................... A

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 4
SECTION 1 - INTRODUCTION
The AVT3000 product family is intended for applications that require accurate and repeatable
airflow measurement with high turn-down with precise closed-loop control using an external PI
controller. The AVT3000 incorporates a state-of-the-art vortex shedding digital transmitter
with an intuitive user-interface software known as the AccuValve Insight.
Theory of Operation (Reference the Diagram Below)
The AccuValve®divides the airflow into two equal chambers using an airfoil shaped
compression section. Each chamber is comprised of a vortex shedding airflow sensor, a
modulating control surface and a static regain section. As air enters the chambers it accelerates
and compresses, creating an ideal location for measuring airflow velocity. The vortex shedding
airflow sensors provide a highly repeatable digital pulse-train with a frequency that is directly
proportional to the air flow velocity in each chamber of the AccuValve®.
The digital pulses generated by each vortex shedding sensor are used to calculate the total
airflow volume flowing through the AccuValve®. The transmitter provides a software-
selectable analog output signal that is directly proportional to the total airflow volume
measurement. The airflow volume can also be provided directly to the building management
system’s BACnet MS/TP network by ordering the optional BACnet MS/TP communications
module.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 5
1.1 Model Code
H-
AVT3
-
-
APPLICATION (Ref. Note 1)
No Prefix = High Speed VAV Lab Applications
H - Prefix = Healthcare/Non VAV Lab Applications
VALVE SHAPE
1 = Round
2 = Rectangular
VALVE HOUSING MATERIAL
2= 304 Stainless Steel, 20 Ga.
3= 316L Stainless Steel, 20 Ga.
4 = Aluminum, 16 Ga.
5= PFA Coated 304SS, 20 Ga (Sizes; 08,10,12 & 14 only)
6= High Temp. 304SS, 20 Ga
ACTUATOR TYPE
2 = Fail Last Position (FLP), 0-10v, PN 20-0008
3 = Fail Last Position (FLP), 2-10v, PN 20-0009
4 = Fail Open/Closed (FSP), 0-10v, PN 20-0010
5= Fail Open/Closed (FSP), 2-10v, PN 20-0011
7= Fail Last Position (FLP), 2-10v, PN 20-0042 (Ref. Note 1)
VALVE SIZE
06 = 6" Diameter Round
08 = 8" Diameter Round
10 = 10" Diameter Round
12 = 12" Diameter Round
14 = 14" Diameter Round
18 = 12" h x 18" w Rectangular
24 = 12" h x 24" w Rectangular
36 = 12" h x 36" w Rectangular
48 = 12" h x 48" w Rectangular
OPTIONS
BLANK = No Options
A= AccuNet
B= BACnet
F= Flanges (Flange does not have predrilled holes)
I = Insulation
S = Tight Shut-off (All 6” valves have blade seals, therefore –S option is not available on 06)
Note 1: Valve Models with H- Prefix are only provided with Actuator Type “7”.
1.2 Valve Types
Round AccuValve
Model AVT3100-xx
Rectangular AccuValve
Model AVT3200-18, -24
Rectangular AccuValve
Model AVT5200-36, -48

