ACDC PAPILLON250 User manual

ARTICULATED ARM OPENERS
FOR RESIDENTIAL
USER MANUAL
24V DC GEAR MOTOR
PAPILLON250 User Manual

INDEX
1.2 Installation
1.2.1 Standard Installation
1.2.2 Dimension Chart
1.2.3 Components of Installation
1.2.4 Installation of Articulated Arm Opener
1.2.5 Emergency Release
1.2.6 WIFI Device
1.2.7 Photocells
1.2.8 Power Supply Connections
2.1 Wiring Connection
2.1.1 Master Motor is installed at right side
2.1.2 Master Motor is installed at left side
3. Get Started
3.1 Step 1: Remote Memorizing
3.1.1 Memorizing
3.2 LED Indication
3.3 Deleting memory of single command
3.3.1 Deleting all memory of all remotes
3.3.2 Step 2: System Learning
3.4 Gate-moving Logic
3.5 Checking the Gate Movement
4. Function Setting
4.1 Function of The LED Display
5. Parameter Modification
5.1 Parameter Learning
5.2 Parameter
5.3 Photocell Adjustment
6. Technical Features
6.1 Dimension
6.2 Technical Feature
7. Maintenance
1
1
1
2
2
3
3
4
4
5
6
7
8
8
8
9
9
9
10
11
11
11
11
12
12
12
14
15
15
15
16
1.1 Warnings
WARNING :
This user manual is only for qualified technicians who is specialized in installations and automations.
(1) All installations, electrical connections, adjustments and testing must be performed only after
reading and understanding of all instructions carefully.
(2) Before carrying out any installation or maintenance operation, disconnect the electrical power
supply by turning off the magneto thermic switch connected upstream and apply the hazard area
notice required by applicable regulations.
(3) Make sure the existing structure is up to standard in terms of strength and stability.
(4) When necessary, connect the motorized gate to reliable earth system during electricity connection phase.
(5) Installation requires qualified personnel with mechanical and electrical skills.
(6) Keep the automatic controls (remote, push bottom, key selectors…etc) being placed properly
and away from children.
(7) For replace or repair of the motorized system, only original parts must be applied. Any damage
caused by inadequate parts and methods will not be claimed to motor manufacturer.
(8) Never operate the drive if you have any suspect with what it might be faulty or damage to the system.
(9) The motors are exclusively designed for the gate opening and closing application, any other
usage is deemed inappropriate. The manufacture should not be liable for any damage resulting
from the improper use. Improper usage should void all warranty, and the user accepts sole
responsibility for any risks thereby may accrue.
(10) The system may only be operated in proper working order. Always follow the standard procedures
by following the instructions in this installation and operating manual.
(11) Only command the remote when you have a full view of the gate.
Please keep this installation manual for future reference.

ARTICULATED ARM OPENERS USER MANUAL
1.2.2 Dimension Chart
1
1.2 Installation
2x1.5 mm2
4x0.5 mm2
TX - 4x0.5 mm2
RX - 4x0.5 mm2
2x1.5 mm2
2x1.5 mm2
44
2
1
5
1. 24V DC blinker with integrated antenna
2. Push Button
3. Photocells
4. 24V DC articulated arm opener
5. TM3 Transmitter
Please comply with the measures shown on the chart for
proper installation. If necessary, please adjust the gate
structure to the best operation.
Before starting the installation, please make sure that the
gate moves smoothly and that :
1) Hinges are properly positioned and greased.
2) No any obstacle in the moving area.
3) No frictions between two leaf gates and on the
ground while moving.
4) Installation reference: to open the gate with 90 degree,
please refer the data table below:
A: Distance between the gate hinge and the wall bracket.
B: Distance between the gate hinge and the motor side.
C: Distance between the gate hinge and the fixing point of the arm.
To open 90 degree.
Inward Opening
Outward Opening
A
C
B
To open 90 degree.
A
C
B
C
50
100
150
200
250
300
unit: mm
A
B
50
625
615
600
585
565
540
100
575
565
550
535
515
/
150
545
540
/
/
/
/
1.2.1 Standard Installation
33

