Actulux SVM EI 24V-5A User manual

Installation instruction
Control Panel for Fire Ventilation
SVM EI 24V-5A / SVM EI 24V-8A
Fire ventilation
Comfort ventilation
24VDC max. 5A/8A
1 re ventilation group, 1 comfort group
Connection for manual control points, wind- and rain sensor, comfort switches, smoke detectors and
Fireman’s Priority Switch.
Possibility for bus connection of 35 control panels
#211534

23
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Address of installation
Name:
___________________________________________________________________________________________
Address:
___________________________________________________________________________________________
Phone no.:
___________________________________________________________________________________________
Contact person:
___________________________________________________________________________________________
Date of installation:
___________________________________________________________________________________________
Installation
Number of control panels and type (ex. SVM EI 24V-5A):
___________________________________________________________________________________________________
Number of re ventilation groups:
___________________________________________________________________________________________________
Type of opening system:
___________________________________________________________________________________________________
Type of opening system:
___________________________________________________________________________________________________
Type of opening system:
___________________________________________________________________________________________________
External controls (AFA-CCS):
___________________________________________________________________________________________________
Comfort control:
___________________________________________________________________________________________________
Wind- and rain sensor:
___________________________________________________________________________________________________
230V power supply from group:
___________________________________________________________________________________________________
Table of contents
Address of installation / Description of installation ..........................................................................2
General description ............................................................................................................................4
Safety rules during installation and operation ...................................................................................5
Explosion danger................................................................................................................................5
Installation..........................................................................................................................................5
Yearly legal requirement of maintenance and control .......................................................................5
Connection to motor- (actuator) outputs and line monitoring ...........................................................6
Current limiter type LIP. ....................................................................................................................7
Operation and connection of re switches.........................................................................................8
Auto reset...........................................................................................................................................9
Connection of smoke-/heat detectors.................................................................................................9
Comfort ventilation - connection and settings...................................................................................9
Diagram control panel and connections ........................................................................................10-11
External LEDs on the front panel (LED board).................................................................................12
Internal LED indication on the main board .......................................................................................12
Fuse specications .............................................................................................................................12
Complete jumper settings ..................................................................................................................13
Connection of more control panels to one re group (bus connection).............................................14
Connection of weather sensor / Close all function ............................................................................15
External signal transfer, connection of AFA systems and other systems...........................................15
Special functions................................................................................................................................16
Fireman’s Priority Switch ..................................................................................................................16
Cable sizes .........................................................................................................................................17
Lock-Out Mode SLAVE ....................................................................................................................18
Lock-Out Mode MASTER ................................................................................................................19
Part nos. and accessories....................................................................................................................20
CE Declaration of conformity ...........................................................................................................21
Service log .........................................................................................................................................23
Technical specications. ....................................................................................................................24
Rev 0.08 10.12.2020
Manufacturer:
Actulux A/S
Håndværkervej 2
9560 Hadsund
Denmark
Tlf.: +45 98 57 40 90
Fax: +45 96 15 28 00
e-mail: [email protected]
www.actulux.com

45
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
General description
The control panel can be used for electrical opening of e.g. skylights, smoke hatches or similar in
connection with re- and comfort ventilation.
The control panel has different inputs with line monitoring which can be activated by e.g. re switches,
smoke detectors, heat detectors, AFA systems and CCS systems.
For control of the indoor climate (comfort ventilation) manual switches, weekly timer, room thermostat
and outdoor weather sensors can be connected.
By means of LEDs in the the front panel the control indicates the operating condition (ok operation
and error- and alarm condition), just as it by means of the built-in potential free relay contacts can re-
lay operating information about ok operation and error- and alarm condition to other systems in the
building.
The polarity of the motor supply is reversed when opening or closing.
The control panel has built-in 72 hours battery back-up.
By a unique bus system consisting of a 4 wire cable the control panels can be mutually connected so
that up to 35 control panels can be connected and operate as an integrated system.
If the temperature in the control panel exceeds 75 °C, the control panel will enter ALARM condition.
Connection of cables to the in- and outputs of the control panel is described in the connection drawing
on page 10-11.
A more detailled connection to the individual in- and outputs is described in the individual sections in
this manual. Selection of cable sizes on page 17.
By means of jumpers and dip switches the control panel has different setting possibilities for in- and
outputs. These settings are indicated in a complete table (please see section with jumper settings on
page 13).
Examples of types of openings systems and the max. power consumption which can be connected to
the control panel:
Type: 24V power supply:
SA Power Single 4A
SA Power Double 8A (2x4A)
SA Power Large 8A
SA Power Mini 2.5A
Others See specication of max. power consumption on the opening
system
Safety rules during installation and operation
The control panel may only be installed and maintained by personnel authorized for installation of
automatic electrical re ventilation equipment.
Explosion danger
The control panel is supplied with back-up batteries, which contain large amounts of energy which can
be released as explosion in case of wrong handling - the following safety rules must therefore always
be observed:
• Νever short-circuit a back-up battery.
• Do not use external chargers on installed batteries. If unauthorized chargers are used explosive
gasses can be released from the battery.
• Do not drop back-up batteries as strong acids can be released if they are broken.
Installation
The control panel can weigh up to 7 kg and must be installed on a stable wall. The mounting holes for
wall mounting are placed on the metal plate underneath the platic lid. When mounting several control
panels side by side, the distance between them must be min. 30 mm.
All cables are connected according to the drawing on page10-11 and are dimensioned according to
table page 17. Keep in mind that the operating voltage from the control panel is 24V and that the max.
voltage drop is 15% which demands correct cable dimension according to table on page 17.
If cables are passed through the back plate, the edges of the plate must be lined with edge bands to
protect the cables.