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 6
SECTION 2 - SPECIFICATIONS
PERFORMANCE
Accuracy
+/- 5% of reading or 5 CFM, whichever is greater
Speed of Response
<1 second
Shut-off Leakage Rate
@ 3”wc valve DP
Standard Round Valves (Model AVT31xx-xx) <1.5% FS max
Round Valves with Blade Seals (Model AVT31xx-xx-S) <0.5% FS max
Standard Rectangular Valves (Model AVT32xx-xx) <1.5% FS max
Rectangular Valves with Blade Seals (Model AVT32xx-xx-S) <1% FS max
Max Operating Pressure
3”wc Differential Pressure Across Valve
Min Operating Pressure
Reference Section 2.1
Airflow Range
Reference Section 2.1
Failure Mode
Fail Last Position or Fail Open/Closed (selectable by model code)
ENVIRONMENTAL
Temperature
Airstream: -20 to 165 deg. F for all Standard Valve Models
-20 to 375 deg. F for the High Temp SS Valve Models
Ambient: -20 to 125 deg. F
Storage: -40 to 165 deg. F
Humidity
0 to 90% non-condensing
TRANSMITTER ELECTRICAL
Power Supply
24 VAC +/- 20% 50/60 Hz, 4 VA max (8.5 VA max with remote display)
24 VDC +/- 10% 1.5 W max (3.5 W max with remote display)
Output Signal
0-20mA, 4-20mA, 0-10V, 2-10V, 0-5V, or 1-5V (Software Config.)
12-bit Resolution
Capable of driving 1K-ohm load
Configuration Port
USB 2.0, Isolated, Micro B Connector
Power Source Switch
Operational Position: Draws power from 24V input terminal block
Nonoperational Position: Draws power from 5V USB port (Use for configuration only)
BACnet MS/TP (Optional)
EIA 485 2-wire BACnet MS/TP, Galvanically Isolated
Data Rates 9600, 19200, 38400, 57600, 76800 and 115200
1/8 Unit Load Receiver Input Impedance
Network bias and EOL Termination not provided within the Transmitter
Remote Display (Sold Separately)
LCD, 2 lines x 8 characters with white LED backlight
Includes USB Configuration Port and Factory Cable
Terminal Plugs
3-position, vertical pluggable, screw on top, wire size 12-30 AWG
ACTUATOR ELECTRICAL
Reference Appendix A
MATERIALS OF CONSTRUCTION
Reference Table 1

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 7
TABLE 1, MATERIALS OF CONSTRUCTION
Model Code Material Designator
(2) 304SS
(3) 316SS
(4) Aluminum
(5) PFA Coated 304SS
(6) High Temp 304SS
Item Description1
8”,10”,12” & 14” Sizes Only
Housing
304 Stainless Steel
316L Stainless Steel
Al. Alloy 5052-H32
PFA Coated 304SS
304 Stainless Steel
Compression Section
304 Stainless Steel
316L Stainless Steel
Al. Alloy 5052-H32
PFA Coated 304SS
304 Stainless Steel
Static Regain Section
304 Stainless Steel
316L Stainless Steel
Al. Alloy 5052-H32
PFA Coated 304SS
304 Stainless Steel
End Plate
304 Stainless Steel
316L Stainless Steel
Galvanized Steel
PFA Coated 304SS
304 Stainless Steel
Control Surfaces
304 Stainless Steel
316L Stainless Steel
Galvanized Steel
PFA Coated 304SS
304 Stainless Steel
Shafts
316L Stainless Steel
316L Stainless Steel
316L Stainless Steel
PFA Coated 316L SS
316L Stainless Steel
Shaft Bearings
Teflon®
Teflon®
Teflon®
Teflon®
Teflon
Vortex Sensors
Polycarbonate, UL94-
VO
Polycarbonate, UL94-
VO
Polycarbonate, UL94-
VO
PVDF
303 Stainless Steel
Sensor Tubing
Polyurethane,
Ether-based
Polyurethane,
Ether-based
Polyurethane,
Ether-based
Viton Rubber
Viton Rubber
Compression Seals
Viton Rubber
Viton Rubber
EPDM Rubber
Viton Rubber
Viton Rubber
Machine Screws
304 Stainless Steel
316 Stainless Steel
304 Stainless Steel
PFA Coated SS
304 Stainless Steel
Rivets
304SS
316SS
304SS
PFA Coated 304 SS
304 SS
Blade Seals (optional)
Viton Rubber
Viton Rubber
EPDM Rubber
NA
Viton Rubber
Note 1: Above list includes only items internal to the valve which are exposed to the airstream.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 8
2.1 Operating Range
The operating range of each AccuValve is provided below along with a characteristic curve
showing the relationship between the minimum operating pressure and maximum airflow
volume as tested in accordance with ANSI/ASHRAE STD 130.
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
25 50 75 100 125 150 175 200 225 250 275 300 325
Valve DP ("wc)
Max Airflow (CFM)
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
100 150 200 250 300 350 400 450 500 550 600 650 700 750 800
Valve DP ("wc)
Max Airflow (CFM)
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
Valve DP ("wc)
Max Airflow (CFM)
6” AccuValve
Operating Range: 0-315 CFM
Min. Measurement: 30 CFM
8” AccuValve
Operating Range: 0-800 CFM
Min. Measurement: 80 CFM
10” AccuValve
Operating Range: 0-1300 CFM
Min. Measurement: 120 CFM