1.2.3 Components of Installation
1.2.4 Installation of Articulated Arm Opener
ARTICULATED ARM OPENERS USER MANUAL
2
1
2
3
4
5
6
7
8
9
10
11
12
13
Straight arm
Curved arm
U-shaped fixing plate
Mechanical stopper
Front-end fixing bracket
Screw
Nut Ø10
Screw
Gasket
Screw
Spring washer
Nut Ø8
Cable gland
1 pce
1 pce
1 pce
2 pcs
1 pce
4 pcs
2 pcs
2 pcs
2 pcs
2 pcs
4 pcs
4 pcs
1 pce
3 4 5
6
7
8
13 12 11 10 9
2
1
1. Refer to the Dimension Chart to choose the correct dimensions of the motors and
position to be installed.
2. Check if the mounting surface of the brackets to be installed is smooth, vertical and rigid.
3. Arrange the cables for power supply cable of the motors, make sure power supply cable is connected to motor.
4. Motor installation and setting for mechanical stopper in opened and closed position.
2) Place the gate in the full closed position and fix the U-shaped
fixing plate on the wall.
1) Remove the upper cover and mechanical
stoppers on the bottom of motor.
4) After positioning the front of curved arm on the bottom of motor,
release the motor and position the straight arm on the end of
curved arm and mounting bracket with corresponding screws
and nuts.
1
5
2
7
6
3
8
12
3) Install the motor on the U-shaped fixing
plate with corresponding screws and nuts.
12
9
10
4
13
11

ARTICULATED ARM OPENERS USER MANUAL 3
1.2.5 Emergency Release
1) Insert the release key to the release slot
2) Turn the release key anti-clockwise
3) Pull out the release bar
4) Turn the release key clockwise to fix the release bar, the release bar has to be in pulled out position when turning
the release key clockwise
5) Closed position adjustment :
5.1 After the full closed position decided, fix the corresponding mechanical stopper at the position.
5.2 After the full closed position decided, make the pointer on limit switch aligned with the pointer on the curved arm.
(Red points shown on the figure below indicate the pointers)
6) Opened position adjustment :
6.1 Adjust the gate to full opened position and after the position decided, fixe with corresponding mechanical stopper.
6.2 Adjust the gate to full opened position and after the position decided, make the pointer on the limit switch aligned with
the pointer on the curved arm. (Red points shown on the figure below indicate the pointers)
1.2.6 WiFi Device
Ports
P button:
Wi-Fi Paring: Press 1 sec
Default Setting: Press 3 sec
LED Display
If you want to switch WIFI AP, please press P button and follow Step 5. from App
Installation to reset.
• LED description:
Blue: LED will be flashing during WIFI pairing, and be ON when completed.
Green: LED will be flashing if WiFi box receives signal from APP.
If your home WIFI disconnects, the green light will continuously flash, and
it will be off until WIFI is connected again.
Red: System failure or wrong PIN.

ARTICULATED ARM OPENERS USER MANUAL
4
Please kindly notice that the operation of power connection should be carried out by a qualified electrician with
following steps:
1). Make sure the motor did not connect with power supply before finishing installation.
2). Make sure all the wires are firmly connected.
3). Then, connect the power with motor.
1.2.8 Power Supply Connections
1.2.7 Photocells
The safety photocells are security devices for control automatic gates. Consist of one transmitter and one
receiver based in waterproof covers; it is triggered while breaking the path of the beams.
SPECIFICATION:
INSTALLATION:
1. Open the cover and connect wires.
2. Mounted the receiver and transmitter on the proper position.
3. Ensure there are no obstacles between receiver and transmitter.
For optimal efficiency, the receiver and transmitter should be properly aligned.
4. Power-up the photocells and make sure the LED light on receiver and transmitter are ON.
Step 1 Step 2 Step 3 Step 4
Detection Method
Sensing Range
Input Voltage
Contact Current
Response Time
Emitting Element
Operation Indicator
Dimensions
Output Method
Current Consumption
Connection Method
Housing Material
Water Proof
Safety Standard
Through Beam
MAX~15m
AC/DC 12~24V
TX: 30mA Max , RX: 25 mA Max
<100mS
Infrared LED/ Wave Length:940nm
RX:Red LED On (beam broken) / Off (beam aligned)
TX:Red LED On
63*63*30 mm
Relay Output
Beam aligned:RX<25ma\TX<30ma
Beam broken:RX <10ma\TX <30ma
Terminal Block
ABS / PC
IP44
CE
RX
1 2 3 4 5
COMNCNO
+
-
TX
+
-
1 2
Antenna
M2-M1- Lmt4Lmt3
Lmt2
SKey
S1
M2+
M1+
Ph2Ph1 PhVcc PhVcc
S25V
ANT
GND
DKey
GND
GND GND GND
Lmt1
GND
PC190-PCB1
40121-377-A1
+ -
SW3
UP
R113
R112
R111
R110
R108
R107
R106
R105
R104
R103
R102
J5
SW1
RF-LEARN
RF1
K3
K2
J3
J7
J8
SW4
SET
SW5
DOWN
NC NO
CO
+-- +
CO
NONC
+
CO
NO
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
26 25 24 23 22 21 20 19
LED2 LED3
LED4

