aci RD2402D Series Installation instructions

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
Version: 6.0
I0000690
RD2402D SERIES
Installation & Operation Instructions Phone: 1-888-967-5224
Website: workaci.com
CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE
MAY BE AFFECTED.
GENERAL INFORMATION
The RD2402D is an output module that works with the MOD9200 series network transceivers to output two (2)
wireless digital signals (dry contact) for wireless control of modulating actuators or wireless status indications. The
network transceiver receives the wireless signal from the sensor/input concentrator and that data is sent to the
BAS via RS-485. If the BAS determines an action is needed, it then sends the command to the transceiver and the
transceiver sends that command wirelessly to the RD2402D, which then outputs a digital signal.
The maximum radio transmission distance is dependent on the building type. In a typical commercial
building with steel I-Beam construction, concrete oors with reinforcing rod, and metal stud walls, it can be
expected that transmissions will penetrate horizontally approximately 200-300 feet of oor, walls, furniture
and air.
Generally, a wireless system will cover at least three oors–one oor above, and one oor below the receiver
location. In some buildings with favorable transmission characteristics the system may cover more oors -
see FIGURE 2, p.2. Wireless sensor transmitters should be installed within 200 to 300 feet of the RM2432D
receiver.
RR2552 signal repeaters can be installed as needed to increase transmission distance between sensors and
receivers - see FIGURE 1.
PRECAUTIONS
• To maintain high performance, do not install sensors, repeaters, or receivers in the following areas:
- Inside metal enclosure / panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or large body of water
- Do not mount above false ceiling. Mount in wall 1” below ceiling.
MOUNTING INSTRUCTIONS
Mount the RD2402D as close to the equipment or
controller as possible using four #8 screws
(mounting dimensions see Figure 3).
WIRING INSTRUCTIONS
WIRING PRECAUTIONS
•Do NOT run Analog/Digital Output wires
in any conduit with line voltage
(24/120/230 VAC).
•Remove power before wiring. NEVER
connect or disconnect wiring with power
applied.
• The RD2402D is full wave rectified.
•It is recommended that you use an
isolated UL-listed Class 2 transformer
when powering the unit with 24 VAC.
Failure to wire the devices with the
correct polarity when sharing transform-
ers may result in damage to any device
powered by the shared transformer.
Observe polarity when connecting analog
outputs to the controller inputs.
Connect 24VAC 60Hz to the TB1 terminals using
16-26 twisted pair wire. Check all connections
before applying power to the unit.
Connect the digital outputs to the appropriate control input terminals on the controller using 16-26 AWG
wire. Each output needs 2 wires. Do not Jumper Commons for relay outputs.
FIGURE 1: WIRELESS BUILDING DIAGRAM
SENSOR
REPEATER
RECEIVER
REPEATER & RECEIVER
1’ FROM CEILING

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
Version: 6.0
I0000690
CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE
MAY BE AFFECTED.
GENERAL INFORMATION
The RD2402D is an output module that works with the MOD9200 series network transceivers to output two (2)
wireless digital signals (dry contact) for wireless control of modulating actuators or wireless status indications. The
network transceiver receives the wireless signal from the sensor/input concentrator and that data is sent to the
BAS via RS-485. If the BAS determines an action is needed, it then sends the command to the transceiver and the
transceiver sends that command wirelessly to the RD2402D, which then outputs a digital signal.
The maximum radio transmission distance is dependent on the building type. In a typical commercial
building with steel I-Beam construction, concrete oors with reinforcing rod, and metal stud walls, it can be
expected that transmissions will penetrate horizontally approximately 200-300 feet of oor, walls, furniture
and air.
Generally, a wireless system will cover at least three oors–one oor above, and one oor below the receiver
location. In some buildings with favorable transmission characteristics the system may cover more oors -
see FIGURE 2, p.2. Wireless sensor transmitters should be installed within 200 to 300 feet of the RM2432D
receiver.
RR2552 signal repeaters can be installed as needed to increase transmission distance between sensors and
receivers - see FIGURE 1.
PRECAUTIONS
• To maintain high performance, do not install sensors, repeaters, or receivers in the following areas:
- Inside metal enclosure / panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or large body of water
- Do not mount above false ceiling. Mount in wall 1” below ceiling.
MOUNTING INSTRUCTIONS
Mount the RD2402D as close to the equipment or
controller as possible using four #8 screws
(mounting dimensions see Figure 3).
WIRING INSTRUCTIONS
WIRING PRECAUTIONS
•Do NOT run Analog/Digital Output wires
in any conduit with line voltage
(24/120/230 VAC).
•Remove power before wiring. NEVER
connect or disconnect wiring with power
applied.
• The RD2402D is full wave rectified.
•It is recommended that you use an
isolated UL-listed Class 2 transformer
when powering the unit with 24 VAC.
Failure to wire the devices with the
correct polarity when sharing transform-
ers may result in damage to any device
powered by the shared transformer.
Observe polarity when connecting analog
outputs to the controller inputs.
Connect 24VAC 60Hz to the TB1 terminals using
16-26 twisted pair wire. Check all connections
before applying power to the unit.
Connect the digital outputs to the appropriate control input terminals on the controller using 16-26 AWG
wire. Each output needs 2 wires. Do not Jumper Commons for relay outputs.
FIGURE 2: WIRELESS MULTILEVEL DIAGRAM
SENSOR
SENSOR
SENSOR
SENSOR
RECEIVER/REPEATER