Please be aware that it often may be required (in order to keep the demands on the CE marking of the
complete installation or another law) that the control panel is supplied with 230VAC from separate
powerline with its own ground error circuit interruper, and that a repair interrupter is mounted on the
motor line.
After connection the control panel must charge the batteries min. 12 hours before complete testing.
Yearly requirement of maintenance and control (authorized)
The functions of the control panel and the opening system must be tested by authorized personnel
at least once a year. The control panel informs when the maintenance should be done. Then the
external LEDs on the front panel are running. The control panel and opening system are of course
still full operating. Please call a service technician at your earliest convenience in order to carry out
the maintenance and to test the control and opening system, in order to prepare it for another year
of operation. The legal requirements for this must be observed and the testing and control must as a
minimum include the following:
• Control that all opening systems move to full opening when the re function is activated
- should not be carried out if the wind is more than 6 m/sec. as there might be a risk that the
opening system cannot close automatically.
• Control of the batteries. If the batteries are replaced it is important to use the same type as the
batteries are carefully chosen to be able to deliver the current, for which the control is specied.
• Control of in- and outputs on the control.
• Control of re switches and smoke- and heat detectors.
The batteries should be replaced as required, however at least every third year!
Use the same brand.

67
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Jumper J2 mounted in pos. »Motor line«
Line monitoring between terminal 2-3.
Jumper J3 (actuator output) is set according to
the number of termination resistors (27 KΩ) to
be detected – 1 to max. 4 lines can be detected
by moving jumper J3 – this means that the cable
installation between the control panel and the
actuators can be established in series connection
(cable connection from e.g. skylight 1, further
to skylight 2, etc.), or parallel connection (cable
connection from each skylight to the control), or
a combination of these. However, as mentioned
max. 4 different lines can be detected each
terminated with a 27 KΩ resistor.
For SVM EI 24V-5A:
the max. allowed current is 5A.
For SVM EI 24V-8A:
the max. allowed current is 8A.
Jumper description
J3 Number of connected 27Kohm terminal
resistors for actuator output
J2 Chooses line monitoring through motor
terminals 2-3 (Mot Mon) or separate
wire terminals 1-3 (Ext Li Mon), or no
line monitoring when J2/J3 is removed
F1 Fuse 8A for actuator output
PriorWeather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
2120
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE
Jumper J2 in pos. »Ext 3 wire«.
Line monitoring between terminal 1-3:
With jumper J3 (actuator output) it is chosen, how many lines (number of 27 KΩ)
you wish to detect - the same way as the motor line.
This setting demands 3 wire cable from motor output to motor.
Current limiter type LIP function and setting (if mounted)
The current limiter type LIP (mounted on the opening system) is used as current limiter between the
24V/48VDC supply and 1 or 2 actuators. When the adjusted current limit is reached, the speed of the
actuators is reduced. When the max. power on the actuator is exceeded, the actuator stops. On the
24V /48V types (LIP5, LIP6 or LIP7) max. 3 times overload cut outs in the same direction is allowed.
After that it will not be possible to run in this direction again, before the motor has run in the opposite
direction. This in order to protect the actuator gear mechanism.
Please note that when opening, the red LED in the LIP must light. This indicates that polarity to
actuator is correct.
M1M2Mn
27K Ohm
(Only last
actuator)
J3
J2
4
3
2
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
3
-
Line 1
12
+
1
24V Out
Actuator
+
+
A4
REV:
SHEET:
Denmark
SCALE:
2 OF 3
DWG NO.:
DRAWN BY: PSP
DATE: 26-09-17
TITLE:
DK 9560 Hadsund
Haandvaerkervej 2
1:1
211704_02
Actulux A/S
www.actulux.com
SIZE:
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
ENGELSK/TYSK
Connection to motor- (actuator-) output and line monitoring
The actuators (motors) must be connected to the actuator output on the output terminals 2-3.
It is possible to connect and disconnect the line monitoring on the actuator output (the factory setting is
“connected”). The cables to the actuators can be connected in series or parallel or a combination of these
(please see drawing with examples or connection diagram on the mid pages).
It is important to keep the right polarity of the cables - The actuators must always be connected through a
current limiter, e.g. the Actulux LIP or similar.
Cable monitoring (line monitoring) on the motor output
The control is equipped with 3 possible settings for cable
monitoring (line monitoring), which can be congured by
means of jumper J2.
* SA Power Large - parallel operation: Jumper OPT mounted - both motors stop at the same time if one stops because of overload.
** When DIP4 is OFF = Tandem mode - both motors stop at the same time if no current ows in one. (1.5 sec. reaction time)
*** Requires actuator with Reed. (3-core incl. black cable)
**** OFF = No delay between Master og Slave / ON = Seven sec. delay between Master and Slave.
Table of LIP settings
Opening System
24V/48V
3A/1.5A SA Power
Single, Double, Large
4A/2A SA Power
Single, Double, Large
2.5A/1.25A SA Power
Mini
2.5A/1.25A Rotary 100 LIP5/6
2A/1A SA Power Mini LIP7
DIP 1 ON OFF ON OFF
DIP 2 OFF ON ON OFF
Type Board
no.
Board
descrip.
Voltage and
function
DIP
1
DIP
2
DIP
3
DIP
4
DIP
5
DIP
6
DIP
7
DIP
8
LIP5 121315 A043 24/48V
1 channel
See
diagram
above
27K
ON Not mounted
LIP6 * 121330 A044 24/48V
2 channels
OFF ON** 27K ON M1-M2 delay =ON
LIP7
Basic
121305 LIP7 24/48V
1 channel
27K
ON Not mounted
LIP7
TA
121306 LIP7 24/48V 1 channel
Tandem
27K
ON
ON =
Com
OFF = Slave
ON = Master
OFF = Syncro Mode
ON = Tandem Mode ****
Not in
use
LIP7***
OC
121308 LIP7 24/48V
1 channel Syncro
m/position ind.
