Brooks firetracker FT1020G3 FDCIE User guide

2022/01/06
FT1020G3 Quick Operation Guide Page 1of 6
FIRETRACKER FT1020G3 - QUICK OPERATION
GUIDE
1 - TO SILENCE PANEL BUZZER:
Press Button once to silence panel buzzer.
2 -TO SILENCE ALARM DEVICES:
Press Button once to silence all alarm devices, Occupant Warning System
(OWS) or sounders and wait for a few seconds.
Pressing the Button again will cause the alarms to resound.
3 - TO RESET FIRE ALARM:
IMPORTANT: Alarm devices must be silenced before pressing “Reset” button.
Press and hold the Button for 1 second until the Fire Alarm Panel starts its
reset sequence. The system will now automatically reset all alarms.
Alarms may re-trigger in the system if the alarm condition is still present. Wait for 30 seconds
and try again.
4 - TO DISABLE (ISOLATE) AN ACTIVE ALARM:
IMPORTANT: Alarm devices must be silenced before pressing “Disable” button.
Press Button to isolate device in alarm (H2/B1) –system will now illuminate
the LED. This zone / address point will remain disabled until
manual re-enabled via Menu H2/B1 button.

2022/01/06
FT1020G3 Quick Operation Guide Page 2of 6
5 - TO DISPLAY MORE THAN ONE ALARM :
When the more than one alarm are queued,red LEDs are illuminated.
Press the Button to see the additional Alarms.
6 - TO MANUALLY DISABLE (ISOLATE) A ZONE OR ZONE ADDRESS FROM
THE MENU:
1. Press Menu Button .
2. Select “Building Officer” Login then Key Enter Access Code.
3. Scroll to the Disable or re-enable menu (H2) by pressing or Button/s then press to
Accept
4. Scroll to Zone or Zone / address menu (B1 by pressing or Button/s then press to
Accept
5. Use the softkey to toggle between Zone 000
(disable Zone) and Zone 000 address 00 (dis
6. Type in the zone number or the zone / address number as required, then press to Accept. The
zone or zone address that is disabled will be indicated by “√”
7. Automatic Re-enable:
a. If Automatic re-enable time not required, scroll to highlight No then press to
Accept.
b. If Automatic re-enable is required, key in the time in hours : minutes (default is
currenttime + 3 Hours), scroll highlight to Yes then press to Accept.
8. If no more disablements required, press the button repeatedly back to main screen.

2022/01/06
FT1020G3 Quick Operation Guide Page 3of 6
7 - MANUALLY RE-ENABLE A ZONE OR ZONE ADDRESS FROM THE MENU:
1. Press Menu Button .
2. Select “Building Officer” Login then Key Enter Access Code.
3. Scroll to the Disable or re-enable menu (H2) by pressing or Button/s then press to
Accept
4. Scroll to Zone or Zone / address menu (B1 by pressing or Button/s then press to
Accept
5. The Disabled zone / zone address is indicated by “√”, press the softkey
to toggle between Disable and Re-enable list
6. If no more disablements required, press the button repeatedly back to main screen.
8 - TO CHECK EVENT LOG:
1. Press Menu Button .
2. Select “Building Officer” Login then Key Enter Access Code.
3. Scroll to the Present System Status menu (H4) by pressing or Button/s then press to
Accept
4. Scroll to Event Log menu (U7) by pressing or Button/s then press to Accept
5. Scroll by pressing or Button/s then press to Accept to select event Log: Alarm,
Interlocking Log, General event log.
6. If no furthers checks required, press the button repeatedly back to main screen.
9 –CHECK THE CURRENT SOFTWARE VERSION OF THE MAINBOARD
1. Press Menu Button .
2. Select “Building Officer” Login then Key Enter Access Code.
3. Scroll to the Present System Status menu (H4) by pressing or Button/s then press to
Accept
4. Scroll to Information menu (U8) by pressing or Button/s then press to Accept
5. If no furthers checks required, press the button repeatedly back to main screen.