ARTICULATED ARM OPENERS USER MANUAL 5
Figure 2(1)
2.1 Wiring Connection
TX RX
Transformer
Antenna
WiFi box
LED Display
LED2 Push button or Key selector
LED3 Photocell 1
LED 4 Photocell 2
UP
SET
SET
DOWN
RF-LEARN
RF-LEARN
LED2LED4LED3
11
Lit+Lit-Lat+Lat-M1+M1-M2+M2-5VS1S2GNDLmt1Lmt2GNDLmt3Lmt4GNDGND Ph1Ph2 PhVccPhVcc GND DKeySKey
26 2425 23 2122 1920 18 1617 15 1314 11 1012 9 8 67 5 34 12
F1
NC
-

ARTICULATED ARM OPENERS USER MANUAL
6
M1+ M1-
Motor1 Power
2.1.1 Master Motor is installed at right side
Motor with Hall sensor
Transformer
Antenna
ANT
GND
M2- M1- Lat- Lit-Lmt4 Lmt3 Lmt2 Lit+SKey S1 M2+ M1+ Lat+Ph2 Ph1PhVccPhVcc S2 5VDKeyGND GNDGNDGND Lmt1GND
PC190-PCB1
40121-377-A1
+ -
T4
SW3
UP
J1
Q17
R113
R112
R111
R110
R108
R107
R106
R105
R104
R103
R102
J5
SW1
RF-LEARN
RF1
MOV1
K5
K3
K2K1
J4 J3
J7
J2
F1
DB1
J8
SW4
SET
SW5
DOWN
NC NO
CO
+-
NC NO
CO
+-- +
CO
NONC
- +
CO
NONCNC NO
CO
+-
-
+
12345678
910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
M2+ M2-
Motor2 Power
Motor with Limit switch
Antenna
ANT
GND
PC190-PCB1
40121-377-A1
+ -
T4
SW3
UP
J1
Q17
R113
R112
R111
R110
R108
R107
R106
R105
R104
R103
R102
J5
SW1
RF-LEARN
RF1
MOV1
K5
K3
K2K1
J4 J3
J7
J2
F1
DB1
J8
SW4
SET
SW5
DOWN
NC NO
CO
+-
NC NO
CO
+-- +
CO
NONC
- +
CO
NONC
NC NO
CO
+-
-
+
12345678
910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
M1- Limit1 Limit2 GNDM1+
Motor1 PowerLimit Switch
M2- Limit4 Limit3 GNDM2+
Motor2 PowerLimit Switch
Antenna
ANT
GND
J5
RF1
J4 J3
J7
J8
NC NO
CO
+-- +
CO
NONC
- +
CO
NONC
NC NO
CO
+-
12345678
910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
M1- 5V S1 GNDM1+
Motor1 PowerHall sensor
M2- 5V S2 GNDM2+
Motor2 PowerHall sensor
Figure 2(2)
Figure 2(3)
Figure 2(4)
Remark:
Limit1, Limit3 (Open limit)
Limit2, Limit4 (Close limit)
M1 M2
M2- M1- Lat- Lit-Lmt4 Lmt3 Lmt2 Lit+SKey S1 M2+ M1+ Lat+Ph2 Ph1PhVccPhVcc S2 5VDKeyGND GNDGNDGND Lmt1GND
M2- M1- Lat- Lit-Lmt4 Lmt3 Lmt2 Lit+SKey S1 M2+ M1+ Lat+Ph2 Ph1PhVccPhVcc S2 5VDKeyGND GNDGNDGND Lmt1GND