27K
ON
ON =
Com
OFF = Slave
ON = Master
OFF = Syncro Mode
ON = Tandem Mode **** Not in
use
No line monitoring
To disable line monitoring, place the 27KΩ resistor in terminal 1 and 3.
Set J2 to “Ext 3 wire monitor (line 1)”, and set J3 to “1”.
Now use Actuator out on 2 and 3.
NOTE: it is recommended that line monitoring should always be activated wherever
possible
LED 4 indicates if there is any fail on the actuator output. Steady light if wire is broken.
“Flashing fast” in case output is connected to earth. Flashing slow if output is shorted.
NOTE: When Flashing RESET or close is not possible

89
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
The Manual Control Point will generally contain the following:
• Breakable glass window and red control button is activated by
pressure - this puts the control panel in ALARM condition, by
which the motor output is activated (for normal service and testing
the lid can be opened with a key).
• RESET button which brings the control panel out of the alarm
condition and starts the closing sequence for about 180 seconds.
Please note that RESET does not cancel errors on the system, e.g.
line errors etc. These must be found and corrected.
• RED LED indicates that the control panel is in ALARM condition
and that the motor output either is or has been activated.
• YELLOW LED indicates faults on the system - please call for a
service technician.
• GREEN LED indicates that the system is in normal operation
condition without errors.
CONNECTION of the re switch is made as shown on the drawing.
The installation with re switches must be terminated with a 10 KΩ or
27 KΩ resistor in the last switch in order to establish the line monitoring
correctly – this can either be done by moving the factory mounted resistor
from the terminal strip to the last re switch or connect jumper J1 in
the re switch type BVT is mounted (by this a 10 KΩ resistor is also
connected).
By means of DIP switches the control panel has different possibilities of
settings for the input to the re switch:
DIP 1 (Conf. resw.):
On = ALARM condition from 500-3 KΩ, (indication of line error by direct
short circuit or open circuit).
Off = ALARM condition from 0-3 KΩ (indication of line error by open
circuit).
DIP 2 (Failsafe):
On = Any line error on re switch or smoke detector puts the control panel
in ALARM condition. This function can be used if cables to re switches
and smoke detectors are not reproof.
Off = An error condition does not report ALARM condition.
BVT
Operation and connection of Manual Control Points
DIP NO
FAIL SAFE
OFF
Fail. 24V
ALARM
OK 24V
7
43
Fire switch type BVT
→
Con. Fire. Sw
BVT for line monitoring
2,2Ω
10 KΩ
4
3
2
1
J1
6
7
Fire switch BVT No. 1
Red LED
Yellow LED
Green LED
10 KΩ
2,2Ω
43
2
1
Gnd
11 12
24V
10 13
6
J1
76
FIRE
15
Reset
14
21
Fit J1 in last
2
1
ON
→
REV:
2 OF 4
Denmark
A4
SCALE:SHEET:
DWG NO.:
DRAWN BY: PSP
DATE: 26-09-17
TITLE:
DK 9560 Hadsund
Haandvaerkervej 2
1:1
211704_03
Actulux A/S
www.actulux.com
SIZE:
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
ENGELSK
Denmark
111700 B
SIZE:
www.actulux.com
DWG NO.:
DRAWN BY: PSP
DATE: 07-02-17
TITLE:
SCALE:
DK 9560 Hadsund
Haandvaerkervej 2
REV:
A4 1 OF 2 2:1
Diagram BVT fireswitch
SHEET:
Actulux A/S Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
111693 Fireswitch 111784
Reset
Alarm
2
4
10 KΩ
3
OK
24V
LED
LED
Reset
7
Buzzer
2,2 KΩ
GND
6
J1
Buzzer
24V
Jumper
Alarm
1
LED
24V
Rød/Red
Rot/Rouge
Gul/Yellow
Gelb/Jaune
Grøn/Green
Grün/Vert
1 green LED OK (lights when OK and while closing)
2 yellow LED (lights on error)
3 red LED alarm (emergency opening)
4 ground (-)
5 not used
6 re switch reset
7 re switch emergency opening
Jumper J1 must only be set in the last or only re switch
Smoke- and heat detectors are connected as shown.
Line monitoring: Correct line monitoring can only be guaranteed with detectors
delivered from the supplier. Other detectors may have different internal resistances
and stand by power consumption.
Comfort ventilation – Connection and settings
The motor output can be controlled separately with a comfort switch.
For comfort ventilation there are the following possibilities:
Potentiometer in Puls pos.:
It is possible to press the »up« button 3 times, which each gives 6 seconds of opening
time - after that nothing happens – Continuous »up« signal gives 3x6 sec.=18 sec.
- One press on »down« closes the actuator completely for a period which is 18 sec.
longer than the complete opening time - In order to avoid »actuator pumping« max. 3
successive closing attempts will be allowed.
Potentiometer in Const. pos.:
As long as »up« signal or »down« signal are given, the actuators are running
Potentiometer in Puls variable pos.:
The time on the above mentioned pulse opening can be adjusted from 0-60 sec. on the
potentiometre.
When moving the potentiometer into the different positions the LED batt low will
ash for about 4 sec. to indicate when in puls mode. LED line fail ashes 4 sec. when
in constant and AC fail ashes when in puls varaiable.
Connection of smoke-/heat detectors
PriorWeather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
2120
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE
20
Gnd
18
Up
19
Down
Up
Down
Comfort
Switch Ch 1
Puls
variable
Min
Const.
Potmeter for
comfort feature
Max.