2022/01/06
FT1020G3 Quick Operation Guide Page 4of 6
10 –TO ACKNOWLEDGE FAULT
1. Press Menu Button .
2. Select “Building Officer” Login then Key Enter Access Code.
3. Scroll to the FAULT ACKNOWLEDGE menu (H6) by pressing or Button/s then press
to Accept
4. Scroll to check the list of faults by pressing or Button/s then press to Accept
5. All faults must be individually acknowledged one by one.
6. When a fault is corrected before it has been acknowledged, the text "Serviced" is added after the
time, still has to be acknowledged to remove it on the display.
7. When a fault is corrected / serviced and acknowledged, it will disappear from the list (H6).
8. If no furthers checks required, press the button repeatedly back to main screen.
11 –TO CHECK FAULTS INFORMATION
1. Refer to Operation Manual FT1020G3 Rev 2.4, check for the fault and resolution
process.
FAULT: 24V for external equipment output x, Control Unit xx Page: 62
FAULT: 24V for routing equipment, Control Unit xx Page: 62
FAULT: 24V out, output unit xxxxxx Page: 62
FAULT: Alert annunciation unit xx, Control Unit xx Page: 62
FAULT: Battery not connected, Control Unit xx Page: 62
FAULT: Battery, technical number xxxxxx Page: 62
FAULT: Battery zone xxx address xx Page: 63
FAULT: Charger, Control Unit xx Page: 63
FAULT: Charging external power supply, Control Unit xx Page: 63
FAULT: Charging output unit xxxxxx Page: 63
FAULT: Checksum MMI program, Control Unit xx Page: 63
FAULT: Checksum system program, Control Unit xx Page: 63
FAULT: Control unit xx has no contact with Control Unit xx, network x Page: 63
FAULT: Cut-off loop x, Control Unit xx SCI nn <-> SCI nn Page: 63
FAULT: Detector removed zone xxx address xx Page: 64
FAULT: Earth fault (plus), Control Unit xx Page: 64
FAULT: Earth fault (minus), Control Unit xx Page: 64
FAULT: Earth fault, technical number xxxxxx Page: 64
FAULT: Expansion board x, Control Unit xx Page: 64
FAULT: Expansion board x, loop x, Control Unit xx Page: 64
FAULT: External fuses, Control Unit xx Page: 64
FAULT: External power supply, Control Unit xx Page: 64
FAULT: External presentation unit xx, Control Unit xx Page: 64
FAULT: Extinguishing system, Control Unit xx Page: 64
FAULT: Factory settings, Control Unit xx Page: 65
FAULT: Fan xx, technical number xxxxxx Page: 65
FAULT: FB Silence switch, Control Unit xx Page: 65
FAULT: Fire brigade panel xx, Control Unit xx Page: 65
FAULT: Fuse on COM loop x, Control Unit xx Page: 65
FAULT: High current, COM loop X, Control Unit xx Page: 65
FAULT: High current consumption, Control Unit xx Page: 65
FAULT: Interlocking input AAA-PP Page: 66
FAULT: Internal short circuit COM loop x, Control Unit xx Page: 66