ARTICULATED ARM OPENERS USER MANUAL 7
M2+ M2-
Motor2 Power
M1+ M1-
Motor1 Power
M2- Limit4 Limit3 GNDM2+
Motor2 PowerLimit Switch
M2- 5V S2 GNDM2+
Motor2 PowerHall sensor
Antenna
ANT
GND
PC190-PCB1
40121-377-A1
+ -
T4
SW3
UP
J1
Q17
R113
R112
R111
R110
R108
R107
R106
R105
R104
R103
R102
J5
SW1
RF-LEARN
RF1
MOV1
K5
K3
K2K1
J4 J3
J7
J2
F1
DB1
J8
SW4
SET
SW5
DOWN
NC NO
CO
+-
NC NO
CO
+-- +
CO
NONC
- +
CO
NONC
NC NO
CO
+-
-
+
12345678
910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
Antenna
ANT
GND
PC190-PCB1
40121-377-A1
+ -
T4
SW3
UP
J1
Q17
R113
R112
R111
R110
R108
R107
R106
R105
R104
R103
R102
J5
SW1
RF-LEARN
RF1
MOV1
K5
K3
K2K1
J4 J3
J7
J2
F1
DB1
J8
SW4
SET
SW5
DOWN
NC NO
CO
+-
NC NO
CO
+-- +
CO
NONC
- +
CO
NONC
NC NO
CO
+-
-
+
12345678
910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
M1- Limit1 Limit2 GNDM1+
Motor1 PowerLimit Switch
Antenna
ANT
GND
J5
RF1
J4 J3
J7
J8
NC NO
CO
+-- +
CO
NONC
- +
CO
NONC
NC NO
CO
+-
12345678
910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
M1- 5V S1 GNDM1+
Motor1 PowerHall sensor
Figure 2(5)
Figure 2(6)
Figure 2(7)
Remark:
Limit1, Limit3 (Close limit)
Limit2, Limit4 (Open limit)
2.1.2 Master Motor is installed at left side
Motor with Hall sensor
Motor with Limit switch
M1M2
M2- M1- Lat- Lit-Lmt4 Lmt3 Lmt2 Lit+SKey S1 M2+ M1+ Lat+Ph2 Ph1PhVccPhVcc S2 5VDKeyGND GNDGNDGND Lmt1GND
M2- M1- Lat- Lit-Lmt4 Lmt3 Lmt2 Lit+SKey S1 M2+ M1+ Lat+Ph2 Ph1PhVccPhVcc S2 5VDKeyGND GNDGNDGND Lmt1GND
M2- M1- Lat- Lit-Lmt4 Lmt3 Lmt2 Lit+SKey S1 M2+ M1+ Lat+Ph2 Ph1PhVccPhVcc S2 5VDKeyGND GNDGNDGND Lmt1GND

ARTICULATED ARM OPENERS USER MANUAL
8
3. Get Started
3.1 Step 1: Remote Memorizing
3.1.1 Memorizing
Note:
(A) Remote memorizing must be done before system learning.
(B) Verifying the GATE CONDITION.
1) Release the gear with the release key and move the gate to the middle so the gate can move in both opening
and closing directions; then lock the gear.
2) Operate the gate to opened and closed position several times and make sure the gates touches the limit switch at least
2~3 cm before the mechanical stop.
1. Press button RF-Learn on the control board (Figure 1) as many times as the number corresponding to the desired
command, according to the following table, Within 10s, press the desired button on the remote that you want it to be
memorized (figure 1)
2. Make sure that the LED display flash the “OSC” or “PED” three times. The code is corresponding to the selected
command. (figure 2)
3. Repeat step 1 & 2 within 10s, if there have other remotes to be memorized for the same type of command. No need within
10s, the memorization stage will terminate automatically.
OSC PED
(figure 2)
New Remote
(Press A/B button
you selected)
(figure 1)
(figure 2)
(figure 3)
Press RF Learn for 1 time
Press RF Learn for 2 times
Command
Open-Stop-Close circle
Pedestrian mode
Massage code
LED display “OSC”
LED display “PED”
Antenna
LED Display
LED2 Push button or Key selector
LED3 Photocell 1
LED 4 Photocell 2
UP
SET
SET
DOWN
RF-LEARN
RF-LEARN
A B

