04 Installation and Commissioning Guide 820-960 Tri-Capacity Package
Doc. No.0525-111 Ver. 2 220722
Package Tri-Capacity
Installation and Commissioning Guide
01. SAFETY PRECAUTIONS
1. To ensure proper equipment operation, read all instructions thoroughly before proceeding with installation. Failure to do
so may result in damage to the unit and void your warranty.
2. Installation must be carried out by qualified technician*.
3. Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance with
AS/NZS 3000:2018 (also known as Australian Wiring Rules).
4. Ensure that unit installation complies with relevant council regulations and building code standards.
5. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as
per electrical diagram provided.
6. This unit is fitted with EC Motors with high power capacitors, which can have dangerous voltages at terminals for up to 5
minutes after main power has been isolated. Wait at least 5 minutes after power isolation and test for high voltage before
performing service work.
7. EC Plug Fan fitted to this unit has dual power supplies, i.e. 415V/3Ph/50Hz motor power supply plus 10VDC control power
supply. Care must be taken to ensure both are safely isolated to prevent personal injury and damage to the equipment.
8. Beware of rotating fans. Long hair, dangling items, such as clothing and jewellery could become entangled and pulled into
the device.
9. Always use PPE for safety and protection.
10.Make sure that safety guards and panel covers are always firmly secured and not damaged.
11. This appliance is not intended for use by young children or infirm person unless they have been adequately supervised by
a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that
they do not play with the appliance.
12. WH&S rules and regulations must be observed and will take precedent during installation process.
**Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and Training, dependent on local State/
Territory regulations.
02.UNPACKING AND INSPECTION
1. Remove the packaging around the unit.
2. Remove anchor bolts between the unit and the pallet.
3. Check the unit components for any sign of transport damage:
• Check for obvious panel dents.
• Check for any dents or breakage in propeller and blower fan.
• Conduct pull test on all wire terminals.
• Check for loosened screws.
If there is any damage to the unit contact ActronAir Customer Care Department immediately on number:ActronAir Customer Care Department immediately on number: 1300 522 7221300 522 722.
03. UNIT MOUNTING AND LOCATION
1. The units must be installed in accordance with relevant authority regulations.
2. Install the unit on a level and strong foundation.
3. Install anti-vibration rubber or isolation mounts (installer to supply) under all of the unit’s feet to help reduce noise
and minimize vibration transfer through the foundation. Ensure that all anti-vibration rubbers are rated to provide stable
support without impairing the unit’s structural integrity.
4. Diameter or width of anti-vibration rubber’s must be at least equal to the width of the actual feet to prevent deformation
overtime.
5. Level the unit to ensure good condensate drainage away from the unit.
6. Ample service access areas and minimum space allowance for airflow must be provided.
7. Avoid installing the unit in such a place where there is danger of fire due to leakage of inflammable fluid.
8.8. Ensure that the spaces around the unit are free from any obstructions for optimum unit performance.Ensure that the spaces around the unit are free from any obstructions for optimum unit performance.