Puls
YELYEL YEL
AC FAIL LINE FAIL BATT LOW
Actulux A/S
211704_05
1:1
1 OF 2
SCALE:
DWG NO.:
Denmark
DRAWN BY: PSP
DATE: 26-09-17
TITLE:
DK 9560 Hadsund
Haandvaerkervej 2
www.actulux.com
SIZE: SHEET:
REV:
A4
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
DANSK/ENGELSK/TYSK
Room thermostats, weekly timers, CCS and
other external control equipment for comfort
ventilation can be connected on the input of the
comfort control.
PriorWeather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
2120
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE
Auto reset
When setting OPTION(DIP8) On, an automatic reset is performed 2 seconds after the re signal is
removed. (From software version V1.005)

10 11
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
PriorWeather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
2120
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE

12 13
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
LED/colour Symbol Operation possibilities for: Alarm/
re
Comfort
operation
LD1/red Actuator open (red). Lights when actuator opens
LD2/green Actuator close (green). Lights when actuator closes
LD3/red Weather sensor active (red). Lights when weather sensor is active Yes No
LD4/red Line error on actuator (red). Lights when actuator has open circuit,
ashes at earth fail or when short circuit occur.
It is not possible to RESET or close with actuator output (see page 7)
Yes No
LD5/red Line error on re switch (red). Lights when re switch has line error,
ashes when Fireman’s Priority Switch has line error
Yes Only
close
LD6/red Line error on smoke detector (red). Lights when smoke detector has
line error, ashes at temperatures above 75 °C
Yes Only
close
LD7/red Bus error (red). Lights when BUS signal from other controls is
missing. Only relevant if J4-J7 is mounted.
Yes Only
close
Green
Board + Front
lights if everything is ok
switched off by local error on this control
ashes by error message from other controls received by bus
Yes Yes
Yellow
Board + Front
Fault
lights by local error on this control
or by error message from other controls received by bus
Yes Only
close
*Yellow
Board + Front
Line error
ashes by local error on this control and if the ribbon cable or
jumper is not mounted on J9, or by error message from other
controls received by bus
Yes Only
close
*Yellow
Board + Front
AC error
ashes by local error on this control
or by error message from other controls received by bus
Yes Only
close
Red
Board + Front
Alarm
lights red constantly
Yes No
*Yellow
Board + Front
DC error
ashes at normal speed (1 Hz) by local battery error on this control
or by error message from other controls received by bus
ashes at high speed (10 Hz) by battery voltage below 19V.
Reset by DIP 4: OFF/ON
Blue
Board + Front
Lights blue constantly in open condition (when windows are open)
ashes when actuator is moving up and down
Lights with* Time for yearly service - please call for supplier (ashes fast) Yes Yes
Fuse specications
Placement
Fuse value
24V
F1 8A fast ading fuse 1 pcs. for 24V motor output
LEDs on main board and front panel
Text on board Factory
mounted
Mounted / ON function Dismounted / OFF function
DIP 1 Conf. Fireswitch No Fire switch active from 500-3 KΩ.
A short circuit of the smoke detector
input will generate a line error
Fire switch active from 0-3 KΩ.
A short circuit of the smoke detector
input will generate alarm
DIP 2 Failsafe No Line error on re switch or detector
puts the control in alarm
Normal mode
DIP 3 Temp. Detekt No Line error on motor line
(upper resistor area) = alarm
Normal mode
DIP 4 Ser Yes Active Inactive
DIP 5 Snitch No LED’s “remember” errors (line
errors, AC/Batt. error, bus error). The
LED’s can only be switched off/reset
again by setting dip switch off
Normal mode
DIP 6 Fail Relay No Failure relay works as indication that
skylight is open
Normal mode (works as failure
relay)
DIP 7 Week open No Weekly open (2 sec.) /close
(5 sec.) cycle activated
Weekly open/close not activated
DIP 8 Option No Auto reset (see page 9) Normal mode
DIP 9 Sprinkler No Motor output closes by active
detector (opens by activating the re
switch)
Normal mode - motor output opens
by ative detectors or re switches
DIP 10 Bus comfort No The control reacts on comfort signal
via bus activity
The control does not react on
comfort signals via bus activity //
NB! Always reaction on weather
signal and failures via bus activity
and own comfort signal
DIP 11 Bus re No The control reacts on alarm signal
via bus activity
The control does not react on alarm
signal via bus activity
//NB! Always reaction on weather
signal and failures via bus activity
and own alarm signal (detector or
re switch)
DIP 12 Lock-Out Mode No Slaves can enter Lock-Out Mode
see page 18
Normal mode
J1 J1 Yes Internal Buzzer ON Internal Buzzer OFF
J3
(motor)
1 - 2 - 3 - 4 Pos. 1 Connect according to number of
27KΩ terminal resistors on actuator
No line monitoring
J2
(motor)
Mot Mon act. Yes 2 wire line monitoring via 27KΩ
terminal 2-3 No line monitoring
Ext Li Mon act. No 3 wire line monitoring with direct
motor connection actuator
J4(Bus) Start term. No First control panel in the bus network
See section concerning connection
of controls panels in bus connection,
page 14
J5(Bus) + Master No
J6(Bus) Slave No Middle and last control panel in the
bus network
J7(Bus) End term. No Last control panel in the bus network
J9 FOIL Yes in Basic Line monotoring of front cabinet Line error ashes
J11 BatSup->Ø23 No Battery backup of terminal 23 Terminal 23 only AC supplied
Others: Reset time = 180 sec. closing // Cut-off motor output and loading after 360 sec. // Comf. var (potetiometer): 1-60 sec.
Complete jumper settings for SVM EI PCB

14 15
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Connection of more controls to one re group (bus connection)
By means of a bus communication it is possible to make 2 – 35 control panels to work as a complete
system. The control panels communicate with each other via a 4 wire bus connection.
This could e.g. be a 4x0.5 mm² reproof cable.