ARTICULATED ARM OPENERS USER MANUAL 9
3.3 Deleting memory of single command:
1. Press and hold RF-LEARN button (Figure 3) on the control board for 5 seconds.
2. Wait until the LED display shows “DKY”, then, within three seconds:
3. Press the button on the remote to be deleted. If the command has been deleted, the LED display will flash quickly five times.
4. Repeat above steps if more command to be need.
3.3.1 Deleting all memory of all remotes:
With this operation all the memorized remotes will be deleted.
1. Press and hold down RF-LEARN button (Figure 4) on the control board for 10 seconds.
2. You will see “DKY” first, and Hold the RF-Learn until you see “DAL”. All memory is deleted.
DKY DKY
(RF-LEARN)
(figure 3)
5 sec Blink 5 times
DKY
(RF-LEARN)
(figure 4)
10 sec
DAL
(RF-LEARN)
LED2 D Key/S Key : Key selector, or the push button is activated, LED2 will be on.
LED4 Ph1 : LED4 will be on when Ph1 are triggered.
LED3 Ph2 : LED3 will be on when Ph2 are triggered.
Antenna
M2-M1-
Lat-
Lit- Lmt4Lmt3
Lmt2
Lit+ SKey
S1
M2+
M1+Lat+ Ph2Ph1 PhVcc PhVcc
S25V
ANT
GND
DKey GND
GND GND GND
Lmt1 GND
PC190-PCB1
40121-377-A1
SW3
UP
Q17
J5
SW1
RF-LEARN
RF1
K5
K3
K2K1
J4 J3
J7
F1
DB1
J8
SW4
SET
SW5
DOWN
NC NO
CO
+-
NC NO
CO
+-- +
CO
NONC
- +
CO
NONC
NC NO
CO
+-
-
+
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
LED2 LED3
LED4
3.2 LED Indication
A B

ARTICULATED ARM OPENERS USER MANUAL
10
3.3.2 Step 2: System Learning
Step1:
Press and Hold the Press SET button for 3s, When LED shows “LEA” then release SET, then the motor runs the
system learning procedure automatically, once learning completed shows “D-G” or “S-G”
(No remote required)
Note: Please check the parameter setting of “FI”(Dual/Single) before going into system learning.
Restore system default setting
Press and Hold the UP + SET + DOWN button for 5s and panel restores back to default setting
Note:
1. LED Shows “D-G” tells the system learning has be completed for Dual Gate installation
2. LED Shows “S-G” tells the system learning has be completed for Single Gate installation
A. Dual Gate:
(1) Slave Gate Close → (2) Master Gate Close → (3) Master Gate Open →
(4) Slave Gate Open → (5) Slave Gate Close → (6) Master Gate Close
B. Single Mode :
(1) Master Gate Close → (2) Master Gate Open → (3) Master Gate Close
1 2 3
1 2 3
4 5 6
Press
3 Sec
1 2 3
D-G/S-G
LEA
Antenna
LED Display
UP
SET
SET
DOWN
RF-LEARN
RF-LEARN

ARTICULATED ARM OPENERS USER MANUAL 11
3.4 Gate-moving Logic
(A) In gate-opening phase: The gates stop if the transmitter/push button/key selector is activated, and close when
the transmitter/push button/key selector is reactivated.
(B) In gate-closing phase: The gates stop if the transmitter/push button/key selector is activated, and open when
the transmitter/push button/key selector is reactivated.
(C) In gate-opening or gate-closing phase: For safety purpose, the gates stop if encountering obstacles.
3.5 Checking the Gate Movement
1). Release the gear with the release key and move the gate to the middle so that it can move in both
opening and closing directions; then lock the gear.
2). Operate the gate to opened and closed position several times, and make sure the gates reaches the limit
switch at least 2~3 centimeters before the mechanical stop.
4.1 Function Of The LED Display
4. Function Setting
LED Display Programmable Functions LED Display Programmable Functions
When the gate is opening, the LED Display
show ‘OPN’ for 2s and then change to Amp
current indication
When the gate is stopped, the LED Display show
‘STP’ until next commend has been made, after
10s no further movement, the LED turns to OFF
When the gate is closing, the LED Display show
‘CLS’ for 2s and then change to Amp current
indication
LED display shows “S01” means the panel did not
detected the M1+/M1 and M2+/M2 both been
connected before the system learning procedure,
check for motor wire connection, for dual gate
system
The memory of the system is all deleted/cleaned
by press and hold the UP + SET+ DOWN button
together for 5s and the panel will be back to
default settings
LED display shows “S02” means the panel did not
detected the M1+/M1 but detected M2+/M2 been
connected, notice the installer to check the motor
wire connection, if this is single gate system,
motor wire should connect to M1+/M1 not on
M2+/M2
LED display show “S03” means same button on
the remote has been identified for more than 2
functions
[LEA] means motor into the system learning
mode, do not interrupt during this procedure
[D-G] means motor completed the learning
procedure for dual gate installation
[S-G] means motor completed the learning
procedure for single gate installation