2022/01/06
FT1020G3 Quick Operation Guide Page 5of 6
FAULT: L-C mixed COM loop x, Control Unit xx Page: 66
FAULT: Loop unit, Technical number xxxxxx Page: 66
FAULT: Loop unit zone: xxx address: xx Page: 66
FAULT: Loop unit zone: xxx address: xx and zone: yyy address:yy Page: 66
FAULT: Low battery capacity, Control Unit xx Page: 66
FAULT: Low battery capacity, Technical number xxxxxx Page: 67
FAULT: Low voltage, Control Unit xx Page: 67
FAULT: Low voltage, technical number xxxxxx Page: 67
FAULT: Mains, Control Unit xx Page: 67
FAULT: Mains, external power supply, Control Unit xx Page: 67
FAULT: Mains, technical number xxxxxx Page: 67
FAULT: Multiple faults, COM-loop x, Control Unit xx Page: 68
FAULT: Network cables mixed, Control Unit xx Page: 68
FAULT: No connection with MMI board, Control Unit xx Page: 68
FAULT: No reply, Expansion Board x, Control Unit xx Page: 68
FAULT: No reply Expansion Board x loop x, Page: 68
FAULT: No reply, alert annunciation unit xx, Control Unit xx Page: 68
FAULT: No reply, external presentation unit xx, Control Unit xx Page: 68
FAULT: No reply Loop unit xxxxxx Page: 69
FAULT: No reply zone: xxx address: xx Page: 69
FAULT: Printer, Control Unit xx Page: 69
FAULT: Read / write site data (SSW), Control Unit xx Page: 69
FAULT: Restart Control Unit nn, Page: 69
FAULT: Sensor zone: xxx address: xx, technical number xxxxxx Page: 70
FAULT: Short circuit loop x, Control Unit xx, SCInn<->SCInn Page: 70
FAULT: Site specific data (SSD), Control Unit xx Page: 70
FAULT: Site specific data, alert annunciation unit xx, Control Unit xx Page: 70
FAULT: Site specific data, external presentation unit xx, Control Unit Page: 70
FAULT: Supervised input x Expansion Board x, Control Unit xx Page: 71
FAULT: Supervised input x, technical number xxxxxx Page: 71
FAULT: Supervised output x, Control Unit xx Page: 71
FAULT: Supervised output x Expansion Board x, Control Unit xx Page: 71
FAULT: Supervised output x, technical number xxxxxx Page: 71
FAULT: Temperature sensor, Control Unit xx Page: 72
FAULT: TLON-board (Network 0), Control Unit xx Page: 72
FAULT: TLON-board (Network 1), Control Unit xx Page: 72
FAULT: Wrong information, Control Unit xx Page: 72
FAULT: Wrong type Expansion Board x loop x, Control Unit xx Page: 72
FAULT: Wrong type, Expansion Board x, Control Unit xx Page: 72
FAULT: Wrong type of unit xxxxxx Page: 72
FAULT: Wrong type of unit zone: xxx address: xx Page: 73
FAULT: Zone Line Input, Zone xxx Address xx Page: 73
FAULT: Zone Line Input, zone: xxx address: xx Page: 73
No contact with main board Page: 73
(External fault; User programmable text) Page: 73
12 –EBLWin SOFTWARE INSTALLATION to PC
1. Refer to Operation Manual FT1020G3, PAGE 80.
2. Needed Hardware
a. EBLWin key 5094
b. USB to Serial Converter to USB adapter
c. Laptop with Win7 - Win10

2022/01/06
FT1020G3 Quick Operation Guide Page 6of 6
13 –OPERATION MANUAL FT1020G3 Rev 2.4
Scan QR code to Search instructions and other relevant operational
procedures.
Software download
Restart
Perform Monthly test (H1)
Disable or re-enable (H2)
Set Calendar and Clock (H3)
Present System Status (H4)
Service (H5)
Acknowledge Faults (H6)
Perform Zone Test (Test Mode) (H7)
Maintenance (H8)
Interlocking Outputs and Inputs (H9)
Change Password (H10)
Other manuals for firetracker FT1020G3 FDCIE
1
Popular Control Panel manuals by other brands

Integrated Technical Vision
Integrated Technical Vision DLK640Plus Dlk640plus

Arrowhead Alarm Products
Arrowhead Alarm Products ESL-2 Installation & programming guide

Rinnai
Rinnai RHFE-556 FM Service manual

Balboa
Balboa SUV M-7 Reference card

Mircom
Mircom FA-300-6L Series Installation and operation manual

weintek
weintek MT6071iP Series Installation instruction