Terminal no. A1, A2, A3 and A4 are for the incoming connection and B1, B2, B3 and B4 for the outgoing
connection.
In the rst control panel start Bus J4 has to be on. Any control can be Master, if so J5 must therefore also be
on. The bus cable is connected on the output terminals B1, B2, B3 and B4 and lead to the next control panel
which is a slave, J6 must therefore be on. The cable is connected to the input terminals A1, A2, A3 and A4 of
the next control panel and further to the next slave control panel from terminal B1, B2, B3 and B4.
In the last slave control panel J7 and J6 must be on in order to terminate the bus connection.
ALARM: Alarms from Manuel Control Point smoke-/heat detectors are controlled locally. When DIP11 is
set the panel will go into alarm state if another control panel connected on the BUS enters alarm state
RESET: If the reset button on one control or in one re switch is activated, the reset function on all
connected controls is activated and starts the closing function on all motor output in approx. 180 sec.
COMFORT: The comfort control can work locally on each control panel. When DIP 10 is set the control
panel will react on any comfort signal send on the bus from another control panel.
If a wind- and rain sensor is connected, it will work on all control panels on the bus no matter dip settings.
Function description for control panels connected with bus connection
If more control panels are connected by means of a bus connection, the following are monitored/
communicated between the control panels:
- A detected bus error makes the LED 7 on the main board lights.
- A detected bus error brings all controls on the bus connection in error condition (line error).
- If one of the control panels in the network goes into alarm condition, all go into alarm condition.
- If one of the control panels goes into a certain error condition (line error, AC error, battery error or
bus error), the other control panels also go into error condition – the type of the error is indicated on
the board of the front plate of all control panels – on the control panel(s) which have not caused the
error, the ok LED on the board of the front plate ashes at the same time as the error. On the control
panel(s) which have caused the error, the OK LED is switched off.
Total length of bus cable: max. 300 m
END termination
Slave
J5
Fireproof
4 x 0,5mm²
J4
START TERM.
First Control Panel on BUS
J5
MASTER
BUS Master
Last Control Panel on BUS
BUS connection
J6
4 x 0,5mm²
BUS connection
Fireproof
Master
0-33 Control Panels on BUS
Slave
A1
J4
A2 A4
Serial In Serial Out
B4
B3B2B1
B1 B2 B3 B4
Serial Out
Serial In
A4A3A2
END TERM
A1 A2 A3 A4
Serial Out
B4B3B2B1
Serial In
BUS Slave
START TERM.
MASTER
J5 J6
SLAVE END TERM
J7
A1
START termination
BUS Slave
END termination
J4
START TERM.MASTER
A3
J6
SLAVE
START termination
J7
BUS Master
BUS Master
BUS Slave
END termination
J7
END TERMSLAVE
Please notice
mounted jumpers
START termination
DATE: 06-05-19
A4
SIZE:
www.actulux.com
TITLE: REV:
SCALE:
DWG NO.:
Denmark
DRAWN BY: ML
DK 9560 Hadsund
Haandvaerkervej 2
1:1
211862
Con. diag. for central BUS
EI
1 OF 4
Actulux A/S
SHEET:
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
B
Connection of weather sensor / Close all function
A weather sensor can be connected to the control panel.
The weather sensor is adjusted according to the instructions.
Actuators should be closed when the wind is above 6 m/s.
LED 3 on the main board indicates active weather sensor - lights
as long as input is active.
As long as the weather sensor is active, motor inputs cannot be opened with
comfort switches.
The weather sensor closes on all controls which are connected through bus
connection.
On the input to weather station a weekly timer can be connected which makes
sure that everything is closed, e.g. by end of a working day.
Power Supply to terminal 22 and 23 is only AC supplied as standard.
If battery backup is needed, then mount J11 .
NOTE: Be aware of standby time due to current consumption.
External signal output, connection to Fire Alarm
Panel and other control systems
The control panel can forward alarm condition to external connected
systems by means of potential free contacts on the terminals 4 (com),
5(NC) and 6(NO).
The control panel can forward failure condition to external connected
systems by means of potential free contacts on the terminals 7 (com),
8(NO) and 9(NC).
Alarm and error contacts work parallel on all controls connected with
bus connection.
DIP6 (fail relay):
On = Fail relay changes function to indicate open/closed window.
PriorWeather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
2120
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE
PriorWeather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
21
20
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE
#111960
#111961
How to make a connection from a Fire Alarm Panel
The control panel can receive potential free zero volt alarm signals from e.g.
AFA systems on the input to re switch or smoke-/heat detector
Terminal 16 and 17.
– Line monitoring resistor must be tted on the contact in the AFA system
Normally open
Supplied with Panel

16 17
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Special functions
Sprinkler function:
DIP 9 On - a special function comes in use where sprinkler systems are installed. With this function
activated, the actuator output closes, if smoke-/heat detector input is activated.
If the re switch is activated, the actuator output opens.
Weekly open/close:
DIP 7 On - the motor output opens shortly (3 seconds) once a week and closes immediately after -
This function is used to give the right tension on the packing of the skylights to keep them watertight.
Function of heat detector in LIP:
DIP 3 On - a heat detector 70-100 °C can be mounted in each LIP. If the temperatur is exceeded, the
control panel goes into alarm and the opening system is opening.
Lock-Out Mode:
DIP 12 On - see page 18
Fireman’s Priority Switch
The Fireman’s Priority switch is an override switch, which makes it possible for the Fireman to control the
panel regardless of sensor inputs.
Connection/function
- The CLOSE-switch activates the panel in close condition for 180 seconds, and the panel stays in re mode.
- The OPEN-switch activates the panel in open condition if not in re mode, and the panel enters re mode.
- The LED output is activated in open condition (windows are open).