ARTICULATED ARM OPENERS USER MANUAL
12
5.2 Parameter
5.1 Parameter Learning
5. Parameter Modification
LED Display Definition Parameter Table Description
Motor Type
Overcurrent for Gate Opening
Overcurrent for Gate Closing
Motor Speed for Opening
Motor Speed for Closing
Deceleration Speed
Time Gap b/w Two Gates
(Opening)
F1
F2
F3
F4
F5
F6
F7
F1-1
F1-2
F1-3
F2-1
F2-2
F2-3
F2-4
F3-1
F3-2
F3-3
F3-4
F4-1
F4-2
F4-3
F4-4
F5-1
F5-2
F5-3
F5-4
F6-1
F6-2
F6-3
F6-4
F7-0
F7-1
F7-2
F7-3
F7-4
F7-5
F7-6
F7-7
F7-8
F7-9
Overcurrent
Limit Switch
Hall Sensor
2A
3A
4A
5A
2A
3A
4A
5A
40%
50%
75%
100%
40%
50%
75%
100%
40%
50%
60%
70%
0 sec
2 sec
5 sec
10 sec
15 sec
20 sec
25 sec
35 sec
45 sec
55 sec
1. The factory setting is "F1-1"
1. The factory setting is "F2-2".
1. The factory setting is "F3-2".
1. The factory setting is "F4-3".
1. The factory setting is "F5-3".
1. The factory setting is "F6-2".
1. The factory setting is "F7-1".
Press “UP+SET” for 3 seconds to get
into the program setting display from F1.
Press “UP” or “DOWN” to change
setting item from F1 to FJ .
Press “SET” button again to get into
the sub-settings
Press “UP” or “DOWN” to change
Push from F1-1 to F1-3.
Press “SET” button again to
confirm.
Press
891011121314
LED1
LED2
LED3
ON
OFF
UP
SET
DOWN
Press
AC INPUT
1234567891011121314
1
23456
LED1
LED2
LED3
ON
OFF
UP
SET
DOWN
Press
AC INPUT
1234567891011121314
1
23456
LED1
LED2
LED3
ON
OFF
UP
SET
DOWN
Press
891011121314
LED1
LED2
LED3
ON
OFF
UP
SET
DOWN
Press
AC INPUT
1234567891011121314
1
23456
LED1
LED2
LED3
ON
OFF
UP
SET
DOWN
1 2
4 5
3

ARTICULATED ARM OPENERS USER MANUAL 13
LED Display Definition Parameter Table Description
Time Gap b/w Two Gates
(Closing)
Auto-closing
Safety Device Function Mode
Pedestrian Mode
Flashing Light
Photocell Activation
Photocell 2 Activation
Alarm Buzzer
Electric Latch Mode
LED Direction
Dual / Single Gate
Over Current Reverses Time
when Close
F8
F9
FA
FB
FC
FD
FE
FF
FG
FH
FI
FJ
F8-0
F8-1
F8-2
F8-3
F8-4
F8-5
F8-6
F8-7
F8-8
F8-9
F9-0
F9-1
F9-2
F9-3
F9-4
F9-5
F9-6
F9-7
F9-8
FA-1
FA-2
FA-3
FA-4
FB-0
FB-1
FC-0
FC-1
FD-0
FD-1
FE-0
FE-1
FF-0
FF-1
FG-0
FG-1
FH-0
FH-1
FI-1
FI-2
FJ-0
FJ-1
FJ-2
FJ-3
FJ-4
FJ-5
FJ-6
0 sec
2 sec
5 sec
10 sec
15 sec
20 sec
25 sec
35 sec
45 sec
55 sec
Function OFF
3 sec
10 sec
20 sec
40 sec
60 sec
120 sec
180 sec
300 sec
Mode 1
Mode 2
Mode 3
Mode 4
Function OFF
Function ON
Function OFF
Function ON
Function OFF
Function ON
Function OFF
Function ON
Function OFF
Function ON
Standard Gate Opening
Release Gate Tension before
Opening (Gate Reversing for 0.25s)
When Terminal Block is at Top
When Terminal Block is at Bottom
Single Gate
Dual Gate
Function OFF
0.1 sec
0.2 sec
0.3 sec
0.4 sec
0.5 sec
0.6 sec
1. The factory setting is "F8-1".
1. Auto-close mode activates when the gates move to
the end position or stopped manually. If the
transmitter, push button, or the key selector is
activated before the auto-close counting, the gate
will close immediately.
2. The factory setting is "F9-0".
1. Please see 5-3 photocell adjustment for photocell logic
2. The factory setting is "FA-1".
1. The factory setting is "FB-1".
1. When function FC-1, the light will flash for 3 seconds
before the gate operates. If set OFF, the flash light will
operate with motor at the same time.
2. The factory setting is "FC-0".
1. The factory setting is "FD-0".
1. The factory setting is "FE-0".
1. The factory setting is "FF-0".
1. If the function is FG-1, the motor will be reversed for
0.25 sec. to release the tension.
2.The factory setting is "FG-1".
1. The factory setting is "FH-0".
1. The factory setting is "FI-2".
1. The factory setting is "FJ-0"
Note(F1-3 over-current setting in Hall sensor mode):
Only in “F1-3”Hall sensor mode, the PCB will record all the current value in learning mode. Please adjust over current value by setting F3 function after
learning mode.
The recorded current values will increase according to the value shown on LED display as over current value.