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 9
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
200 400 600 800 1000 1200 1400 1600 1800
Valve DP ("wc)
Max Airflow (CFM)
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
300 600 900 1200 1500 1800 2100 2400 2700
Valve DP ("wc)
Max Airflow (CFM)
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
400 800 1200 1600 2000 2400 2800 3200
Valve DP ("wc)
Airflow (CFM)
12” AccuValve
Operating Range: 0-1790 CFM
Min. Measurement: 180 CFM
14” AccuValve
Operating Range: 0-2750 CFM
Min. Measurement: 250 CFM
12x18” AccuValve
Operating Range: 0-3200 CFM
Min. Measurement: 260 CFM

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 10
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
500 1000 1500 2000 2500 3000 3500 4000
Valve DP ("wc)
Max Airflow (CFM)
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
800 1600 2400 3200 4000 4800 5600 6400
Valve DP ("wc)
Max Airflow (CFM)
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
1000 2000 3000 4000 5000 6000 7000 8000
Valve DP ("wc)
Max Airflow (CFM)
12x24” AccuValve
Operating Range: 0-4000 CFM
Min. Measurement: 350 CFM
12x36” AccuValve
Operating Range: 0-6400 CFM
Min. Measurement: 520 CFM
12x48” AccuValve
Operating Range: 0-8000 CFM
Min. Measurement: 700 CFM

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 11
SECTION 3 –PHYSICAL DIMENSIONS & WEIGHTS
3.1 Round Valve Sizes
3.2 Rectangular Valve Sizes
Note: All dimensions are to the “outside” and have a tolerance of +/- .062” (1.6mm).
Valve Model
Dimensions
Weight
“D”
“L”
“H”
Stainless Steel
Aluminum
in.
mm
in.
mm
in.
mm
Lbs.
kg
Lbs.
kg
AVT3100-06
5.88
149
22
559
10
254
13
5.9
9
4.1
AVT3100-08
7.88
200
24
610
13
381
16
7.3
12
5.4
AVT3100-10
9.88
250
24
610
15
432
20
9.1
14
6.4
AVT3100-12
11.88
300
27
686
17
483
26
11.8
16
7.3
AVT3100-14
13.88
350
30
762
19
533
30
13.6
20
9.1
Valve Model
Valve Width “W”
Weight
Ref Diagram
Stainless Steel
Aluminum
in.
mm
Lbs.
kg
Lbs.
kg
AVT3200-18
17.88
454
43
19.5
26
11.8
AVT3200-24
23.88
607
49
22.2
29
13.2
AVT3200-36
35.88
911
97
44.0
59
26.8
AVT3200-48
47.88
1216
109
49.4
69
31.3
“H”
12”
(305mm)
“D”
“L”
19”
483mm
30”
762mm
“W”
11.88”
302mm