When actuator is moving up or down LED ashes with 1Hz, in case of fail LED ashes with 10 Hz.
- The output is maximum 1 mA 24V.
- OPEN and CLOSE switches have line surveillance.
- Only one Fireman’s Priority Switch can be connected.
- When activating OPEN and CLOSE at the same time = reset is performed.
- The input is not a part of Congure Fire switch DIP1 = the input is active between 0-3 Kohm.
Prior
Weather
J11
K11
#111961
AWR-24
24V
®
2,2KΩ
Blue
1 Cannel LIP 7
M2
12
5
6
LIP #2
M1
8
7
34
Brown
2 channel LIP 6
Next LIP
Brown
Blue
Next LIP
Max. Torque 0.5 Nm
Max. Torque 0.5 Nm
Open
24
Close
25 27
Gnd
NO FOIL
26
Keyboard
T
OpenLed
RESET
NO
NC
COM
AC/DC
B4
A4
RED
GRE
#111960
RED
RED
RED
RED
RED
®
Manuel Control Point Smoke Comfort
R
E
S
E
#111980
See page 12
}
RED
ALARM
GRE
OK
YEL
FAILURE
J8
BUZZER ON/OFF
RED
RED
RED
RED
RED
GRE
RED
LED 1 Actuator open (red). Lit when actuator is opening.
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
LOCKOUT
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
OPTION
SPRINKLER
BUS COMFORT
BUS FIRE
12
3
4
6
7
5
8
11
9
10
BUS Master
BUS Slave
END termination
Puls
Max.
Potmeter for
comfort features
Con. Fire. Sig
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
LINE FAILAC FAIL
YEL YEL
BAT +
BAT -
ON
®
DIP NO.
1
2
OFF
®
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
SVM EI 24V - 5A/8A
BUZZER
B3
®
J5
J6
J7
A3
B1 B2
®
®
Serial Out
next unit.
Connection to
®
A1
prev. unit.
®
2120
Gnd
2322
Weather
Gnd
24V
A2
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
®
J4
Set J11 for batteri backup
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
L1 Out
L1 In
No.1
L2
L1 In
L2
Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
J1
Red LED
Yellow LED
Green LED
Extra relay print #111933
provides 2 additional
potential free contacts
each 30V 0,5A
Potential free ALARM switch.
Com + NO connected on alarm.
Max 48V 0,5A
Potential free Failure switch.
Com + NO connected on failure.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
12347
6
10 KΩ J1
Fire switch type BVT.
Fit J1 in last BVT for
line monitoring
(only last sensor)
Connection diagram SVM EI 24
Drawing: 211863_B
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
6
LIP #1
5
Actuator
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
24V Out
PS1
Power Supply 180-250 VAC
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
J1
DIP settings see page 13
REMOTE
no: 111894
GND
LED
OPEN
CLOSE
61
Firemans Priority switch
OPENCLOSE
Power
consumption
per group in
ampere
Cable cross section and amount of cores
2x1.5 mm² 2x2.5 mm²4x1.5 mm²
(2x1.5+2x1.5)
4x2.5 mm²
(2x2.5+2x2.5)
2x6 mm²5x2.5 mm²
(2x2.5+3x2.5)
2x10 mm²
2 74 m 12 3m 148 m 246 m 295 m 307 m 492 m
4 37 m 61 m 74 m 122 m 148 m 154 m 244 m
6 25 m 41 m 50 m 82 m 98 m 102 m 164 m
8 18 m 31 m 36 m 62 m 74 m 77 m 124 m
Table for SVM EI 24V-5A/8A allowed voltage drop 15% = 3.6V
Cable sizes
It is very important to use the correct cable types and sizes to make sure that the re ventilation system
meets the standards and works correct in an emergency.
The two most important factors are the ability of the cables to resist heat and to make sure that the
voltage drop in the cables to the actuators do not exceed 15 % at full load on the re ventilation hatches.
Fire resistant cables according to IEC 60331 must be used for the following functions:
Opening systems with actuators 24V 2 wires, see diagramme
(3 wires by external line surveillance)
Max. cable length
Fire switch 24V Min. 6 x 0.5 mm² (0.8 mm) 100 m*
Smoke detector 24V Min. 2 x 0.5 mm² (0.8 mm) 100 m*
Heat detector Min. 2 x 0.5 mm² (0.8 mm) 100 m*
Total length of bus cable 4 x 0.5 mm² (0.8 mm) 300 m*
* For cable lengths longer than 100m, properly closed shielded cables must be used.
Normal cables can be used for the following functions:
Supply for control 230VAC e.g. 3 x 1.5 mm² PVIK-J
Comfort ventilation button 24V Min. 3 x 0.5 mm²
Wind- and rain sensor 24V Min. 4 x 0.5 mm²
#111980

18 19
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Lock-Out Mode SLAVE
Slaves are connected to Smoke Vents on each oor.
DIP11 = ON
DIP12 = ON
When Slave Panel receives an alarm signal from Manual control Point or Smoke Detector:
- it enters Alarm, sets it’s motor output in open direction and transmit Fire on the bus.
- the Master enters Alarm (Flashes 1 Hz with Alarm led) and sets it’s motor output in open direction.
- the other Slaves enter lockout (Flashes 10 Hz with Alarm led) and set it’s motor output in close direction
the lockout slave’s can’t enter alarm mode from manual control point or smoke detector, before reset has
been executed.
Fireman’s Priority Switch:
Slaves can have a local Fireman’s Priority switch to override the lock-out mode.
The Fireman’s Override Switch will be able to control the slave panel whatever the alarm condition.
Pressing Open / Close buttons on the Fireman’s Priority Switch at the same time:
- reset is executed.
- the blue led will ash for 5 seconds.
- Open / Close buttons are disabled during this.