ARTICULATED ARM OPENERS USER MANUAL
14
5.3 Photocell Adjustment
The actions of the photocells safety edge loop detector when they detecting obstacles.
FA-1 Photocell OPEN/CLOSE (Standard set up)
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safefy Device1
Photocell-CLOSE
No effect
Reload automatic closing time
Reload automatic closing time
Open
No effect
Safefy Device2
Photocell-OPEN
Open not allowed
No effect
Open not allowed
No effect
Close
Position of Gate When safety devices are activated
FA-2 Safety Edge
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safefy Device1
Photocell-CLOSE
No effect
Reload automatic closing time
Open
No effect
Reload automatic closing time
Safefy Device2
Safety Edge
Open not allowed
OPEN/CLOSE not allowed
Reverse to open for 2 seconds
Reverse to close for 2 seconds
Position of Gate When safety devices are activated
FA-3 Open Only Device (Vehicle detector)
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safefy Device1
Photocell-CLOSE
No effect
Reload automatic closing time
Open
No effect
Reload automatic closing time
Safefy Device2
Opening Device
Open
Open
Open
No effect
Position of Gate When safety devices are activated
FA-4 Double photocell set up
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safefy Device1
Photocell-CLOSE
No effect
Open for 2 seconds, when auto closing is ON
Close not allowed
Open
No effect
Safefy Device2
Photocell-OPEN/CLOSE
Open not allowed
No effect
Open not allowed
No effect
Stop
Position of Gate When safety devices are activated

ARTICULATED ARM OPENERS USER MANUAL 15
6. Technical Features
6.1 Dimension
6.2 Technical Feature:
Model
Motor
Gear type
Nominal thrust
Maximum Gate Weight
Maximum Gate Length
Operating Temperature
Dimension
Weight
Papillon250
24Vdc motor
Electromechanical worm gear
2500N
250 kg per leaf
2.5 meters per leaf
-20oC~+50oC
256 x 187 x 267mm
6 kg
Model
Main power supply
Back-up battery
Receiver board
Installation
Operating Temperature
Dimension
CB19
230Vac/110Vac, 50Hz/60Hz
2pcs of batteries for emergency operation, 1.3A each
433.92MHz; 200 transmitters memory
Built-in PCBA
-20oC~+50oC
275mm x 195mm x 102mm
190mm250mm
255.2mm

ARTICULATED ARM OPENERS USER MANUAL
16
7. Maintenance
Conduct the following operations at least every 6 months. If you are a high intensity user, please shorten the period
in between.
Disconnect the power supply:
(1) Clean and lubricate the screws, the pins, and the hinge with grease.
(2) Check the fastening points are properly tightened.
(3) Maintain the wire connection are in good condition.
Connect the power supply:
(1) Check the power adjustments.
(2) Check the function of the manual release.
(3) Check the function of photocells or other safety devise.

ARTICULATED ARM OPENERS USER MANUAL 17

Low Voltage
24V
24V power supply
for great safety
Durability
Solid material apply
with lasting usage
EZ Instal
Easy installation
and user friendly
interface
Silence
Worm gear application
give silence operation
Manual release device
with easy use and
highly protection
Key Release
34100-124-16-A
Table of contents