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 12
SECTION 4 - INSTALLATION
Read all instructions and review the installation diagrams provided on the following pages prior
to beginning installation. Also reference the product submittal drawings before proceeding.
WARNING: Wear eye protection, cut-resistant gloves, and clothing suitable for working
with sheet metal. Failure to do so may result in personal injury.
1. Verify the tag number located on the valve label matches the HVAC schedule.
2. Locate the duct section which the valve is servicing and select a suitable mounting
location for the valve.
NOTE: the AccuValve does not require straight-run inlet conditions to operate properly,
however it’s always best to follow HVAC Best Practices for Commercial Buildings during
installation which includes locating the valve away from transitions and bends to
minimize impact on system static pressure. Also, be sure to select a location that will
provide a minimum clearance of 14” (356mm) unobstructed access to the transmitter,
actuator and valve access cover.
3. Provide an opening in the duct section sized appropriately for the valve being installed.
NOTE: A slip-fit valve will require an opening approximately 2” smaller than the valve
length and a flanged valve will require an opening the same as the valve length. For
valve dimensions, reference Section 4.
4. Install duct hangers within 12” (305mm) from each end of the valve connections.
Reference Section 4 for valve weights.
WARNING:Use duct hangers and hardware designed to support the total load of the
valve and associated duct sections. Failure to do so may result in serious personal injury
or death.
5. Install the valve into the duct in accordance with the airflow direction label located on
the valve. Position the valve for easy access to the control module side. Since the
AccuValve is not position sensitive, it can be installed in any plane or rotational axis
without having impact on the performance.
NOTE: Screws, nuts, fasteners, duct sealant, hangers, companion flanges and gaskets
are NOT provided by Accutrol.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 13
4.1 Round Valve Installation Diagrams
Standard Slip-fit Valve Secured to Duct with Tek Screws. NOT ACCEPTABLE FOR PFA COATED
VALVE.
Standard Slip-fit Valve Secured to Duct with Draw Band Clamps
Flanged Valve “Option –F” Secured to Duct with Companion Flanges and Hardware
INLET
DISCHARGE
Locate duct supports within 12” of each end of the valve.
Locate duct supports within 12” of each end of the valve.
DISCHARGE
INLET
4. Secure valve to duct using tek-screws.
2. Position valve to provide
unobstructed access to the
control module, actuator
and access panel.
3. Install gaskets and/or
duct sealant between
the valve flanges and
companion flanges.
1. Slip the draw band clamps over each end of the duct.
2. Slip the inlet end of the valve into the duct far enough to allow the valve
to be lifted into the duct opening.
3. Slip the discharge end of the
valve into the duct engaging valve
into duct 1” at each end.
4. Position valve to provide
unobstructed access to the
control module, actuator and
access panel.
6. Secure both ends of valve to the duct using draw band clamps.
2. Slip the discharge end of the
valve into the duct engaging
valve into duct 1” at each end.
1. Slip the inlet end of valve into the duct far enough to allow the valve to be lifted
into the duct opening.
4. Apply duct sealant and secure valve to duct at both ends using tek-screws.
3. Position valve to provide
unobstructed access to the
control module, actuator and
access panel.
Locate duct supports within
12” of each end of the valve.
DISCHARGE
INLET
Air Flow
Direction
1. Slip the companion flanges over each end of the duct and install to duct as required.
5. For clean air applications,
apply UL181 compliant foil tape
over the valve/duct seams.
For corrosive exhaust applications, apply PTFE tape (available from Accutrol)
over the valve/duct seams.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 14
4.2 Rectangular Valve Installation Diagrams
Valve Sizes -18 and -24
Valve Sizes -36 and -48
Flanged Valve “Option –F”
4. Slip the discharge end of the valve
into the duct engaging valve into duct
1” at each end.
3. Slip the inlet end of valve into the
duct far enough to allow the valve to
be lifted into the duct opening.
5. Secure both ends of valve to duct
using tek screws and duct sealant.
Locate duct supports within 12” of each end of the valve.
14” (356mm) Min. Clearance for Access to this Side
INLET
DISCHARGE
Air Flow Direction
1. Verify the opening in the duct is properly sized for the valve and installation method being used. Also verify
both ends of the duct where the valve is to be attached are true and square before attempting to install valve.
If the duct ends are not square and true, do not attempt to install valve as it will not operate properly.
2. Lift valve into position to provide
unobstructed access to the control
module, actuator and access panel.
The 36” and 48” wide valves are provided with integral mounting struts to help support the weight of the valve.
In addition to following the installation instructions above, each end of the strut shall be secured to the building
structure using properly rated hardware and methods in accordance with local building codes.
Mounting
Struts
Support Here
3. Install gaskets and/or duct
sealant between the valve flanges
and companion flanges.
1. Install companion flanges (provided by others) over each end of the duct.
14” (356mm) Min. Clearance for Access to this Side
Locate duct supports within
12” of each end of valve
INLET
DISCHARGE
2. Lift the valve into position to
provide unobstructed access to
the control module, actuator
and access panel.
NOTE: It’s acceptable to fabricate and install flanges onto the AccuValve and ductwork on location. If
flanges are fabricated on site, it’s still important to verify both ends of duct are true and square prior to
and after installing flanges, otherwise the valve will not operate properly.
4. Secure both ends using tek-screws.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 15
SECTION 5 –WIRING
5.1 AVT3000 Transmitter Description
5.2 Wiring Instructions
1. Remove cover and route cables through strain relief fitting into enclosure.
2. Remove terminal block plug(s) and connect wires to the appropriate terminals.
3. Secure terminal screws and reinstall plug(s).
4. Insert the ratcheting strain relief over cable(s) and push down until snug.
5. Reinstall cover and secure thumb screw.
5.3 Transmitter Wiring Diagram: The figure below includes the optional BACnet and AccuNet
communication modules and the AFM3000 Monitor which is sold separately. For more details
regarding the AccuNet wiring, reference the Accutrol AccuNet Manual.
24 vAC
24 vDC
or
Analog Input
BMS Controller /
Signal Receiving
Device
+
Common
Power Source
BACnet MSTP Bus
AccuNet
Bus
AVT3000 Transmitter
AFM3000
Remote
Monitor
Factory
Cable
Clear Tubing
Connected to Sen 1
Black Tubing
Connected to Sen 2
CAUTION: Maintain polarity if power source is used for multiple devices, otherwise
equipment may be damaged.
Captive Thumb Screw for Removing/Securing Cover
Cable from Optional Monitor
Cable Entry
with Ratcheting
Strain Relief
Alternate
Cable Entry
NOTE: If a direct conduit connection is
required, remove strain relief fitting and
replace with a .875 (22mm) conduit
fitting. (Provided by Others)
AFM3000 Direct Connection to RJ-45 Connector
Cover Tab Slot