FIGURE 3: DIMENSIONS
STANDARD
NEMA 4X
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 6.0
I0000690
6.73"
(171mm)
4.76"
(121mm)
6.26"
(159mm)
3.58"
(91mm)
6.73"
(171mm)
Ø0.18"
Mounting Holes
2.17"
(55.1mm)
TOP VIEW
SIDE VIEW
TOP
24VAC
6.75"
(171.5mm)
3.5"
(88.9mm)
Ø0.190 (4 PLCS.)
7.285"
(185mm)
6.12"
(155.5mm)
4.72"
(119.89mm)
2.367"
(60.12mm)
TOP
TOP VIEW
SIDE VIEW
Antenna
Active LED
Data Link LED
24VAC

WARRANTY
The RD2402D Series are covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S
SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
PRODUCT SPECIFICATIONS
24 VAC, 60 Hz (Full wave rectied)
300 mA
Screw Terminal Blocks
16 AWG (1.31 mm) to 26 AWG (0.129 mm)
0.37 ft-lb (0.5 Nm) Nominal
32 to 140ºF (0 to 60ºC)
30 to 50% RH, Noncondensing
-4 to 176ºF (-20 to 80ºC), 70% RH
IEEE 802.15.4-2003/2006
900 MHz, Operating Frequency 10 channels between 902 – 928 MHz
Transmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm
200 – 300 ft horizontally depending on building type and constructions, and typically
one oorabove and below the transceiver vertically
Two (2) SPDT Pilot Duty Relays, Dry Contact
1.0A, 30 VDC @ 104ºF (40ºC), 0.5A, 125 VAC @ 104ºF (40ºC) Resistive
Mechanical: 5,000,000 operations minimum @ 36K operations/hr
Electrical: 100,000 operations minimum (under rated load @ 1.8K operations/hr)
(1) SPDT, Dry contact relay, 1.0A, 30 VDC @ 104ºF (40ºC), 0.5A, 125 VAC @ 104ºF (40ºC)
Resistive
Standard: ABS Plastic | UL94-5VA | NEMA 4X: Polycarbonate Plastic | UL94 HB
Supply Voltage:
Supply Current:
Connections:
Wire Size:
Terminal Block Torque Rating:
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature Range:
Data Protocol:
RF Characteristics:
Transmission Distance:
Digital Outputs:
Contact Rating:
Relay Durability:
Lost Signal Alarm:
Enclosure Material | Flammability
Rating:
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 6.0
I0000690
Table of contents
Popular Wireless Module manuals by other brands

Ebyte
Ebyte E70-433NW3S0 user manual

Cooper Wiring Devices
Cooper Wiring Devices ESPIRE RF RFAPM installation instructions

Lenovo
Lenovo TginkPad EM160R-GL Regulatory notice

Banner
Banner SureCross DX80 manual

Weidmüller
Weidmüller WL-TX installation manual

Telit Wireless Solutions
Telit Wireless Solutions ME910G1 Design guide