NOTE - A Slave unit in lockout mode will not respond to any inputs.
The only way of controlling the Slave unit in lock-out mode, is by using a Fireman’s Priority Switch.
27-02-2018
Actulux A/S ∙Haandvaerkervej 2 ∙DK 9560 Hadsund ∙Denmark ∙www.actulux.com
Phone: +45 98 57 40 90 ∙Email: info@actulux.com ∙VAT no.: DK28892195
ALARM ON ONE OF THE SLAVES
SLAVE EVENT
MASTER
ALL OTHER SLAVES
SMOKE FIRE MODE
FIRE mode
Lock-Out mode
MCP (BVT) FIRE MODE
FIRE mode
Lock-Out mode
MASTER S L AV E SL AV E S L AV E
MC P S M OKE MC P SM OK E MC P S M OKE MC P S M OKE
LO CK -OUTLO CK -OUT
MASTER S L AV E S LAV E S L AV E
MC P S M OKE MC P S M OKE MC P S M OKE MC P SM OKE
LO CK -OUTLO CK -OUT
Manual Control Point (MCP)
Smoke Detector
27-02-2018
Actulux A/S ∙Haandvaerkervej 2 ∙DK 9560 Hadsund ∙Denmark ∙www.actulux.com
Phone: +45 98 57 40 90 ∙Email: info@actulux.com ∙VAT no.: DK28892195
ALARM ON MASTER INPUT
MASTER EVENT
ALL SLAVES
SMOKE FIRE MODE
Lock-Out mode
MCP (BVT) FIRE MODE
FIRE mode
MASTER S L AV E SL AV E S L AV E
MC P S M OKE MC P SM OK E MC P S M OKE MC P S M OKE
MASTER S L AV E S LAV E S L AV E
MC P S M OKE MC P S M OKE MC P S M OKE MC P SM OKE
LO CK -OUTLO CK -OUTLO CK -OUT
Lock-Out Mode MASTER
Master is connected to the Smoke Vent.
DIP11 = ON
DIP12 = ON
When Master Panel receives an alarm signal from Manual control Point or Smoke Detector:
Only Master panel enters alarm mode sets it’s motor output in open direction
Fireman’s Priority Switch:
The Master can have a Fireman’s Priority Switch installed to overrule alarm mode.
The Fireman’s Override Switch will be able to control the panel whatever the alarm condition.
Pressing Open / Close buttons on the Fireman’s Priority Switch at the same time:
- reset is executed.
- the blue led will ash for 5 seconds.
- Open / Close buttons are disabled during this.
Manual Control Point (MCP)
Smoke Detector
-
-
Only mandatory
in UK!
Only mandatory
in UK!

20 21
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Spare parts
no.
Name of part Description
211062 Power supply 150W 27VDC MW Power supply 230VAC/27VDC for 5A control
211072 Power supply 200W 27VDC MW Power supply 230VAC/27VDC for 8A control
211210 Circuit breaker 13A Automatic fuse 13A / input terminal
800348 Batteri 12V/7.2Ah 151x65x98mm Battery for 24V / 5A controls / 8A controls
111789 Fire switch/reset IP40 Actulux Fire switch IP 40
111629 Replacement glass for BVT Replacement glass for re switch
111626 Fireswitch BVS in IP65 Box Fire switch built in IP65 box
111960 Rain sensor 250VAC / 24VDC Rain sensor closes everything when raining
111961 Wind and rain sensor 250VAC /24VDC Wind- and rain sensor closes everything when raining or
strong wind
111735 Heat detector+base 75 degree Heat detector 75 degrees temperature activation
111741 Heat detector+base 90 degree Heat detector 90 degrees temperature activation
111740 Smoke detector, optical Optical smoke detector
111943 Comfort switch w/ open indication Comfort switch Fuga complete with housing
111753 Comfort switch OPUS w housing Comfort switch Opus complete with housing
111758 Comfort switch FUGA w housing Comfort switch Fuga complete with housing
111760 Weekly timer 1 channel Weekly timer, can e.g. close everything in the evening
111761 Comfort sw.up/down OPUS IP44 Comfort switch Opus 44 white
111767 AUTO MAN switch OPUS w housin Switch Auto. man. OPUS white, activates room
thermostat or weekly timer
111770 Room thermostat RTR w.resis. Room thermostat for control of comfort ventilation
111933 Relay PCB extra Board with 2x2 extra relay outputs 30V 0.5A
122201 PCB SVM EI Daughter R2 Data logger for SVM EI
121611 Programming PCB f. SVM Central Interface for reading datalog
111892 Transmitter for Wind and Rain Wireless weather signal together with #111894
111894 Remote control w/receiver SVM Remote control for comfort
111980 Fireman’s Priority switch w/reset Fireman’s button, override the alarm and closes
Part nos. and accessories
(DK) YDEEVNEDEKLARATION IHT. FORORDNING NR. (EU) 305/2011)
(UK) DECLARATION OF PERFORMANCE ACCORDING TO REGULATION NO. (EU) 305/2011)
(D) LEISTUNGSERKLÄRUNG GEMÄSS DER VERORDNUNG NR. (EU) 305/2011)
(F) DECLARATION DES PERFORMANCES SELON RÈGLEMENT UE 305/2011
Produkt: Strømforsyning
Product: Power Supply
Produkt: Stromversorgung
Produit: Source de courant
Type/Type/Typ/Type:SVM/SVM EI/DFM 24V/5A & SVM/SVM EI/DFM 24V/8A
Formål: Strømforsyning til aktuator brugt i forbindelse med brandventilation
Purpose: Power supply for actuators used for SHEV
Verwendungszweck: Stromversorgung für Antriebe, die für Rauchabzug genutzt werden
Description du produit: Asservissement pour vérins électriques
Producenten:
Manufacture: Actulux A/S, Haandvaerkervej 2, 9560 Hadsund Denmark
Hersteller:
Usine de fabrication:
System for attestering og kontrol af ydeevne:/
System for attestation and verification of performance:/ SYSTEM 1
System zur Bescheinigung und Prüfung der Performance:/
Système(s) d'évaluation et de vérification de la constance des performances du produit:
Det bemyndigede organ 0402 RISE Research Institute of Sweden udførte den indledende inspektion af fabrikken og af dennes
egen produktionskontrol samt løbende overvågning, vurdering og evaluering af fabrikkens egen produktions- kontrol til SYSTEM 1, og
følgende vises:
The notified body 0402 RISE Research Institute of Sweden made the initial inspection of factory and of factory production
control, and ongoing monitoring, assessment and evaluation of factory production control to the SYSTEM 1 and the following is displayed:
Die notifizierte Stelle 0402 RISE Research Institute of Sweden hat die Erstinspektion des Werkes und der werks- eigenen
Produktionskontrolle sowie die laufenden Überwachung, Bewertung und Evaluierung der werkseigenen Produktionskontrolle nach dem
SYSTEM 1 vorgenommen und Folgendes ausgestellt:
L'organisme notifié RISE (Research Institute of Sweden) 0402 a procédé à l'inspection initiale de l'usine et à son propre contrôle
de production, ainsi qu'à la surveillance, à l'appréciation et à l'évaluation continues du contrôle de production propre à l'usine pour
SYSTEM 1. Les éléments suivants sont indiqués:
CERTIFICATE OF CONSTANCY OF PERFORMANCE
NO. 0402 – CPR – SC0354-13
Feature/Feature/Merkmal/
Fonctionnalité
Ydeevne/Performance/Leistung/
Performance
Specifikation/Specification/Spezifikation
Spécification
Environmental class 1 Class A EN 12101-10:2005/AC:2007
Ydeevnen af produktet i overensstemmelse med punkt 1 og 2 svarer til den deklarerede ydeevne for punkt 9.
Ansvarlig for udfærdigelse af denne ydeevnedeklaration er producenten der er henvist til i punkt 4.
Underskrevet på vegne af fabrikanten og navnet på fabrikanten af:
The performance of the product in accordance with point 1 and 2 corresponds to the declared performance for point 9.
Responsible for creating this declaration of performance is only the manufacturer referred to point 4.
Signed on behalf of the manufacturer and the name of the manufacturer of:
Die Leistung des Produkts gemäß den Punkt 1 und 2 entspricht der erklärten Leistung nach Punkt 9.
Verantwortlich für die Erstellung dieser Leistungserklärung ist allein der Hersteller gemäß Punkt 4.
Unterzeichnet für den Hersteller und im Namen des Herstellers von:
Les performances du produit identifié aux points §1 et §2 sont conformes aux performances déclarées indiquées au point §9.
La présente déclaration des performances est établie sous la seule responsabilité du fabricant identifié au point §4.
Signé au nom du fabricant et nom du fabricant de:
Hadsund d. 1 June 2020, Jens Buus,
Managing director
EN 12101-10:2005

22 23
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Service / Maintenance Record
System
ID:
Date Company Engineer Next Due Comments

24
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Technical specications SVM EI 24V-5A SVM EI 24V-8A
Power supply 230VAC / max. 1.2A 230VAC / max. 1.7A
Output supply 24-28VDC 24-28VDC
Motor outputs 1 pcs. (line detecton: 1-4 lines) 1 pcs. (line detecton: 1-4 lines)
Max. load 5A 8A
Operation temperture -15°C - +40°C -15°C - +40°C
Density IP54 IP54
Battery back-up (72h) Yes Ye s
Batteries 2 pcs. 12V/7Ah 2 pcs. 12V/7Ah
Dimensions (WxDxH) 238 x 113 x 286 mm 238 x 113 x 286 mm
Weight incl. batteries 7.5 kg 7.5 kg
Colour White front / Black indication label White front / Black black indication label
Fire groups 1 pcs. with line detect. / Max. power consumption for re switches (LED+buzzer) = 17.6mA=
approx. 8 re switches / 1 Fireman’s Priority Switch
Comfort groups 1 pcs. unlimited number of comfort switches
Detector (smoke/heat) input 1 pcs. with line detection / Max. power consumption for detectors = 2.2 mA = approx. 22 pcs. detectors.
Trigger point 15mA
Weather sensor input / close all Yes Ye s
Alarm output Yes - potential free contact, max. 48V / 0.5A Yes - potential free contact, max. 48V / 0.5A
Failure output Yes - potential free contact, max. 48V / 0.5A Yes - potential free contact, max. 48V / 0.5A
24V DC for external use 24V DC / max. 0.5A - at 230V operation 24V DC / max. 0.5A - at 230V operation
Bus communication Yes - connection of 2-35 pcs. control panels - line detection
Visual (LED) indication in front
panel
“OK” / “AC fault” / “Low battery” / “Line fault” / “Alarm” / “Comfort open”
Approvals / Conforms EN12101-10:2005 approved and certied - class A (double supply)
- envir. class 1 (to -15°C). Conform EN12101-9.
Primary supply: 27-28.5V DC rippel 600mw P/P
Secondary supply: 20-27V DC
Interruption time: less than 1.5 sec.
Low Voltage Directive 2014/35/EU
EN 61558-1:2006 (2nd edition), EN 61558-2-6, EN 61558-2-16 and EN 60335-1:2012 (4th edition)
Electrical equipment, accessories and packaging must be sent for recycling for the protection of
our environment!
Do not dispose electrical equipment with household waste!
According to European Guideline 2002/96 / EC on electrical waste, this must be disposed
separately and sent for recycling to protect our environment.