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 16
SECTION 6 –ACCUVALVE INSIGHT USER INTERFACE SOFTWARE
Using a PC you can communicate directly with the AVT transmitter to configure the analog
output or locally monitor the transmitter performance. All that’s required is a Windows PC or
Tablet with a USB Port, a USB Cable and the AccuValve Insight Software.
6.1 Minimum Requirements for PC
•PC or Tablet with Windows Version 10
•USB 2.0 Port
•Screen Resolution 1280 x 768 or greater suggested
•USB Cable Type A/MICRO B
6.2 Installing the AccuValve Insight Software
Before starting the following process, close any programs running on the computer.
1. Download the AccuValve Insight Software from http://www.accutrolllc.com.
2. Install software by running the setup application. The setup wizard will guide you through
the software installation process. Follow screen prompts and select the appropriate
responses to proceed with installation.
6.3 AccuValve Insight Software Product Registration
Once the AccuValve Insight Software has been installed, you will need to register the product
and obtain a valid software key from the factory before you can use the software.
Note: When selecting the Register Product Key button, the information provided will be
copied to the clipboard and Insight will attempt to generate an email using your default
Email Program. If a default Email program has not been configured you will need to
paste the clipboard information into the body of the email. The Installation Serial
Number is unique to the computer which it was installed on. Therefore, the Registration
Key will only function on this one computer. If you require the software to be installed on
more than one computer, a request for each computer must be generated separately.
1. Double click on the desktop shortcut created during the installation or go to the Start Menu
and select Programs>AccuValve Insight.
2. Fill in the required information on the Product Registration Form and click on the “Request
Product Key” button to generate the email key request to the factory.
3. Once the key request email has been received by the factory, a unique Product Key will be
generated and sent to the email address provided on the Registration Form.
4. After receiving the email from the factory, copy the product key and paste it into the field
provided at the bottom of the form then click on the “Register Product Key” button.
5. You will now be able to use the AccuValve Insight Software on this computer.
If you have any problems completing the process outlined above, contact Accutrol Customer
Service at 203-445-9991 and ask for technical support.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 17
6.5 Connecting the PC to the AVT Transmitter
For connecting directly to the AVT3000 Transmitter, remove the cover from the transmitter
and connect the USB cable into the Micro USB connector located on the transmitter per the
figure below.
AVT ACCUVALVE
PC WITH AVC
INSIGHT SOFTWARE
USB CABLE WITH
MICRO TYPE B
Power Source Switch
The AVT3000 Transmitter pcb has a Power Source Switch which should always be in the
“Operational Position” for the transmitter to function normally. The “Nonoperational
Position” is provided so the transmitter can be programmed or configured when there is no
24v power source available. This is a convenient feature for configuring the BACnet
parameters or the transmitter’s analog output prior to having the 24v power source wired.
Operational Position
Nonoperational Position
24v power is provided to the transmitter
through the 24v connector. This is the
normal position for the Power Source
Switch.
5vdc power is provided to the
transmitter through the computer
connected to the USB Configuration Port.
This is a temporary position only.
Caution:The Power Source Switch must be returned to the Operational Position after
completing the configuration otherwise the transmitter will not function.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 18
For connecting to the AVT3000 through the AFM3000 Monitor (sold separately); remove
the rubber dust plug protecting the AFM3000 USB port and insert the USB cable into the
Micro USB connector located on the AFM3000. Be sure to reinstall the rubber dust plug on
the AFM3000 when finished.
AFM3000
PC with
AccuValve
Insight
Software
Factory
Supplied Cable
AVT3000
USB cable with Micro B
Note:The Power Source Switch on the AVT3000 transmitter pcb must be in the
Operational Position when the AFM3000 Monitor is connected. The Nonoperational
Position shall not be used when the AFM3000 is connected to the AVT3000.

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 19
6.6 AccuValve Insight Software
To open the AccuValve Insight application double click on the desktop shortcut or go to the
Start Menu and select Programs > AccuValve Insight.
Select the appropriate COM port then select Connect.
Note: if you’re not sure which COM port your computer is using for the AccuValve
connection, unplug the AVT transmitter from the USB port and view the drop-down list
noting the COM ports that are included in the list. Now plug the AVT into USB port and
view the drop-down list. The new COM port added to the list is the AVT COM port.
6.6.1 Insight Dashboard
The Insight Dashboard is the primary screen for accessing the transmitter parameters and
viewing the real-time performance of the AVT3000 valve. The Dashboard provides an intuitive
graphical user interface that is easy to understand while providing easy access to the field-
configurable parameters. The diagram below identifies the different objects of the dashboard
with brief descriptions of each on the following pages.
Airflow Volume Gauge
AccuNet Totalizer Gauge
Analog Output Configuration
Connection Status Indicators
Valve Airflow Gauge
Dashboard Menu
Sensor Frequency Signals
USB Com Status
Valve ID
BACnet MAC Address
Dashboard Task Bar

Installation & Operation Manual - Model AVT3000 & H-AVT3000
Contents of this Manual are Subject to Change Without Notification Page 20
6.6.2 Airflow Volume Gauge
The Airflow Volume Gauge provides the real-time measurement of the volumetric air flowing
through the AccuValve. The range of this gauge is determined by the size of the valve and it
cannot be reset in the field.
6.6.5 Valve Airflow Gauge
The Valve Airflow Volume Gauge provides the real-time measurement of the volumetric air
flowing through the AccuValve. The range of this gauge can be configured to match the full-
scale range of the Analog Output or it can be configured with a full-scale range that is
independent of the Analog Output. To change the full-scale range, click on the gauge face.
6.6.5 AccuNet Totalizer Gauge (Only available when the AccuNet Board is Installed)
The AccuNet Gauge displays the sum of the airflows reported by all the devices connected to
the AccuNet network. This gauge can only be activated by configuring this device as the
Totalizer on the local AccuNet network. The full-scale range of this gauge can be configured to
match the full-scale range of the Analog Output or it can be configured with a full-scale range
that is independent of the Analog Output. To change the full-scale range, click on the gauge
face.
This manual suits for next models
5
Table of contents
Other Accutrol Control Unit manuals

Accutrol
Accutrol AccuValve AV3000 User manual

Accutrol
Accutrol AccuValve AVT4000 Series User manual

Accutrol
Accutrol AccuValve AVT6000 User manual

Accutrol
Accutrol AVC5000 User manual

Accutrol
Accutrol AccuValve AVR6000 User manual

Accutrol
Accutrol ACCUVALVE AVC6000 User manual

Accutrol
Accutrol AccuValve AVC4000 User manual